Liquid-cooled PM340 Power Module in blocksize format 6SL3215-1SE... |
|
---|---|
Line connection voltage (up to 2000 m (6562 ft) above sea level) |
380 ... 480 V 3 AC ±10 % (in operation -15 % < 1 min) |
Line system configuration |
Grounded TN/TT systems and non-grounded IT systems |
Line frequency |
47 … 63 Hz |
Line power factor with a 3 AC line connection voltage and rated power |
|
|
> 0,96 |
|
0.65 … 0.95 |
Overvoltage category to EN 60664-1 |
Class III |
Precharging frequency of the DC link |
1 every 30 s |
DC link voltage, approx. |
1.35 x line voltage |
Output frequency |
|
|
0 … 650 Hz1) |
|
0 … 300 Hz1) |
|
0 … 600 Hz1) |
Electronics power supply |
24 V DC -15 %/+20 % |
Radio interference suppression |
|
|
No radio interference suppression |
Type of cooling |
Liquid cooling with integrated heat exchanger in stainless-steel version |
Coolant2)
|
6.0 … 9.0 < 200 mg/l < 240 mg/l < 2.5 mmol/l3) < 2000 S/cm < 1000 col/ml4) < 100 m |
Cooling circuit2) |
|
|
600 kPa 70 kPa 80 … 200 kPa Dependent on the ambient temperature, condensation is not permitted |
Permissible ambient temperature (air) during operation |
Dependent on the inlet temperature of the coolant, condensation is not permissible |
Installation altitude |
Up to 2000 m (3281 ft) above sea level without derating, |
Conformity |
CE (Low-Voltage and EMC Directives) |
Approvals, according to |
cULus |
Safety Integrated |
Safety Integrity Level 2 (SIL 2) acc. to IEC 61508, Performance Level d (PLd) acc. to ISO 13849 1 and Control Category 3 acc. to ISO 13849 1 or EN 954 1. For further information see chapter "Safety Integrated" |
1) Note the correlation between max. output frequency, pulse frequency and current derating.
For further information see chapter "System description – Dimensioning".
2) The values are applicable to coolant (water) without the addition of anti-freeze or inhibitors. When anti-freeze or inhibitors are added, the specifications of the manufacturer regarding water quality must be observed. The proportion of anti-freeze must not exceed a minimum concentration, otherwise the coolant has a marked corrosive effect. In the case of Antifrogen N, the recommended range of the ratio of Antifrogen N to water lies between 20/80 and 45/55 Vol.%
3) The hardness of the coolant, especially the concentration of calcium compounds should be kept to a minimum to prevent the build-up of damaging calcium deposits (lime scale). A hardness < 1.5 mmol/l is recommended.
4) The number of microbes should generally be as low as possible to prevent damage as a result of slime-producing, iron-depositing, corroding bacteria. In closed coolant circuits, the accumulation of microbes can be prevented, for example, by adding anti-freeze. The concentration of anti-freeze must only reach a minimum level to prevent corrosion, see Footnote2).
Line voltage 380 … 480 V 3 AC |
Liquid-cooled Power Module in blocksize format |
|||
---|---|---|---|---|
6SL3215-1SE23 8UA0 |
6SL3215-1SE26 0UA0 |
6SL3215-1SE27 5UA0 |
||
Output current |
||||
|
A |
38 |
60 |
75 |
|
A |
33 |
48 |
65 |
|
A |
49 |
78 |
98 |
|
A |
64 |
90 |
124 |
Type rating1) |
||||
|
kW (HP) |
18.5 (25) |
30 (40) |
37 (50) |
|
kW (HP) |
15 (20) |
22 (30) |
30 (50) |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
Power loss |
||||
|
kW |
0.38 |
0.69 |
0.99 |
|
kW |
0.09 |
0.13 |
0.16 |
Cooling circuit |
||||
|
dm3/min |
8 |
8 |
8 |
|
Pipe thread ISO 228 – G B (external thread ’’, flat-sealing) |
Pipe thread ISO 228 – G B (external thread ’’, flat-sealing) |
Pipe thread ISO 228 – G B (external thread ’’, flat-sealing) |
|
|
dm3 |
0.1 |
0.1 |
0.13 |
Sound pressure level L pA (1 m) at 50/60 Hz |
