Центральные процессоры

6ES7 211-0AA23-0XB0

6ES7 211-0BA23-0XB0

6ES7 212-1AB23-0XB0

6ES7 212-1BB23-0XB0

Supply voltages

Rated value

    • 24 V DC

Yes

Yes

    • permissible range, lower limit (DC)

20.4 V

20.4 V

    • permissible range, upper limit (DC)

28.8 V

28.8 V

    • 120 V AC

Yes

Yes

    • 230 V AC

Yes

Yes

    • permissible range, lower limit (AC)

85 V

85 V

    • permissible range, upper limit (AC)

264 V

264 V

    • permissible frequency range, lower limit

47 Hz

47 Hz

    • permissible frequency range, upper limit

63 Hz

63 Hz

Voltages and currents

Load voltage L+

    • Rated value (DC)

24 V

24 V

24 V

24 V

    • permissible range, lower limit (DC)

20.4 V

5 V

20.4 V

5 V

    • permissible range, upper limit (DC)

28.8 V

30 V

28.8 V

30 V

Load voltage L1

    • Rated value (AC)

100 V; 100 to 230 V AC

100 V; 100 to 230 V AC

    • permissible range, lower limit (AC)

5 V

5 V

    • permissible range, upper limit (AC)

250 V

250 V

    • permissible frequency range, lower limit

47 Hz

47 Hz

    • permissible frequency range, upper limit

63 Hz

63 Hz

Current consumption

  • Inrush current, max.

10 A; at 28.8 V

20 A; at 264 V

10 A; at 28.8 V

20 A; at 264 V

  • from supply voltage L+, max.

450 mA; 80 to 450 mA

500 mA; 85 to 500 mA, output current for expansion modules (5 V DC) 340 mA

  • from supply voltage L1, max.

120 mA; 15 to 60 mA (240 V), 30 to 120 mA (120 V); output current for expansion modules (5 V DC) 340 mA

140 mA; 20 to 70 mA (240 V), 40 to 140 mA (120 V); output current for expansion modules (5 V DC) 340 mA

back-up battery

    • Backup time

50 h; (min. 8 h at 40 °C); 200 days (typ.) with optional battery module

50 h; (min. 8 h at 40 °C); 200 days (typ.) with optional battery module

50 h; (min. 8 h at 40 °C); 200 days (typ.) with optional battery module

50 h; (min. 8 h at 40 °C); 200 days (typ.) with optional battery module

Memory/backup

Memory

    • Number of memory modules (optional)

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

  • Data memory and program memory

    • Data memory, max.

2 KByte

2 KByte

2 KByte

2 KByte

    • Program memory, max.

4 KByte

4 KByte

4 KByte

4 KByte

Backup

    • available

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

CPU/processing times

  • for bit instruction, max.

0.22 µs

0.22 µs

0.22 µs

0.22 µs

Timers/counters and their retentive characteristics

S7 counter

    • Number

256

256

256

256

  • of which retentive with battery

    • adjustable

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

    • lower limit

1

1

1

1

    • upper limit

256

256

256

256

  • Counting range

    • lower limit

0

0

0

0

    • upper limit

32,767

32,767

32,767

32,767

S7 times

    • Number

256

256

256

256

  • of which retentive with battery

    • adjustable

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

    • upper limit

64

64

64

64

  • Timing range

    • lower limit

1 ms

1 ms

1 ms

1 ms

    • upper limit

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

Data areas and their retentive characteristics

Flags

    • Number

32 Byte

32 Byte

32 Byte

32 Byte

    • adjustable retentivity

Yes; M0.0 to M31.7

Yes; M0.0 to M31.7

Yes; M0.0 to M31.7

Yes; M0.0 to M31.7

    • of which retentive with battery

0 to 255, via super capacitor or battery, adjustable

0 to 255, via super capacitor or battery, adjustable

0 to 255, via super capacitor or battery, adjustable

0 to 255, via super capacitor or battery, adjustable

    • of which retentive without battery

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

Configuration

  • Connectable programming devices/PCs

SIMATIC PG/PC, Standard PC

SIMATIC PG/PC, Standard PC

SIMATIC PG/PC, Standard PC

SIMATIC PG/PC, Standard PC

  • Central units/expansion units, max.

2 expansion modules. Only expansion modules of the S7-22x series can be used. Because of the limited output current, the use of expansion modules may be subject to restrictions.

2 expansion modules. Only expansion modules of the S7-22x series can be used (because of the limited output current, the use of expansion modules may be subject to restrictions.)

I/O expansions

    • Analog inputs/outputs, max.

