п»ї Motor reactors for blocksize format Motor reactors reduce the voltage loading on the motor windings. At the same time, the capacitive charge/discharge currents that place an additional load on the power unit when long motor cables are used are reduced. The maximum permissible output frequency when a motor reactor is used is 150В Hz. The motor reactors are designed for a pulse frequency of 4В kHz. Higher pulse frequencies are not permissible. The motor reactor must be installed as close as possible to the Power Module. |