In a station for the S7-CPU, the SIPLUS communication module TIM 4R-IE DNP3 (TeleControl Interface Module) handles the data exchange with the assigned SIMATIC PCS7 TeleControl V8.0 master system using the open DNP3 protocol. In addition, the V3.0 module now also supports master and node functionality.
With the double-width S7-300 housing, the module can be fully integrated into the S7-300 system
Can be connected as a stand-alone module to a SIMATIC S7-400 and SIMATIC S7-400 H System
Two RS232/RS485 interfaces support connection of an external modem for data transmission via a conventional WAN or of a Modbus RTU slave to an S7-300 system
The module has two RJ45 interfaces for data transmission via IP-based networks
By using physically separate connection paths, the module permits media redundancy without loss of data during the switchover
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were adopted from the respective standard products. Information specific to SIPLUS extreme was added.
SIPLUS TIM 4R-IE DNP3
Article No.
6AG1803-4BA00-7AA0
Article No. based on
6NH7803-4BA00-0AA0
Ambient temperature range
-25 … +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical specifications
The technical specifications of the standard product apply except for the ambient conditions.
Ambient conditions
Relative humidity
100%, condensation/frost permissible. No commissioning if condensation present.
Biologically active substances, compliance with EN 60721-3-3
Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation.
Chemically active substances, compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation.
Mechanically active substances, compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
Air pressure (depending on the highest positive temperature range specified)
1 080 ... 795 hPa (-1 000 ... +2 000 m) see ambient temperature range
795 ... 658 hPa (+2 000 ... +3 500 m) derating 10 K
658 ... 540 hPa (+3 500 ... +5 000 m) derating 20 K