10; max. 8 inputs and 2 outputs (EM) or max. 0 inputs and 4 outputs (EM)

10; max. 8 inputs and 2 outputs (EM) or max. 0 inputs and 4 outputs (EM)

    • Digital inputs/outputs, max.

78; max. 40 inputs and 38 outputs (CPU+EM)

78; max. 40 inputs and 38 outputs (CPU+EM)

    • AS interface inputs/outputs, max.

31; AS interface slaves (CP 243-2)

31; AS interface slaves (CP 243-2)

Connection system

  • Pluggable I/O terminals

No

No

No

No

1st interface

  • Type of interface

integrated RS 485 interface

integrated RS 485 interface

integrated RS 485 interface

integrated RS 485 interface

  • Physical

RS 485

RS 485

RS 485

RS 485

Functionality

    • MPI

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

    • PPI

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

    • Serial data transmission

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

MPI

    • Transmission rates, max.

187.5 kBit/s

187.5 kBit/s

187.5 kBit/s

187.5 kBit/s

    • Transmission rates, min.

19.2 kBit/s

19.2 kBit/s

19.2 kBit/s

19.2 kBit/s

CPU/ programming

Programming language

    • KOP

Yes

Yes

Yes

Yes

    • FUP

Yes

Yes

Yes

Yes

    • AWL

Yes

Yes

Yes

Yes

  • Instruction set

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

  • User program protection/password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

  • Program execution

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

  • Program organization

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

  • Number of sub-programs, max.

64

64

64

64

Digital inputs

  • Number of digital inputs

6; integrated

6; integrated

8

8

Length of cable

    • Length of cable shielded, max

500 m; Standard input: 500m, fast counters: 50m

500 m; Standard input: 500m, fast counters: 50m

500 m; Standard input: 500m, fast counters: 50m

500 m; Standard input: 500m, fast counters: 50m

    • Length of cable unshielded, max

300 m; not for high-speed signals

300 m; not for high-speed signals

300 m; not for high-speed signals

300 m; not for high-speed signals

  • m/p reading

Yes; optional, per group

Yes; optional, per group

Yes; optional, per group

Yes; optional, per group

Input voltage

    • Rated value, DC

24 V

24 V

24 V

24 V

    • for signal "0"

0 to 5 V

0 to 5 V

0 to 5 V

0 to 5 V

    • for signal "1"

min. 15 V

min. 15 V

min. 15 V

min. 15 V

Input current

    • for 1 signal, typical

2.5 mA

2.5 mA

2.5 mA

2.5 mA

Input delay (at rated value of the input voltage)

  • For standard inputs

    • Parameterizable

Yes; all

Yes; all

Yes; all

Yes; all

    • at 0 after 1, min.

0.2 ms

0.2 ms

0.2 ms

0.2 ms

    • at 0 after 1, max.

12.8 ms

12.8 ms

12.8 ms

12.8 ms

  • for alarm inputs

    • parameterizable

Yes; I0.0 to I0.3

Yes; I0.0 to I0.3

Yes; I0.0 to I0.3

Yes; I0.0 to I0.3

  • for counters/technological functions

    • parameterizable

Yes; (E0.0 to E0.5) 30 kHz

Yes; (E0.0 to E0.5) 30 kHz

Yes; (E0.0 to E0.5) 30 kHz

Yes; (E0.0 to E0.5) 30 kHz

Digital outputs

  • Number of digital outputs

4; Transistor

4; Relay

6; Transistor

6; Relay

  • Length of cable shielded, max.

500 m

500 m

500 m

500 m

  • Length of cable unshielded, max.

150 m

150 m

150 m

150 m

  • Short-circuit protection of the output

No; provided externally

No; provided externally

No; provided externally

No; provided externally

  • Limitation of voltage induced on circuit interruption to

1 W

1 W

Switching capacity of the outputs

    • at resistive load, max.

0.75 A

2 A

0.75 A

2 A

    • at lamp load, max.

5 W

30 W DC, 200 W AC

5 W

30 W DC, 200 W AC

Output voltage

    • for 1 signal

20 V DC

L+/L1

20 V DC

L+/L1

Output current

    • for 1 signal rated value

750 mA

2 A

750 mA

2 A

    • for 0 signal residual current, max.

0.1 mA

0 mA

10 A

0 mA

Output delay at resistive load

    • "0" after "1", max.

15 µs; of standard outputs, max. (A0.2 to A0.3) 15 µs; of pulse outputs, max. (A0.0 to A0.1) 2 µs

10 ms; all outputs

15 µs; of standard outputs, max. (A0.2 to A0.5) 15 µs; of pulse outputs, max. (A0.0 to A0.1) 2 µs

10 ms; all outputs

    • "1" after "0", max.

