Meter |
|
Accuracy |
Standard calibration: |
Extended calibration DN 50 … DN 300 (2" … 12"): |
|
Media conductivity |
Clean water > 20 s/cm |
Temperature |
|
Ambient |
-20 … +60 °C (-4 … +140 °F) |
Media |
0 … 70 °C (32 … 158 °F) |
Storage |
-40 … +70 °C (-40 … +158 °F) |
Enclosure rating |
IP68/NEMA 6P; |
Cable glands mounted requires Sylgard potting kit to remain IP68/NEMA 6P, otherwise IP67/NEMA 4 is obtained; |
|
Factory-mounted cable provides IP68/NEMA 6P. |
|
Certificates and approvals |
|
Calibration |
2 x 25 % and 2 x 90 % |
Drinking water approvals |
|
|
|
|
|
|
|
|
|
|
|
Conformity |
|
For pressure/temperature curves see MAG 3100 on page 4/xx |
|
|
|
Sensor version |
DN 25 … 1200 (1" … 48") |
Measuring principle |
Electromagnetic induction |
Excitation frequency |
|
Basic version |
|
|
DN 25 … 150 (1” … 6”): 1/15 Hz |
DN 200 … 600 (8” … 24”): 1/30 Hz |
|
DN 700 … 1200 (28“ … 48“): 1/60 Hz |
|
|
DN 25 … 150 (1” … 6”): 6.25 Hz |
DN 200 … 600 (8” … 24”): 3.125 Hz |
|
DN 700 … 1200 (28“ … 48“): 1.5625 Hz |
|
Advanced version |
|
|
DN 25 … 150 (1” … 6”): 1/15 Hz |
DN 200 … 600 (8” … 24”): 1/30 Hz |
|
DN 700 ... 1200 (28“ ... 48“): 1/60 Hz |
|
|
DN 25 ... 150 (1” ... 6”): 6.25 Hz |
DN 200 ... 600 (8” ... 24”): 3.125 Hz |
|
DN 700 ... 1200 (28“ ... 48“): 1.5625 Hz |
|
Flanges |
|
EN 1092-1 (DIN 2501) |
DN 25 and DN 40 (1" and 1 "): PN 40 (580 psi) |
DN 50 ... 150 (2" ... 6"): PN 16 (232 psi) |
|
DN 200 ... 1200 (8" ... 48"): PN 10 or PN 16 (145 psi or 232 psi) |
|
ANSI 16.5 Class 150 |
1” ... 24”: 20 bar (290 psi) |
AWWA C-207 |
28" ... 48": PN 10 (145 psi) |
AS 4087 |
DN 50 … 1200 (2" … 48"): PN 16 (232 psi) |
Liner |
EPDM |
Electrode and grounding electrodes |
Hastelloy C276/2.4819 |
Grounding straps |
Grounding straps are premounted from the factory on each side of the sensor. |
1) For further information on PED standard and requirements see page 10/xx.