3NA3822Öåíà íà ñàéòå óêàçàíà ðîçíè÷íàÿ â ÅÂÐÎ áåç ó÷åòà ÍÄÑ. Äëÿ óòî÷íåíèÿ öåíû è ðàçìåðà ïðåäîñòàâëÿåìîé ñêèäêè - çâîíèòå èëè ïðèñûëàéòå çàÿâêè | Çàêàçíîé íîìåð | Âåñ | PG | Îïèñàíèå ïðîäóêòà | Öåíà | | 3NA3822 | 0.13 | 1BM | ÏËÀÂÊÀß ÂÑÒÀÂÊÀ ÍÈÇÊÎÂÎËÜÒÍÀß GL/GG Ñ ÍÅÈÇÎËÈÐÎÂÀÍÍÛÌÈ ÂÛÑÒÓÏÀÌÈ ÄËß ÌÎÍÒ./ÄÅÌÎÍÒ. ÒÈÏÎÐÀÇÌÅÐ 00, Iíîì.=63A, Uíîì.=500 | Ïî çàïðîñó |
Selection and ordering dataThe following tables list recommendations for additional line-side components, such as fuses and circuit breakers. The values in the table take into account the overload capability of the inverter. Notes for use in compliance with IEC standards: 3NA3 or 3NE1 fuses and 3RV motor starter protectors or 3VL circuit breakers are recommended for European countries. Notes for use in compliance with UL regulations: UL-listed fuses Class J, T, CC, G or CF (with rated voltage 250 V AC or 600 V AC) or 3NE1 (UL-compliant – corresponds to RU) are required for North America. Short Circuit Current Rating (SCCR) according to UL Applies to industrial control panel installations to NEC Article 409 or UL 508A/508C - PM240-2: 100 kA (200 V versions), 100 kA (400 V versions), 65 kA (690 V versions)
(the value depends on the fuses and circuit breakers used) - PM240: 65Â kA
- PM250: 40Â kA (frame size FSC), 42Â kA (frame sizes FSD to FSF)
Notes regarding installations in Canada: Overvoltage protection devices in accordance with overvoltage category III and with the following ratings must be connected on the line side of the inverter: - Rated voltage 480 V (phase-phase) and 480 V (phase-ground)
- Voltage limit 4Â kV (phase-phase) and 6Â kV (phase-ground)
All overvoltage protection devices used must comply with Canadian standards for industrial installations. Further information, particularly regarding use in accordance with UL guidelines, is available at https://support.industry.siemens.com/cs/document/109479152 Additional information about the line-side power components can be found in Catalogs LVÂ 10, ICÂ 10 and ICÂ 10Â AO as well as the Industry Mall. Rated power 1) | PM240-2 Power Module standard variant | IEC-compliant | UL/cUL-compliant |
|---|
 |  |  |  | Fuse | Circuit breaker | Fuse type Rated voltage 250 V AC or 600 V AC |
|---|
 |  | Type |  | Current |  |  |  | Current |
|---|
kW | hp | 6SL3210-... | Frame size | A | Article No. | Article No. | Class | A |
|---|
200 ... 240 V 1 AC/3 AC | 0.55 | 0.75 | 1PB13-0 . L0 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 15 | 0.75 | 1 | 1PB13-8 . L0 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 15 | 1.1 | 1.5 | 1PB15-5 . L0 | FSB | 32 | 3NA3812 | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 1.5 | 2 | 1PB17-4 . L0 | FSB | 32 | 3NA3812 | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 2.2 | 3 | 1PB21-0 . L0 | FSB | 32 | 3NA3812 | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 3 | 4 | 1PB21-4 . L0 | FSC | 50 | 3NA3820 | 3RV1031-4HA10 | J, T, CC, G, CF | 50 | 4 | 5 | 1PB21-8 . L0 | FSC | 50 | 3NA3820 | 3RV1031-4HA10 | J, T, CC, G, CF | 50 | 200 ... 