130 µs; of standard outputs, max. (A0.2 to A0.3) 100 µs; of pulse outputs, max. (A0.0 to A0.1) 10 µs

10 ms; all outputs

130 µs; of standard outputs, max. (A0.2 to A0.5) 100 µs; of pulse outputs, max. (A0.0 to A0.1) 10 µs

10 ms; all outputs

Parallel switching of 2 outputs

    • to increase power

Yes

No

Yes

No

Switching frequency

    • of pulse outputs, at resistive load, max.

20 kHz; A0.0 to A0.1

20 kHz; A0.0 to A0.1

Summation current of the outputs (per group)

    • up to 40 °C, max.

3 A

6 A

4.5 A

6 A

    • horizontal installation, up to 55 °C, max.

3 A

6 A

4.5 A

6 A

Relay outputs

  • Number of operating cycles

10,000,000; mechanical 10 million, at rated load voltage 100,000

10,000,000; mechanical 10 million, at rated load voltage 100,000

Analog inputs

  • Number of analog potentiometers

1; Analog potentiometer; resolution 8 bits

1; Analog potentiometer; resolution 8 bits

1; Analog potentiometer; resolution 8 bits

1; Analog potentiometer; resolution 8 bits

Sensor supply

24 V - sensor supply

    • 24 V

Yes; permissible range: 15.4 to 28.8 V

Yes; permissible range: 20.4 to 28.8 V

Yes; permissible range: 15.4 to 28.8 V

Yes; permissible range: 20.4 to 28.8 V

    • Short-circuit protection

Yes; electronic at 600 mA

Yes; electronic at 600 mA

Yes; electronic at 600 mA

Yes; electronic at 600 mA

    • Output current, max.

180 mA

180 mA

180 mA

180 mA

Sensor

Connectable encoders

    • 2-wire BEROS

Yes

Yes

Yes

Yes

    • permissible closed-circuit current (2-wire BEROS), max.

1 mA

1 mA

1 mA

1 mA

Integral functions

  • Number of counters

4; fast counters (each 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

4; fast counters (each 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

4; fast counters (each 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

4; fast counters (each 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

  • Count frequency (counters) max.

30 kHz

30 kHz

30 kHz

30 kHz

  • Number of alarm inputs

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

  • Number of pulse outputs

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

  • Cut-off frequency (pulse)

20 kHz

20 kHz

20 kHz

20 kHz

Potentials/ electrical isolation

Digital output functions

    • between the channels

Yes; Optocoupler

Yes; Relay

Yes; Optocoupler

Yes; Relay

    • between the channels, in groups of

4

1 and 3

6

3

Digital input functions

    • between the channels

Yes

Yes

Yes

Yes

    • between the channels, in groups of

2 and 4

2 and 4

4

4

Permissible potential difference

  • between different circuits

500 V DC between 24 V DC and 5 V DC

500 V DC between 24 V DC and 5 V DC; 1500 V AC between 24 V DC and 230 V AC

500 V DC between 24 V DC and 5 V DC

500 V DC between 24 V DC and 5 V DC; 1500 V AC between 24 V DC and 230 V AC

Environmental requirements

  • Environmental conditions

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

Operating temperature

    • vertical mounting, min.

0 °C

0 °C

0 °C

0 °C

    • vertical mounting, max.

45 °C

45 °C

45 °C

45 °C

    • horizontal mounting, min.

0 °C

0 °C

0 °C

0 °C

    • horizontal mounting, max.

55 °C

55 °C

55 °C

55 °C

Air pressure

    • permissible range, min

860 hPa

860 hPa

860 hPa

860 hPa

    • permissible range, max

1,080 hPa

1,080 hPa

1,080 hPa

1,080 hPa

Relative humidity

    • Operation, min.

5 %

5 %

5 %

5 %

    • Operation, max.

95 %; RH stressing level 2 in accordance with IEC 1131-2

95 %; RH stressing level 2 in accordance with IEC 1131-2

95 %; RH stressing level 2 in accordance with IEC 1131-2

95 %; RH stressing level 2 in accordance with IEC 1131-2

Degree of protection and class of protection

    • IP 20

Yes

Yes

Yes

Yes

Dimensions and weight

  • Weight, approx.

