3RV2031-4WA10Öåíà íà ñàéòå óêàçàíà ðîçíè÷íàÿ â ÅÂÐÎ áåç ó÷åòà ÍÄÑ. Äëÿ óòî÷íåíèÿ öåíû è ðàçìåðà ïðåäîñòàâëÿåìîé ñêèäêè - çâîíèòå èëè ïðèñûëàéòå çàÿâêè | Çàêàçíîé íîìåð | Âåñ | PG | Îïèñàíèå ïðîäóêòà | Öåíà | | 3RV2031-4WA10 | 1.16 | 41E | ÀÂÒÎÌÀÒÈ×ÅÑÊÈÉ ÂÛÊËÞ×ÀÒÅËÜ ÄËß ÇÀÙÈÒÛ ÝËÅÊÒÐÎÄÂÈÃÀÒÅËß, ÒÈÏÎÐÀÇÌÅÐ S2, ÊËÀÑÑ 10, ÐÅÃÓËÈÐÎÂÊÀ ÐÀÑÖÅÏÈÒÅËß ÏÅÐÅÃÐÓÇÊÈ 42…52À, ÓÑÒÀÂÊÀ ÐÀÑÖÅÏÈÒÅËß ÒÎÊΠÊÇ ÌÃÍÎÂÅÍÍÎÃÎ ÄÅÉÑÒÂÈß 741A, ÂÈÍÒÎÂÛÅ ÊËÅÌÌÛ, ÑÒÀÍÄÀÐÒÍÀß ÊÎÌÌÓÒÀÖÈÎÍÍÀß ÑÒÎÉÊÎÑÒÜ, | Ïî çàïðîñó |
Selection and ordering dataThe following table lists recommendations for additional line-side components, such as fuses and circuit breakers. Note for use in compliance with IEC standards: Type 3NA3 fuses and type 3RV circuit breakers are recommended for European countries. The values in the table take into account the overload capability of the inverter. Notes for use in compliance with UL regulations: Fuses for use in North America must be UL-certified, class J, T, CC, G or CF fuses with a rated voltage of 600 V AC. Short Circuit Current Rating (SCCR) according to UL Applies to industrial control panel installations to NEC Article 409 or UL 508A. - SINAMICS G120C: 100 kA (the value depends on the fuses and circuit breakers used)
Notes regarding installations in Canada: Overvoltage protection devices in accordance with overvoltage category III and with the following ratings must be connected on the line side of the inverter: - Rated voltage 480 V (phase-phase) and 480 V (phase-ground)
- Voltage limit 4Â kV (phase-phase) and 6Â kV (phase-ground)
All overvoltage protection devices used must comply with Canadian standards for industrial installations. Further information, particularly regarding use in accordance with UL guidelines, is available at https://support.industry.siemens.com/cs/document/109478990 Additional information about the listed fuses and circuit breakers is available in the Catalogs LVÂ 10, ICÂ 10 and ICÂ 10Â AO as well as in the Industry Mall. Rated power | SINAMICSÂ G120C | IEC-compliant | UL/cUL-compliant |
|---|
 |  |  | Fuse | Circuit breaker | Fuse type Rated voltage 600 V AC |
|---|
 |  |  | Current | 3NA3 | 2NE1 |  |  | Current |
|---|
kW | hp | Type 6SL3210-... | Frame size | A | Article No. | Article No. | Article No. | Class | A |
|---|
Line voltage 380 ... 480 V 3 AC | 0.55 | 0.75 | 1KE11-8..2 | FSAA | 10 | 3NA3803 | – | 3RV2011-1JA10 | J, T, CC, G, CF | 10 | 0.75 | 1 | 1KE12-3..2 | 1.1 | 1.5 | 1KE13-2..2 | 1.5 | 2 | 1KE14-3..2 | 2.2 | 3 | 1KE15-8..2 | 3 | 4 | 1KE17-5..1 | FSA | 16 | 3NA3805 | – | 3RV2011-4AA10 | J, T, CC, G, CF | 15 | 4 | 5 | 1KE18-8..1 | 5.5 | 7.5 | 1KE21-3..1 | FSB | 32 | 3NA3812 | – | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 7.5 | 10 | 1KE21-7..1 | 11 | 15 | 1KE22-6..1 | FSC | 63 | 3NA3822 | – | 3RV1041-4JA10 | J, T, CC, G, CF | 60 | 15 | 20 | 1KE23-2..1 | 18.5 | 25 | 1KE23-8..1 | 22 | 30 | 1KE24-4.F1 | FSD | 80 | 3NA3824 | 3NE1820-0 | 3RV2031-4WA10 | J, T, CC, G, CF | 70 | 30 | 40 | 1KE26-0.F1 | FSD | 100 | 3NA3830 | 3NE1021-0 | 3RV1041-4LA10 | J, T, CC, G, CF | 90 | 37 | 50 | 1KE27-0.F1 | 3RV1041-4MA10 | J, T, CC, G, CF | 100 | 45 | 60 | 1KE28-4.F1 | FSD | 125 | 3NA3832 | 3NE1022-0 | – | J, T, CC, G, CF | 125 | 55 | 75 | 1KE31-1.F1 | FSE | 160 | 3NA3836 | 3NE1224-0 | – | J, T, CC, G, CF | 150 | 75 | 100 | 1KE31-4.F1 | FSF | 200 | 3NA3140 | 3NE1225-0 | – | J, T, CC, G, CF | 200 | 90 | 125 | 1KE31-7.F1 | FSF | 250 | 3NA3142 | 3NE1277-0 | – | J, T, CC, G, CF | 250 | 110 | 150 | 1KE32-1.F1 | FSF | 315 | 3NA3250 | 3NE1230-0 | – | J, T, CC, G, CF | 300 | 132 | 200 | 1KE32-4.F1 | FSF | 350 | 3NA3252 | 3NE1331-0 | – | J, T, CC, G, CF | 350 |
|
|