6RA7085-6FC00-0 |
6RA7091-6FC00-0 |
6RA7095-6FC00-0 |
6RA7090-6KC00-0 |
6RA7095-6KC00-0 |
||
---|---|---|---|---|---|---|
Rated voltage |
V |
460 (+15 %/-20 %) |
690 (+10 %/-20 %) |
|||
Rated current |
A |
600 |
1 200 |
2 000 |
1 000 |
2 000 |
Current range that can be covered 1) |
A |
up to 600 |
up to 1 200 |
up to 2 000 |
up to 1 000 |
up to 2 000 |
Rated supply voltage, electronics power supply |
V |
380 (-20 %) … 60 V (+15 %) 2 AC;In = 1 A or |
||||
Rated frequency |
Hz |
45 ... 65 |
||||
Power loss |
W |
100 |
||||
Ambient temperature |
||||||
|
°C |
0 ... 55 |
||||
|
°C |
-25 ... +70 |
||||
Installation altitude above sea level |
m |
1 000 m |
||||
Climate class |
3K3 acc. to EN 60721-3-3 |
|||||
Degree of pollution |
2 acc. to EN 50178 2) |
|||||
Degree of protection |
IP00 acc. to EN 60529 |
|||||
Dimensions |
||||||
|
mm |
406 |
||||
|
mm |
780 |
||||
|
mm |
500 |
||||
Weight, approx. |
kg |
35 |
35 |
55 |
45 |
75 |
Fuse for connections 1U1, 1V1, 1W1 and 1D1 |
3NA3365-6 |
3NA3365-6 |
3NA3365-6 |
3NA3365-6 |
3NA3365-6 |
|
Fuse for connections 2U1, 2V1, 2W1 |
DIAZED 5SD604 |
1) The current range that can be covered corresponds to the actual rated current of the SINAMICS DC MASTER. When the rated current is reduced (via parameter) then the lower value obtained applies. This means that for a SINAMICS DC MASTER with (according to the type plate) a rated current higher than 2 000 A (necessary e.g. to maintain longer specified overload times), it is possible to use the CCP if the actual rated current, specified by the parameterization, does not exceed 2 000 A. The possible overload capability of 1.8x the actual rated current can be additionally utilized.
2) Definition of pollution degree 2:
Generally only non-conductive pollution occurs. However, occasionally conductive pollution can be expected for a short period of time if the electronic equipment is not operational.
General technical data |
||||
---|---|---|---|---|
Relevant standards |
||||
EN 50178 |
Electronic equipment for use in power installations |
|||
EN 50274 |
Low-voltage switchgear and controlgear assemblies: Protection against electric shock – Protection against unintentional direct contact with hazardous live parts |
|||
EN 60146-1-1 |
Semiconductor converters: General requirements and line-commutated converters; specification of basic requirements |
|||
EN 61800-1 |
Adjustable speed electrical power drive systems, Part 1 – (DC drives) General requirements - Rating specifications for low-voltage DC power drive systems |
|||
EN 61800-3 |
Adjustable speed electrical power drive systems, Part 3 – EMC product standard including specific test methods |
|||
EN 61800-5-1 |
Adjustable speed electrical power drive systems – Part 5-1: Requirements regarding safety – electrical, thermal, and energy requirements |
|||
IEC 62103 (identical to EN 50178) |
Electronic equipment for use in power installations |
|||
UBC 97 |
Uniform Building Code |
|||
Mechanical strength |
Storage |
Transport |
Operation |
|
Vibratory load |
1M2 acc. to EN 60721-3-1 |
2M2 acc. to EN 60721-3-2 |
Constant deflection: |
|
Shock load |
1M2 acc. to EN 60721-3-1 |
2M2 acc. to EN 60721-3-2 |
100 m/s2 at 11 ms (testing and measuring techniques acc. to EN 60068-2-27, Ea) |
|
Approvals |
||||
UL/cUL |
UL file No.: E145153 |
|||
UL 508 C (UL Standard for Power Conversion Equipment), certification of the units up to and including 575 V |
||||
GOST |