270 g

310 g

270 g

310 g

  • Width

90 mm

90 mm

90 mm

90 mm

  • Height

80 mm

80 mm

80 mm

80 mm

  • Depth

62 mm

62 mm

62 mm

62 mm


6ES7 214-1AD23-0XB0

6ES7 214-1BD23-0XB0

6ES7 214-2AD23-0XB0

6ES7 214-2BD23-0XB0

6ES7 216-2AD23-0XB0

6ES7 216-2BD23-0XB0

Supply voltages

Rated value

    • 24 V DC

Yes

Yes

Yes

    • permissible range, lower limit (DC)

20.4 V

20.4 V

20.4 V

    • permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

    • 120 V AC

Yes

Yes

Yes

    • 230 V AC

Yes

Yes

Yes

    • permissible range, lower limit (AC)

85 V

85 V

85 V

    • permissible range, upper limit (AC)

264 V

264 V

264 V

    • permissible frequency range, lower limit

47 Hz

47 Hz

47 Hz

    • permissible frequency range, upper limit

63 Hz

63 Hz

63 Hz

Voltages and currents

Load voltage L+

    • Rated value (DC)

24 V

24 V

24 V

24 V

24 V

24 V

    • permissible range, lower limit (DC)

20.4 V

5 V

20.4 V

5 V

20.4 V

5 V

    • permissible range, upper limit (DC)

28.8 V

30 V

28.8 V

30 V

28.8 V

30 V

Load voltage L1

    • Rated value (AC)

100 V; 100 to 230 V AC

100 V; 100 to 230 V AC

100 V; 100 to 230 V AC

    • permissible range, lower limit (AC)

5 V

5 V

5 V

    • permissible range, upper limit (AC)

250 V

250 V

250 V

    • permissible frequency range, lower limit

47 Hz

47 Hz

47 Hz

    • permissible frequency range, upper limit

63 Hz

63 Hz

63 Hz

Current consumption

  • Inrush current, max.

12 A; at 28.8 V

20 A; at 264 V

12 A; at 28.8 V

20 A; at 264 V

10 A; at 28.8 V

20 A; at 264 V

  • from supply voltage L+, max.

700 mA; 110 to 700 mA, output current for expansion modules (5 V DC) 660 mA

900 mA; 120 to 900 mA, output current for expansion modules (5 V DC) 660 mA

1,050 mA; 150 to 1050 mA, output current for expansion modules (5 V DC) 1000 mA

  • from supply voltage L1, max.

200 mA; 30 to 100 mA (240 V), 60 to 200 mA (120 V); output current for expansion modules (5 V DC) 600 mA

220 mA; 35 to 100 mA (240 V), 70 to 220 mA (120 V); output current for expansion modules (5 V DC) 600 mA

320 mA; 40 to 160 mA (240 V), 80 to 320 mA (120 V); output current for expansion modules (5 V DC) 1000 mA

back-up battery

    • Backup time

100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module

100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module

100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module

100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module

100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module

100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module

Memory/backup

Memory

    • Number of memory modules (optional)

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

1; pluggable memory module, content identical to integral EEPROM, in addition, recipes, data logs and other files can be saved.

  • Data memory and program memory

    • Data memory, max.

8 KByte

8 KByte

10 KByte

10 KByte

10 KByte

10 KByte

    • Program memory, max.

12 KByte; 8 Kbytes for active run-time edit

12 KByte; 8 Kbytes for active run-time edit

16 KByte; 12 Kbytes for active run-time edit

16 KByte; 12 Kbytes for active run-time edit

24 KByte; 16 Kbytes with active run-time edit

24 KByte; 16 Kbytes with active run-time edit

Backup

    • available

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

Yes; Program: entire program maintenance-free in integral EEPROM, programmable via CPU; data: entire DB 1 loaded from PG/PC maintenance-free in integral EEPROM, current values of DB 1 in RAM, retentive flags, timers, counters etc., maintenance free via super capacitor; optional battery

CPU/processing times

  • for bit instruction, max.

0.22 µs

0.22 µs

0.22 µs

0.22 µs

0.22 µs

0.22 µs

Timers/counters and their retentive characteristics

S7 counter

    • Number

256

256

256

256

256

256

  • of which retentive with battery

    • adjustable

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

    • lower limit

1

1

1

1

1

1

    • upper limit

256

256

256

256

256

256

  • Counting range

    • lower limit

0

0

0

0

0

0

    • upper limit

32,767

32,767

32,767

32,767

32,767

32,767

S7 times

    • Number

256

256

256

256

256

256

  • of which retentive with battery

    • adjustable

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

Yes; via super capacitor or battery

    • upper limit

64

64

64

64

64

64

  • Timing range

    • lower limit

1 ms

1 ms

1 ms

1 ms

1 ms

1 ms

    • upper limit

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

54 min; 4 times, 1 ms to 30 s 16 times, 10 ms to 5 min 236 times, 100 ms to 54 min

