Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru
SM 326 F-digital input module - Safety Integrated

6ES7 326-1RF00-0AB0

6ES7 326-1BK02-0AB0

Supply voltage

Rated value (DC)

24 V

24 V

Input current

from load voltage L+ (without load), max.

160 mA

450 mA

from backplane bus 5 V DC, max.

90 mA

100 mA

Encoder supply

Number of outputs

8

4; Isolated

Output voltage

8.2 V DC

Output current, rated value

400 mA

Power losses

Power loss, typ.

4.5 W

10 W

Digital inputs

Number/binary inputs

8; 8 (one-channel); 4 (two-channel)

24

Number of simultaneously controllable inputs

  • all mounting positions

    • up to 40 °C, max.

8; vertical setup

24

    • up to 60 °C, max.

8; horizontal set up

24; (at 24 V) or 18 (at 28.8 V)

Input voltage

  • Rated value, DC

in accordance with DIN 19234 or NAMUR

24 V

  • for signal "0"

-30 to +5 V

  • for signal "1"

11 to 30 V

Input current

  • for signal "0", max. (permissible quiescent current)

0.35 to 1.2 mA

2 mA

  • for signal "1", typ.

2.1 to 7 mA

10 mA

Input delay (for rated value of input voltage)

  • for standard inputs

    • at "0" to "1", max.

3.4 ms

    • at "1" to "0", max.

3.4 ms

  • for NAMUR inputs

    • at "0" to "1", max.

1.2 to 3 ms

    • at "1" to "0", max.

1.2 to 3 ms

Cable length

  • Cable length, shielded, max.

200 m

200 m

  • Cable length unshielded, max.

100 m

100 m

Encoder

Connectable encoders

  • 2-wire BEROS

Yes; if short-circuit test is deactivated

    • permissible quiescent current (2-wire BEROS), max.

2 mA

Interrupts/diagnostics/status information

Alarms

  • Diagnostic alarm

Yes

Yes

Diagnoses

  • Diagnostic information readable

Yes

Yes

Ex(i) characteristics

Module for Ex(i) protection

Yes

Max. values of input circuits (per channel)

  • Co (permissible external capacity), max.

3 µF

  • Io (short-circuit current), max.

13.9 mA

  • Lo (permissible external inductivity), max.

80 mH

  • Po (power of load), max.

33.1 mW

  • Uo (output no-load voltage), max.

10 V

  • Um (fault voltage), max.

60 V DC/30 V AC

  • Ta (permissible ambient temperature), max.

60 °C

60 °C

Galvanic isolation

Galvanic isolation digital inputs

  • between the channels

Yes

Yes

  • between the channels, in groups of

12

  • between the channels and the backplane bus

Yes

Yes

Isolation

Isolation checked with

500 V DC

500 V DC / 350 V AC

Standards, approvals, certificates

Highest safety class achievable in safety mode

  • acc. to DIN VDE 0801

AK 4 (one channel), AK 5 und 6 (two channel)

AK 6

  • acc. to EN 954

Cat. 3 (single-channel), Cat. 4 (two-channel)

Cat. 4

  • acc. to IEC 61508

SIL 2 (single-channel), SIL 3 (two-channel)

SIL 3

Use in hazardous areas

  • Test number KEMA

99 ATEX 2671 X

Connection method

required front connector

40-pin

40-pin

Dimensions

Width

80 mm

80 mm

Height

125 mm

125 mm

Depth

120 mm

120 mm

Weight

Weight, approx.

482 g

442 g

























































  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366
Яндекс.Метрика