Primary differential pressure devices are standardized mechanical flow sensors, often also referred to as differential pressure transducers. The primary differential pressure devices are calculated and manufactured according to DIN EN ISO 5167.
Through constriction of the line diameter in the pressure device, the flow rate creates a differential pressure that is converted with the help of a differential pressure transmitter into a proportional current signal or flow value. The assignment of differential pressure to flow is created by means of a "calculation of the primary differential pressure device".
Primary differential pressure devices are suitable for single-phase media such as gas, vapor and liquids without solid components.
Requirement when ordering a primary differential pressure device
Always quote the orifice plate calculation and the classification according to the pressure equipment directive 97/23/EC (PED) when placing an order.
Orifice plate calculation - calculation protocol
For the "orifice plate calculation" service, you need to fill out the "Questionnaire for calculation of a primary differential pressure device according to DIN EN ISO 5167". The intelligent "SITRANS F O questionnaire online" can be found in the PIA Life Cycle Portal athttp://www.siemens.com/pia-portal.
For this purpose, you need to specify all the data of the measuring point, medium, process and pipe data, as well as details of installation conditions, flow conditions, permissible pressure losses and accuracy requirements.
We will be unable to carry out the calculation if there are any data missing. A calculation protocol with a consecutive number documents the calculation of the orifice plate. We require this calculation protocol from the customer for manufacturing purposes. It is to be included in the order for the orifice plate.
Important note:
The "Orifice Plate Calculation with Preparation of a Calculation Protocol" service is a separate process, and must be carried out before the orifice plate is ordered.
The calculation protocol issued by the customer is to be included in the order for the orifice plate.
Classification in accordance with pressure equipment directive 97/23/EC (PED)
The pressure equipment directive must also be applied to the Orifice portfolio for use in Europe.
In compliance with the pressure equipment directive, equipment is divided into categories I to III or Article 3 paragraph 3 according to danger potential (medium/pressure/volume/nominal diameter).
Submission of this design data in accordance with pressure equipment directive 97/23/EC is mandatory for ordering and manufacture, and must be specified by customers in the orifice plate order.
The Order No. of the orifice plate contains the relevant Category I, II, III or Article 3 paragraph 3 in the order code.
Detailed information is available under "Pressure equipment directive 97/23/EC".
How to order the "Orifice plate with appended calculation protocol" product
To order an orifice plate, you need to supply the following data:
- Complete Order No. of the orifice plate, including the respective order code "Manufacture according to pressure equipment directive":
- Category I, II, III or Article 3 paragraph 3 and the design data with Order Codes Y31 to Y35
- Or without (only available outside Europe!)
- Appended "Calculation Protocol" issued by the customer with Order Code Y21 or Y22, or statement "Orifice plate without calculation" with Order Code Y01
The orifice plate can only be manufactured when it has been passed as a "clean order", i. e. it has been confirmed that the data of the Order No. match the data of the calculation protocol.