Data areas and their retentive characteristics

Flags

    • Number

32 Byte

32 Byte

32 Byte

32 Byte

32 Byte

32 Byte

    • adjustable retentivity

Yes; M0.0 to M31.7

Yes; M0.0 to M31.7

Yes; M0.0 to M31.7

Yes; M0.0 to M31.7

Yes; M0.0 to M31.7

Yes; M0.0 to M31.7

    • of which retentive with battery

0 to 255, via super capacitor or battery, adjustable

0 to 255, via super capacitor or battery, adjustable

0 to 255, via super capacitor or battery, adjustable

0 to 255, via super capacitor or battery, adjustable

0 to 255, via super capacitor or battery, adjustable

0 to 255, via super capacitor or battery, adjustable

    • of which retentive without battery

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

0 to 112 in EEPROM, adjustable

Configuration

  • Connectable programming devices/PCs

SIMATIC PG/PC, Standard PC

SIMATIC PG/PC, Standard PC

SIMATIC PG/PC, Standard PC

SIMATIC PG/PC, Standard PC

SIMATIC PG/PC, Standard PC

SIMATIC PG/PC, Standard PC

  • Central units/expansion units, max.

7 expansion modules. Only expansion modules of the S7-22x series can be used. (Because of the limited output current, the use of expansion modules may be subject to restrictions.)

7 expansion modules. Only expansion modules of the S7-22x series can be used. (Because of the limited output current, the use of expansion modules may be subject to restrictions.)

7 expansion modules. Only expansion modules of the S7-22x series can be used. (Because of the limited output current, the use of expansion modules may be subject to restrictions.)

7 expansion modules. Only expansion modules of the S7-22x series can be used. (Because of the limited output current, the use of expansion modules may be subject to restrictions.)

7 expansion modules. Only expansion modules of the S7-22x series can be used. (Because of the limited output current, the use of expansion modules may be subject to restrictions.)

7 expansion modules. Only expansion modules of the S7-22x series can be used. (Because of the limited output current, the use of expansion modules may be subject to restrictions.)

I/O expansions

    • Analog inputs/outputs, max.

35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM)

35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM)

38; 2 on board inputs and one output, in addition
max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM)

38; 2 on board inputs and one output, in addition
max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM)

35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM)

35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM)

    • Digital inputs/outputs, max.

168; max. 94 inputs and 74 outputs (CPU+EM)

168; max. 94 inputs and 74 outputs (CPU+EM)

168; max. 94 inputs and 74 outputs (CPU+EM)

168; max. 94 inputs and 74 outputs (CPU+EM)

148; max. 128 inputs and 120 outputs (CPU+EM)

148; max. 128 inputs and 120 outputs (CPU+EM)

    • AS interface inputs/outputs, max.

62; AS interface A/B slaves (CP 243-2)

62; AS interface A/B slaves (CP 243-2)

62; AS interface A/B slaves (CP 243-2)

62; AS interface A/B slaves (CP 243-2)

62; AS interface A/B slaves (CP 243-2)

62; AS interface A/B slaves (CP 243-2)

Connection system

  • Pluggable I/O terminals

Yes

Yes

Yes

Yes

Yes

Yes

1st interface

  • Type of interface

integrated RS 485 interface

integrated RS 485 interface

integrated RS 485 interface

integrated RS 485 interface

integrated RS 485 interface

integrated RS 485 interface

  • Physical

RS 485

RS 485

RS 485

RS 485

RS 485

RS 485

Functionality

    • MPI

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

    • PPI

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

    • Serial data transmission

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

MPI

    • Transmission rates, max.

187.5 kBit/s

187.5 kBit/s

187.5 kBit/s

187.5 kBit/s

187.5 kBit/s

187.5 kBit/s

    • Transmission rates, min.

19.2 kBit/s

19.2 kBit/s

19.2 kBit/s

19.2 kBit/s

19.2 kBit/s

19.2 kBit/s

2nd interface

  • Type of interface

integrated RS 485 interface

integrated RS 485 interface

integrated RS 485 interface

integrated RS 485 interface

  • Physical

RS 485

RS 485

RS 485

RS 485

Functionality

    • MPI

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

Yes; as MPI Slave for data exchange with MPI Masters (S7-300/S7-400-CPUs, OPs, TDs, Push Button Panels); internal S7-200 CPU/CPU communication is limited in the MPI network; transmission rates 19.2/187.5 kbit/s

    • Functionality PPI

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

Yes; with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200 internal CPU/CPU communication; transmission rates 9.6/19.2/187.5 kbit/s

    • Serial data transmission

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

Yes; as a freely programmable interface with an interrupt option for serial data transmission with external units with ASCII ptotocol baud rates: 0.3/0.6/1.2/2.4/4.8/9.6/19.2/38.4 kbit/s; at 1.2 to 38.4 kbit/s, the PC/PPI cable can be used as an RS232/RS485 converter

MPI

    • Transmission rate, max.