240 V 3 AC | 5.5 | 7.5 | 1PC22-2 . L0 | FSC | 50 | 3NA3820 | 3RV1031-4HA10 | J, T, CC, G, CF | 50 | 7.5 | 10 | 1PC22-8 . L0 | FSC | 50 | 3NA3820 | 3RV1031-4HA10 | J, T, CC, G, CF | 50 | 11 | 15 | 1PC24-2UL0 | FSD | 63 | 3NE1818-0 | 3RV1041-4JA10 | J | 60 | 15 | 20 | 1PC25-4UL0 | FSD | 80 | 3NE1820-0 | 3RV1041-4KA10 | J | 70 | 18.5 | 25 | 1PC26-8UL0 | FSD | 100 | 3NE1021-0 | 3RV1041-4LA10 | J | 90 | 22 | 30 | 1PC28-0UL0 | FSE | 100 | 3NE1021-0 | 3VL1712-2DD33-.... *) | J | 100 | 30 | 40 | 1PC31-1UL0 | FSE | 160 | 3NE1224-0 | 3VL1716-2DD33-.... *) | J | 150 | 37 | 50 | 1PC31-3UL0 | FSF | 200 | 3NE1225-0 | 3VL3720-3DC33-.... *) | J | 175 | 45 | 60 | 1PC31-6UL0 | FSF | 200 | 3NE1225-0 | 3VL3720-3DC33-.... *) | J | 200 | 55 | 75 | 1PC31-8UL0 | FSF | 250 | 3NE1227-0 | 3VL3725-3DC33-.... *) | J | 225 | 380 ... 480 V 3 AC | 0.55 | 0.75 | 1PE11-8 . L1 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 10 | 0.75 | 1 | 1PE12-3 . L1 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 10 | 1.1 | 1.5 | 1PE13-2 . L1 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 15 | 1.5 | 2 | 1PE14-3 . L1 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 20 | 2.2 | 3 | 1PE16-1 . L1 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 30 | 3 | 4 | 1PE18-0 . L1 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 30 | 4 | 5 | 1PE21-1 . L0 | FSB | 32 | 3NA3812 | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 5.5 | 7.5 | 1PE21-4 . L0 | FSB | 32 | 3NA3812 | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 7.5 | 10 | 1PE21-8 . L0 | FSB | 32 | 3NA3812 | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 11 | 15 | 1PE22-7 . L0 | FSC | 50 | 3NA3820 | 3RV1031-4HA10 | J, T, CC, G, CF | 50 | 15 | 20 | 1PE23-3 . L0 | FSC | 50 | 3NA3820 | 3RV1031-4HA10 | J, T, CC, G, CF | 50 | 18.5 | 25 | 1PE23-8 . L0 | FSD | 63 | 3NE1818-0 | 3RV1041-4JA10 | J | 60 | 22 | 30 | 1PE24-5 . L0 | FSD | 80 | 3NE1820-0 | 3RV1041-4KA10 | J | 70 | 30 | 40 | 1PE26-0 . L0 | FSD | 100 | 3NE1021-0 | 3RV1041-4LA10 | J | 90 | 37 | 50 | 1PE27-5 . L0 | FSD | 100 | 3NE1021-0 | 3RV1041-4MA10 | J | 100 | 45 | 60 | 1PE28-8 . L0 | FSE | 125 | 3NE1022-0 | 3VL1712-2DD33-.... *) | J | 125 | 55 | 75 | 1PE31-1 . L0 | FSE | 160 | 3NE1224-0 | 3VL1716-2DD33-.... *) | J | 150 | 75 | 100 | 1PE31-5 . L0 | FSF | 200 | 3NE1225-0 | 3VL3720-3DC33-.... *) | J | 200 | 90 | 125 | 1PE31-8 . L0 | FSF | 250 | 3NE1227-0 | 3VL3725-3DC33-.... *) | J | 225 | 110 | 150 | 1PE32-1 . L0 | FSF | 315 | 3NE1230-0 | 3VL4731-3DC36-.... *) | J | 300 | 132 | 200 | 1PE32-5 . L0 | FSF | 350 | 3NE1331-0 | 3VL4740-3DC36-.... *) | J | 350 | 500 ... 690 V 3 AC | 11 | 10 | 1PH21-4 . L0 | FSD | 25 | 3NE1815-0 | 3RV1042-4BA10 | J | 20 | 15 | 15 | 1PH22-0 . L0 | FSD | 25 | 3NE1815-0 | 3RV1042-4EA10 | J | 25 | 18.5 | 20 | 1PH22-3 . L0 | FSD | 35 | 3NE1803-0 | 3RV1042-4EA10 | J | 30 | 22 | 25 | 1PH22-7 . L0 | FSD | 35 | 3NE1803-0 | 3VL1704-2DD33-.... *) | J | 35 | 30 | 30 | 1PH23-5 . L0 | FSD | 50 | 3NE1817-0 | 3VL1705-2DD33-.... *) | J | 45 | 37 | 40 | 1PH24-2 . L0 | FSD | 63 | 3NE1818-0 | 3VL1706-2DD33-.... *) | J | 60 | 45 | 50 | 1PH25-2 . L0 | FSE | 80 | 3NE1820-0 | 3VL1708-2DD33-.... *) | J | 80 | 55 | 60 | 1PH26-2 . L0 | FSE | 80 | 3NE1820-0 | 3VL1710-2DD33-.... *) | J | 80 | 75 | 75 | 1PH28-0 . L0 | FSF | 100 | 3NE1021-0 | 3VL1712-2DD33-.... *) | J | 100 | 90 | 100 | 1PH31-0 . L0 | FSF | 125 | 3NE1022-0 | 3VL1712-2DD33-.... *) | J | 125 | 110 | 100 | 1PH31-2 . L0 | FSF | 160 | 3NE1224-0 | 3VL1716-2DD33-.... *) | J | 150 | 132 | 125 | 1PH31-4 . L0 | FSF | 200 | 3NE1225-0 | 3VL3720-3DC33-.... *) | J | 200 |
1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO). *) See Catalog LV 10 for Article No. supplements.  Rated power 1) | PM240‑2 Power Module Push Through variant | IEC-compliant | UL/cUL-compliant |
