Recommended line-side power components for blocksize format Selection and ordering data The following tables list recommendations for additional line-side components, such as fuses and circuit breakers. The values in the table take into account the overload capability of the inverter.
Notes for use in compliance with IEC standards:
3NA3 or 3NE1 fuses and 3RV motor starter protectors or 3VL circuit breakers are recommended for European countries.
Notes for use in compliance with UL regulations:
UL-listed fuses Class J, T, CC, G or CF (with rated voltage 250 V AC or 600 V AC) or 3NE1 (UL-compliant – corresponds to RU) are required for North America.
Short Circuit Current Rating (SCCR) according to UL Applies to industrial control panel installations to NEC Article 409 or UL 508A/508C
PM240-2: 100 kA (200 V versions), 100 kA (400 V versions), 65 kA (690 V versions) (the value depends on the fuses and circuit breakers used) Notes regarding installations in Canada:
Overvoltage protection devices in accordance with overvoltage category III and with the following ratings must be connected on the line side of the inverter:
Rated voltage 480 V (phase-phase) and 480 V (phase-ground) Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground) All overvoltage protection devices used must comply with Canadian standards for industrial installations.
Further information, particularly regarding use in accordance with UL guidelines, is available athttps://support.industry.siemens.com/cs/document/109479152
https://support.industry.siemens.com/cs/document/109486009
Additional information about the line-side power components can be found in Catalogs LV 10, IC 10 and IC 10 AO as well as the Industry Mall.
Type rating 1)
PM240-2 Power Module standard variant
IEC-compliant
UL/cUL-compliant
Fuse
Circuit breaker
Fuse type Rated voltage 250 V AC or 600 V AC
Type
Current
Current
kW
hp
6SL3210-...
Frame size
A
Article No.
Article No.
Class
A
200 ... 240 V 1 AC/3 AC
0.55
0.75
1PB13-0 . L0
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
0.75
1
1PB13-8 . L0
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
1.1
1.5
1PB15-5 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
1.5
2
1PB17-4 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
2.2
3
1PB21-0 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
3
4
1PB21-4 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
4
5
1PB21-8 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
200 ... 240 V 3 AC
5.5
7.5
1PC22-2 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
7.5
10
1PC22-8 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
11
15
1PC24-2UL0
FSD
63
3NE1818-0
3RV1041-4JA10
J
60
15
20
1PC25-4UL0
FSD
80
3NE1820-0
3RV1041-4KA10
J
70
18.5
25
1PC26-8UL0
FSD
100
3NE1021-0
3RV1041-4LA10
J
90
22
30
1PC28-0UL0
FSE
100
3NE1021-0
3VL1712-2DD33-....
*)
J
100
30
40
1PC31-1UL0
FSE
160
3NE1224-0
3VL1716-2DD33-....
*)
J
150
37
50
1PC31-3UL0
FSF
200
3NE1225-0
3VL3720-3DC33-....
*)
J
175
45
60
1PC31-6UL0
FSF
200
3NE1225-0
3VL3720-3DC33-....
*)
J
200
55
75
1PC31-8UL0
FSF
250
3NE1227-0
3VL3725-3DC33-....
*)
J
225
380 ... 480 V 3 AC
0.55
0.75
1PE11-8 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
10
0.75
1
1PE12-3 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
10
1.1
1.5
1PE13-2 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
1.5
2
1PE14-3 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
20
2.2
3
1PE16-1 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
30
3
4
1PE18-0 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
30
4
5
1PE21-1 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
5.5
7.5
1PE21-4 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
7.5
10
1PE21-8 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
11
15
1PE22-7 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
15
20
1PE23-3 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
18.5
25
1PE23-8 . L0
FSD
63
3NE1818-0
3RV1041-4JA10
J
60
22
30
1PE24-5 . L0
FSD
80
3NE1820-0
3RV1041-4KA10
J
70
30
40
1PE26-0 . L0
FSD
100
3NE1021-0
3RV1041-4LA10
J
90
37
50
1PE27-5 . L0
FSD
100
3NE1021-0
3RV1041-4MA10
J
100
45
60
1PE28-8 . L0
FSE
125
3NE1022-0
3VL1712-2DD33-....
*)
J
125
55
75
1PE31-1 . L0
FSE
160
3NE1224-0
3VL1716-2DD33-....
*)
J
150
75
100
1PE31-5 . L0
FSF
200
3NE1225-0
3VL3720-3DC33-....
*)
J
200
90
125
1PE31-8 . L0
FSF
250
3NE1227-0
3VL3725-3DC33-....
*)
J
225
110
150
1PE32-1 . L0
FSF
315
3NE1230-0
3VL4731-3DC36-....
*)
J
300
132
200
1PE32-5 . L0
FSF
350
3NE1331-0
3VL4740-3DC36-....
*)
J
350
500 ... 690 V 3 AC
11
10
1PH21-4 . L0
FSD
25
3NE1815-0
3RV1042-4BA10
J
20
15
15
1PH22-0 . L0
FSD
25
3NE1815-0
3RV1042-4EA10
J
25
18.5
20
1PH22-3 . L0
FSD
35
3NE1803-0
3RV1042-4EA10
J
30
22
25
1PH22-7 . L0
FSD
35
3NE1803-0
3VL1704-2DD33-....
*)
J
35
30
30
1PH23-5 . L0
FSD
50
3NE1817-0
3VL1705-2DD33-....
*)
J
45
37
40
1PH24-2 . L0
FSD
63
3NE1818-0
3VL1706-2DD33-....
*)
J
60
45
50
1PH25-2 . L0
FSE
80
3NE1820-0
3VL1708-2DD33-....
*)
J
80
55
60
1PH26-2 . L0
FSE
80
3NE1820-0
3VL1710-2DD33-....
*)
J
80
75
75
1PH28-0 . L0
FSF
100
3NE1021-0
3VL1712-2DD33-....
*)
J
100
90
100
1PH31-0 . L0
FSF
125
3NE1022-0
3VL1712-2DD33-....
*)
J
125
110
100
1PH31-2 . L0
FSF
160
3NE1224-0
3VL1716-2DD33-....
*)
J
150
132
125
1PH31-4 . L0
FSF
200
3NE1225-0
3VL3720-3DC33-....
*)
J
200
1) Type rating based on the rated output current I rated . The rated output current I rated is based on the duty cycle for low overload (LO).
*) See Catalog LV 10 for Article No. supplements.
Type rating 1)
PM240?2 Power Module push-through variant
IEC-compliant
UL/cUL-compliant
Fuse
Circuit breaker
Fuse type Rated voltage 250 V AC or 600 V AC
Type
Current
Current
kW
hp
6SL3211-...
Frame size
A
Article No.
Article No.
Class
A
200 ... 240 V 1 AC/3 AC
0.75
1
1PB13-8 . L0
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
2.2
3
1PB21-0 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
4
5
1PB21-8 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
380 ... 480 V 3 AC
3
4
1PE18-0 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
30
7.5
10
1PE21-8 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
15
20
1PE23-3 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
1) Type rating based on the rated output current I rated . The rated output current I rated is based on the duty cycle for low overload (LO).