187.5 kBit/s

187.5 kBit/s

187.5 kBit/s

187.5 kBit/s

    • Transmission rate, min.

19.2 kBit/s

19.2 kBit/s

19.2 kBit/s

19.2 kBit/s

CPU/ programming

Programming language

    • KOP

Yes

Yes

Yes

Yes

Yes

Yes

    • FUP

Yes

Yes

Yes

Yes

Yes

Yes

    • AWL

Yes

Yes

Yes

Yes

Yes

Yes

  • Instruction set

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

Bit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, integer math instructions, floating-point math instructions, numeric functions, move instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions

  • User program protection/password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

Yes; 3-stage password protection

  • Program execution

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

free cycle (OB 1), interrupt-driven, time-driven (1 to 255 ms)

  • Program organization

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

1 OB, 1 DB, 1 SDB subprograms with/without parameter transfer

  • Number of sub-programs, max.

64

64

64

64

64

64

Digital inputs

  • Number of digital inputs

14

14

14

14

24

24

Length of cable

    • Length of cable shielded, max

500 m; Standard input: 500m, fast counters: 50m

500 m; Standard input: 500m, fast counters: 50m

500 m; Standard input: 500m, fast counters: 50m

500 m; Standard input: 500m, fast counters: 50m

500 m; Standard input: 500m, fast counters: 50m

500 m; Standard input: 500m, fast counters: 50m

    • Length of cable unshielded, max

300 m; not for high-speed signals

300 m; not for high-speed signals

300 m; not for high-speed signals

300 m; not for high-speed signals

300 m; not for high-speed signals

300 m; not for high-speed signals

  • m/p reading

Yes; optional, per group

Yes; optional, per group

Yes; optional, per group

Yes; optional, per group

Yes; optional, per group

Yes; optional, per group

Input voltage

    • Rated value, DC

24 V

24 V

24 V

24 V

24 V

24 V

    • for signal "0"

0 to 5 V

0 to 5 V

0 to 5 V; 0 to 1V (I0.3 to I0.5)

0 to 5 V
0 to 1V (I0.3 to I0.5)

0 to 5 V

0 to 5 V

    • for signal "1"

min. 15 V

min. 15 V

min. 15 V; at least 4V (I0.3 to I0.5)

min. 15 V
at least 4V (I0.3 to I0.5)

min. 15 V

min. 15 V

Input current

    • for 1 signal, typical

2.5 mA

2.5 mA

2.5 mA; 8 mA for I0.3 to I0.5

2.5 mA; 8 mA for I0.3 to I0.5

2.5 mA

2.5 mA

Input delay (at rated value of the input voltage)

  • For standard inputs

    • Parameterizable

Yes; all

Yes; all

Yes; all

Yes; all

Yes; all

Yes; all

    • at 0 after 1, min.

0.2 ms

0.2 ms

0.2 ms

0.2 ms

0.2 ms

0.2 ms

    • at 0 after 1, max.

12.8 ms

12.8 ms

12.8 ms

12.8 ms

12.8 ms

12.8 ms

  • for alarm inputs

    • parameterizable

Yes; I0.0 to I0.3

Yes; I0.0 to I0.3

Yes; I0.0 to I0.3

Yes; I0.0 to I0.3

Yes; I0.0 to I0.3

Yes; I0.0 to I0.3

  • for counters/technological functions

    • parameterizable

Yes; (E0.0 to E1.5) 30 kHz

Yes; (E0.0 to E1.5) 30 kHz

Yes; (E0.0 to E1.5) up to 200 kHz

Yes; (E0.0 to E1.5) up to 200 kHz

Yes; (E0.0 to E1.5) 30 kHz

Yes; (E0.0 to E1.5) 30 kHz

Digital outputs

  • Number of digital outputs

10; Transistor

10; Relay

10; Transistor

10; Relay

16; Transistor

16; Relay

  • Length of cable shielded, max.

500 m

500 m

500 m

500 m

500 m

500 m

  • Length of cable unshielded, max.

150 m

150 m

150 m

150 m

150 m

150 m

  • Short-circuit protection of the output

No; provided externally

No; provided externally

No; provided externally

No; provided externally

No; provided externally

No; provided externally

  • Limitation of voltage induced on circuit interruption to

1 W

1 W

1 W

Switching capacity of the outputs

    • at resistive load, max.