|---|
 |  |  |  | Fuse | Circuit breaker | Fuse type Rated voltage 250 V AC or 600 V AC |
|---|
 |  | Type |  | Current |  |  |  | Current |
|---|
kW | hp | 6SL3211-... | Frame size | A | Article No. | Article No. | Class | A |
|---|
200 ... 240 V 1 AC/3 AC | 0.75 | 1 | 1PB13-8 . L0 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 15 | 2.2 | 3 | 1PB21-0 . L0 | FSB | 32 | 3NA3812 | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 4 | 5 | 1PB21-8 . L0 | FSC | 50 | 3NA3820 | 3RV1031-4HA10 | J, T, CC, G, CF | 50 | 380 ... 480 V 3 AC | 3 | 4 | 1PE18-0 . L1 | FSA | 16 | 3NA3805 | 3RV2011-4AA10 | J, T, CC, G, CF | 30 | 7.5 | 10 | 1PE21-8 . L0 | FSB | 32 | 3NA3812 | 3RV2021-4EA10 | J, T, CC, G, CF | 35 | 15 | 20 | 1PE23-3 . L0 | FSC | 50 | 3NA3820 | 3RV1031-4HA10 | J, T, CC, G, CF | 50 |
1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO). Â Rated power 1) | PM240 Power Module | IEC-compliant | UL/cUL-compliant |
|---|
 |  |  |  | Fuse | Circuit breaker | Fuse | Fuse type Rated voltage 600 V AC |
|---|
 |  | Type |  | Current | Type 3NA3 |  | Type 3NE1 (RU) |  | Current |
|---|
kW | hp | 6SL3224-... | Frame size | A | Article No. | Article No. | Article No. | Class | A |
|---|
380 ... 480 V 3 AC | 160 | 250 | 0XE41-3UA0 | FSGX | 355 | 3NA3254 | 3VL4740-.DC36-.... *) | 3NE1333-2 | – | – | 200 | 300 | 0XE41-6UA0 | FSGX | 400 | 3NA3260 | 3VL5750-.DC36-.... *) | 3NE1333-2 | – | – | 250 | 400 | 0XE42-0UA0 | FSGX | 630 | 3NA3372 | 3VL5750-.DC36-.... *) | 3NE1436-2 | – | – |
1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO). *) See Catalog LVÂ 10 for Article No. supplements. Â Rated power 1) | PM250 Power Module | IEC-compliant | UL/cUL-compliant |
|---|
 |  |  |  | Fuse | Circuit breaker | Fuse | Fuse type Rated voltage 600 V AC |
|---|
 |  | Type |  | Current | Type 3NA3 |  | Type 3NE1 (RU) |  | Current |
|---|
kW | hp | 6SL3225-... | Frame size | A | Article No. | Article No. | Article No. | Class | A |
|---|
380 ... 480 V 3 AC | 7.5 | 10 | 0BE25-5AA1 | FSC | 20 | 3NA3807 | 3RV1031-4EA10 | – | K5 2) | 50 | 11 | 15 | 0BE27-5AA1 | FSC | 32 | 3NA3812 | 3RV1031-4FA10 | – | K5 2) | 50 | 15 | 20 | 0BE31-1AA1 | FSC | 35 | 3NA3814 | 3RV1031-4HA10 | – | K5 2) | 50 | 18.5 | 25 | 0BE31-5UA0 | FSD | 50 | 3NA3820 | 3RV1042-4KA10 | – | – | – | 0BE31-5AA0 | 3NE1817-0 | – | – | 22 | 30 | 0BE31-8UA0 | FSD | 63 | 3NA3822 | 3RV1042-4KA10 | – | – | – | 0BE31-8AA0 | 3NE1818-0 | – | – | 30 | 40 | 0BE32-2UA0 | FSD | 80 | 3NA3824 | 3RV1042-4MA10 | – | – | – | 0BE32-2AA0 | 3NE1820-0 | – | – | 37 | 50 | 0BE33-0UA0 | FSE | 100 | 3NA3830 | 3VL1712-.DD33-.... *) | – | – | – | 0BE33-0AA0 | 3NE1021-0 | – | – | 45 | 60 | 0BE33-7UA0 | FSE | 125 | 3NA3832 | 3VL1716-.DD33-.... *) | – | – | – | 0BE33-7AA0 | 3NE1022-0 | – | – | 55 | 75 | 0BE34-5UA0 | FSF | 160 | 3NA3836 | 3VL3720-.DC36-.... *) | – | – | – | 0BE34-5AA0 | 3NE1224-0 | J | 150 | 75 | 100 | 0BE35-5UA0 | FSF | 200 | 3NA3140 | 3VL3725-.DC36-.... *) | – | – | – | 0BE35-5AA0 | 3NE1225-0 | J | 200 | 90 | 125 | 0BE37-5UA0 | FSF | 250 | 3NA3144 | 3VL4731-.DC36-.... *) | – | – | – | 0BE37-5AA0 | 3NE1227-0 | J | 250 |
1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO). 2) Any UL-listed fuse may be used, e.g. Class K5, Class J, etc. *) See Catalog LVÂ 10 for Article No. supplements.
|
|