dB |
< 60 |
< 60 |
< 60 |
Rated input current with/without line reactor |
A |
40/46 |
63/72 |
78/88 |
Resistance value of the external braking resistor |
|
27 |
27 |
15 |
Cable length, max. to braking resistor |
m (ft) |
15 (49) |
15 (49) |
15 (49) |
24 V DC power supply for the Control Unit |
A |
1.0 |
1.0 |
1.0 |
Line connection U1/L1, V1/L2, W1/L3 |
Stud M6, |
Stud M6, |
Stud M6, |
|
DC link connection, connection for the braking resistor DCP/R1, DCN, R2 |
Stud M6, |
Stud M6, |
Stud M6, |
|
Motor connection U2, V2, W2 |
Stud M6, |
Stud M6, |
Stud M6, |
|
PE connection |
On housing with M6 screw |
On housing with M6 screw |
On housing with M6 screw |
|
Motor cable length, max. |
||||
|
m (ft) |
70 (230) |
70 (230) |
70 (230) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection |
IP20 |
IP20 |
IP20 |
|
Dimensions |
||||
|
mm (in) |
275 (10.83) |
275 (10.83) |
275 (10.83) |
|
mm (in) |
471 (18.54) |
471 (18.54) |
577 (22.72) |
|
||||
|
mm (in) |
159.5 (6.28) |
159.5 (6.28) |
159.5 (6.28) |
|
mm (in) |
240.4 (9.46) |
240.4 (9.46) |
240.4 (9.46) |
|
mm (in) |
181.3 (7.14) |
181.3 (7.14) |
181.3 (7.14) |
Frame size |
FSD |
FSD |
FSE |
|
Weight, approx. |
kg (lb) |
10.5 (23) |
10.5 (23) |
15 (33) |
1) Rated output of a typical standard asynchronous motor at 400 V 3 AC. For specific sizing select drive based on motor nameplate current and overload.
Line voltage 380 … 480 V 3 AC |
Liquid-cooled Power Module in blocksize format |
|||
---|---|---|---|---|
6SL3215-1SE31 0UA0 |
6SL3215-1SE31 1UA0 |
6SL3215-1SE31 8UA0 |
||
Output current |
||||
|
A |
90 |
110 |
178 |
|
A |
80 |
95 |
155 |
|
A |
117 |
143 |
231 |
|
A |
150 |
180 |
290 |
Type rating1) |
||||
|
kW (HP) |
45 (60) |
55 (75) |
90 (125) |
|
kW (HP) |
37 (60) |
45 (60) |
75 (100) |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
Power loss |
||||
|
kW |
1.21 |
1.42 |
2.31 |
|
kW |
0.19 |
0.21 |
0.35 |
Cooling circuit |
||||
|
dm3/min |
8 |
8 |
8 |
|
Pipe thread ISO 228 – G B (external thread ’’, flat-sealing) |
Pipe thread ISO 228 – G B (external thread ’’, flat-sealing) |
Pipe thread ISO 228 – G B (external thread ’’, flat-sealing) |
|
|
dm3 |
0.13 |
0.2 |
0.2 |
Sound pressure level L pA (1 m (3.28 ft)) at 50/60 Hz |
dB |
< 62 |
62 |
65 |
Rated input current with/without line reactor |
A |
94/105 |
115/129 |
186/204 |
Resistance value of the external braking resistor |
|
15 |
8.2 |
8.2 |
Cable length, max. to braking resistor |
m (ft) |
15 (49) |
15 (49) |
15 (49) |
24 V DC power supply for the Control Unit |
A |
1.0 |
1.0 |
1.0 |
Line connection U1/L1, V1/L2, W1/L3 |
M6 screw stud, |
M8 screw stud, |
M8 screw stud, |
|
DC link connection, connection for the braking resistor DCP/R1, DCN, R2 |
M6 screw stud, |
M8 screw stud, |
M8 screw stud, |
|
Motor connection U2, V2, W2 |
M6 screw stud, |
M8 screw stud, |
M8 screw stud, |
|
PE connection |
On housing with M6 screw |
On housing with M8 screw |
On housing with M8 screw |
|
Motor cable length, max. |
||||
|
m (ft) |
70 (230) |
70 (230) |
70 (230) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection |
IP20 |
IP20 |
IP20 |
|
Dimensions |
||||
|
mm (in) |
275 (10.83) |
350 (13.78) |
350 (13.78) |
|
mm (in) |
577 (22.72) |
660 (25.98) |
660 (25.98) |
|
||||
|
mm (in) |
159.5 (6.28) |
241.5 (9.51) |
241.5 (9.51) |
|
mm (in) |
240.4 (9.46) |
322.5 (12.70) |
322.5 (12.70) |
|
mm (in) |
181.3 (7.14) |
263 (10.35) |
263 (10.35) |
Frame size |
FSE |
FSF |
FSF |
|
Weight, approx. |
kg (lb) |
15 (30) |
29 (64) |
29 (64) |
1) Rated output of a typical standard asynchronous motor at 400 V 3 AC. For specific sizing select drive based on motor nameplate current and overload.