0.75 A

2 A

0.75 A

2 A

0.75 A

2 A

    • at lamp load, max.

5 W

200 W; 30 W DC, 200 W AC

5 W

200 W; 30 W DC, 200 W AC

5 W

200 W; 30 W DC, 200 W AC

Output voltage

    • for 1 signal

20 V DC

L+/L1

L+ minus 0.4V (5V/20,4V for A0.0 to A0.4; 20,4V A0.5 to A1.1)

L+/L1

20 V DC

L+/L1

Output current

    • for 1 signal rated value

750 mA

2 A

750 mA

2 A

750 mA

2 A

    • for 0 signal residual current, max.

10 A

0 mA

10 A

0 mA

10 A

0 mA

Output delay at resistive load

    • "0" after "1", max.

15 µs; of the standard outputs, max. (A0.2 to A1.1) 2 µs; of the pulse outputs, max. (A0.0 to A0.1) 2 µs

10 ms; all outputs

15 µs; of the standard outputs, max. (A0.2 to A1.1) 15 µs; of the pulse outputs, max. (A0.0 to A0.1) 0.5 µs

10 ms; all outputs

15 µs; of the standard outputs, max. (A0.2 to A1.1) 2 µs; of the pulse outputs, max. (A0.0 to A0.1) 2 µs

10 ms; all outputs

    • "1" after "0", max.

130 µs; of the standard outputs, max. (A0.2 to A1.1) 10 µs; of the pulse outputs, max. (A0.0 to A0.1) 10 µs

10 ms; all outputs

130 µs; of the standard outputs, max. (A0.2 to A1.1) 130 µs; of the pulse outputs, max. (A0.0 to A0.1) 1.5 µs

10 ms; all outputs

130 µs; of the standard outputs, max. (A0.2 to A1.1) 10 µs; of the pulse outputs, max. (A0.0 to A0.1) 10 µs

10 ms; all outputs

Parallel switching of 2 outputs

    • to increase power

Yes

No

Yes

No

Yes

No

Switching frequency

    • of pulse outputs, at resistive load, max.

20 kHz; A0.0 to A0.1

1 Hz

100 kHz; A0.0 to A0.1

1 Hz

20 kHz; A0.0 to A0.1

1 kHz

Summation current of the outputs (per group)

    • up to 40 °C, max.

6 A

10 A

3.75 A

10 A

6 A

10 A

    • horizontal installation, up to 55 °C, max.

6 A

10 A

3.75 A

10 A

6 A

10 A

Relay outputs

  • Number of operating cycles

10,000,000; mechanical 10 million, at rated load voltage 100,000

10,000,000; mechanical 10 million, at rated load voltage 100,000

10,000,000; mechanical 10 million, at rated load voltage 100,000

Analog inputs

  • Number of analog potentiometers

2; Analog potentiometer; resolution 8 bits

2; Analog potentiometer; resolution 8 bits

2; Analog potentiometer; resolution 8 bits

2; Analog potentiometer; resolution 8 bits

2; Analog potentiometer; resolution 8 bits

2; Analog potentiometer; resolution 8 bits

Sensor supply

24 V - sensor supply

    • 24 V

Yes; permissible range: 15.4 to 28.8 V

Yes; permissible range: 20.4 to 28.8 V

Yes; permissible range: 15.4 to 28.8 V

Yes; permissible range: 20.4 to 28.8 V

Yes; permissible range: 15.4 to 28.8 V

Yes; permissible range: 20.4 to 28.8 V

    • Short-circuit protection

Yes; electronic at 280 mA

Yes; electronic at 280 mA

Yes; electronic at 280 mA

Yes; electronic at 280 mA

Yes; electronic at 400 mA

Yes; electronic at 400mA

    • Output current, max.

280 mA

280 mA

280 mA

280 mA

400 mA

400 mA

Sensor

Connectable encoders

    • 2-wire BEROS

Yes

Yes

Yes

Yes

Yes

Yes

    • permissible closed-circuit current (2-wire BEROS), max.

1 mA

1 mA

1 mA

1 mA

1 mA

1 mA

Integral functions

  • Number of counters

6; fast counters (each 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 4 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

6; fast counters (each 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 4 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

6; fast counters (2 to 200 kHz and 4 to 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 1 to 100 kHz and 3 to 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

6; fast counters (2 to 200 kHz and 4 to 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 1 to 100 kHz and 3 to 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

6; fast counters (each 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 4 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

6; fast counters (each 30 kHz), 32 bits (incl. sign), usable as up/down counter or for connecting 4 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counter)); parameterizable enable and reset input; interrupt options (incl. Call up a sub-program with any content) when the setpoint value is reached; change of count direction etc.

