product brandname | | SIPLUS |
Product designation | | Power unit |
General technical data: | | | | | |
Design of the product | | PM240-2 |
Vibration frequency during transport acc. to EN 60721-3-2 Note | | Class 2M3 |
Shock acceleration during operation acc. to EN 60068-2-27 | m/s? | 147 |
Power factor | | 0.85 |
Brake version | | DC braking, compound braking, resistance braking with integrated brake chopper (for size FSGX optional) |
Protection function parameter lock | | Yes |
Electrical output frequency | Hz | 50 |
Consumed current from supply voltage for Control Unit at DC at 24 V | A | 1 |
Phase number of the output voltage | | 3 |
Input current | | | | | |
| A | 5.5 | 10.1 | 22.2 | 39.9 |
| A | 4.7 | 8.8 | 19.8 | 36 |
Output current | | | | | |
| A | 6.2 | 11.8 | 27 | 52 |
| A | 4.1 | 7.7 | 18 | 32 |
| A | 4.1 | 7.7 | 18 | 32 |
| A | 3.1 | 5.9 | 13.2 | 26 |
Supplied active power at rated value of output voltage | | | | | |
| kW | 1.5 | 3 | 7.5 | 15 |
| kW | 1.1 | 2.2 | 5.5 | 11 |
Efficiency | | 0.96 | 0.97 |
Cooling air flow | m?/s | 0.005 | 0.0092 | 0.019 |
1 m measuring surface sound pressure level maximum | dB | 50 | 62 | 65 |
Type of electrical connection | | | | | |
| | Plug-in screw terminals |
| | Plug-in screw terminals |
| | Plug-in screw terminals |
Connectable conductor cross-section for mains supply line | | 1 ... 2.5 | 1.5 ... 2.5 | 1.5 ... 6 | 6 ... 16 |
Connectable conductor cross-section for motor supply line | | 1 ... 2.5 | 1.5 ... 2.5 | 1.5 ... 6 | 6 ... 16 |
Wire length for motor shielded maximum | m | 50 |
Power loss [W] maximum | kW | 0.07 | 0.12 | 0.2 | 0.37 |
Protection class IP | | IP20 |
Width | mm | 73 | 100 | 140 |
Height | mm | 196 | 292 | 355 |
Depth | mm | 165 |
Design of the converter | | FSA | FSB | FSC |
Net weight | kg | 1.4 | 3 | 4.8 |
Ambient conditions: | | | | | |
Ambient temperature during operation maximum | °C | 55 |
Relative humidity without condensation during operation maximum Note | | RH incl. condensation/frost (no commissioning in bedewed state) |
Relative humidity without condensation during operation maximum | % | 100 |
Touch protection acc. to EN 61800-5-1 | | Assuming use as prescribed |
Operating resource protection class acc. to EN 61800-5-1 | | Class I (with protective bonding circuit) and Class III (PELV) |
Ambient temperature | | | | | |
| | -25 ... +55 |
| | -40 ... +70 |
Ambient temperature [°F] | | | | | |
| | -13 ... +131 |
| | Class 1K3 acc. to EN 60721-3-1 |
| | -40 ... +158 |
| | Class 2K3 according to EN 60721-3-2 |
Degree of pollution | | 2 according to EN 61800-5-1 |
Resistance to biologically active substances conformity acc. to EN 60721-3-3 | | Yes |
Resistance to biologically active substances | | Class 3B2 acc. to EN 60721-3-3, mold and fungal spores (except fauna) |
| | The supplied plug covers must remain in place over the unused interfaces during operation! |
conformity acc. to EN 60721-3-3 | | Yes |
Resistance to chemically active substances | | Class 3C4 acc. to EN 60721-3-3, including salt spray acc. to EN 60068-2-52 (severity level 3) |
| | Compliant with EN 60721-3-3, Class 3C4 incl. salt spray in accordance with EN 60068-2-52 (severity 3); the supplied plug covers must remain in place on the unused interfaces during operation. |
Resistance to mechanically active substances conformity acc. to EN 60721-3-3 | | No |
Certificate of suitability | | CE / TUV |
Certificate of suitability for CE marking | | EMC Directive 2004/108/EC, Low-Voltage Directive 2006/95/EC |
Standard for EMC acc. to EN 61800-3 | | The EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter. |
Product component Line filter | | No |
Power Electronics: | | | | | |
Type of voltage of the input voltage | | AC |
Electrical output frequency | | | | | |
| | 0 ... 650 |
| | 0 ... 200 |
Pulse frequency rated value | kHz | 4 |
Output voltage in percent related to the input voltage | | 0 ... 95 |
Type of duty cycle duration | | | | | |
| | 1.1 x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s 1.5 ? rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s |
| | 1.5 ? output current rating (i.e., 150 % overload) for 57 s with a cycle time of 300 s 2 ? output current rating (i.e., 200 % overload) for 3 s with a cycle time of 300 s |
Type of cooling | | Internal air cooling |
Installation altitude at height above sea level without power reduction maximum | m | 1 000 |
Short-time withstand current (SCCR) of the entire control cabinet acc. to UL 508A | kA | 65 |
Protection function | | | | | |
| | Yes |
| | Yes |
| | Yes |
| | Yes |
| | Yes |
| | Yes |
| | Yes |
| | Yes |
| | Yes |
Mechanical data: | | | | | |
Shock acceleration during operation Note | | (15 ? g)/11 ms |
Vibration frequency with constant deflection during operation acc. to EN 60068-2-6 maximum Note | | constant deflection 0.075 mm |
Vibration frequency with constant deflection during operation acc. to EN 60068-2-6 | | 10 ... 58 |
Vibration frequency with constant acceleration during operation acc. to EN 60068-2-6 maximum Note | | constant acceleration = 9.81 m/s2 (1 ? g) |
Vibration frequency with constant acceleration during operation acc. to EN 60068-2-6 | | 58 ... 200 |