  • Count frequency (counters) max.

30 kHz

30 kHz

200 kHz

200 kHz

30 kHz

30 kHz

  • Number of alarm inputs

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

4; 4 rising edges and/or 4 falling edges

  • Number of pulse outputs

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

2; fast outputs, 20 kHz, with interrupt option; pulse width and frequency modulation

  • Cut-off frequency (pulse)

20 kHz

20 kHz

20 kHz

20 kHz

20 kHz

20 kHz

Potentials/ electrical isolation

Digital output functions

    • between the channels

Yes; Optocoupler

Yes; Relay

Yes; Optocoupler

Yes; Relay

Yes; Optocoupler

Yes; Relay

    • between the channels, in groups of

5

3, 3 and 4

5

3, 3 and 4

8 and 8

4, 5 and 7

Digital input functions

    • between the channels

Yes

Yes

Yes

Yes

Yes

Yes; Optocoupler

    • between the channels, in groups of

6 and 8

6 and 8

6 and 8

6 and 8

13 and 11

13 and 11

Permissible potential difference

  • between different circuits

500 V DC between 24 V DC and 5 V DC

500 V DC between 24 V DC and 5 V DC; 1500 V AC between 24 V DC and 230 V AC

500 V DC between 24 V DC and 5 V DC

500 V DC between 24 V DC and 5 V DC; 1500 V AC between 24 V DC and 230 V AC

500 V DC between 24 V DC and 5 V DC

500 V DC between 24 V DC and 5 V DC; 1500 V AC between 24 V DC and 230 V AC

Environmental requirements

  • Environmental conditions

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

For other ambient conditions: see "S7-200 Programmable Controller, System Manual"

Operating temperature

    • vertical mounting, min.

0 °C

0 °C

0 °C

0 °C

0 °C

0 °C

    • vertical mounting, max.

45 °C

45 °C

45 °C

45 °C

45 °C

45 °C

    • horizontal mounting, min.

0 °C

0 °C

0 °C

0 °C

0 °C

0 °C

    • horizontal mounting, max.

55 °C

55 °C

55 °C

55 °C

55 °C

55 °C

Air pressure

    • permissible range, min

860 hPa

860 hPa

860 hPa

860 hPa

860 hPa

860 hPa

    • permissible range, max

1,080 hPa

1,080 hPa

1,080 hPa

1,080 hPa

1,080 hPa

1,080 hPa

Relative humidity

    • Operation, min.

5 %

5 %

5 %

5 %

5 %

5 %

    • Operation, max.

95 %; RH stressing level 2 in accordance with IEC 1131-2

95 %; RH stressing level 2 in accordance with IEC 1131-2

95 %; RH stressing level 2 in accordance with IEC 1131-2

95 %; RH stressing level 2 in accordance with IEC 1131-2

95 %; RH stressing level 2 in accordance with IEC 1131-2

95 %; RH stressing level 2 in accordance with IEC 1131-2

Degree of protection and class of protection

    • IP 20

Yes

Yes

Yes

Yes

Yes

Yes

Dimensions and weight

  • Weight, approx.

360 g

410 g

390 g

440 g

550 g

660 g

  • Width

120.5 mm

120.5 mm

140 mm

140 mm

196 mm

196 mm

  • Height

80 mm

80 mm

80 mm

80 mm

80 mm

80 mm

  • Depth

62 mm

62 mm

62 mm

62 mm

62 mm

62 mm
























































Каталог оборудования 2012
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Промышленные системы автоматизации SIMATIC Программируемые контроллеры Логические модули LOGO! SIMATIC S7 S7-200 Демонстрационные модели Центральные процессоры CPU стандартного исполнения Модули расширения Функциональные модули Коммуникационные модули Блоки питания Отображение и контроль Программное обеспечение Аксессуары S7-1200 S7-300/ S7-300F/ SIPLUS S7-300 S7-400/S7-400H/S7-400F/FH Встраиваемые системы автоматизации SIMATIC PC-based Control Дополнительные компоненты Распределенный ввод/вывод Система автоматизации SIMATIC TDC Программное обеспечение для SIMATIC S7/WinAC Программаторы Наборы Micro Automation Sets SIEMENS Solution Partner Motion Control - система SIMOTION Системы автоматизации ЧПУ SINUMERIK Система соединителей/ шкафы управления Программное обеспечение для систем автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Системы управления процессом Датчики Блоки питания Продукты для специальных требований Автоматизация зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо