General information | |
Product type designation | F-DQ 4x24VDC HF |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V12 |
| V5.5 SP3 / - |
| V2.31 |
Supply voltage | |
Type of supply voltage | 24 V DC |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Digital outputs | |
Number of digital outputs | 4 |
Digital outputs, parameterizable | Yes |
Short-circuit protection | Yes |
Open-circuit detection | Yes |
Overload protection | Yes |
Limitation of inductive shutdown voltage to | typ. 2*47V |
Switching capacity of the outputs | |
| 2 A |
| 10 W |
Load resistance range | |
| 12 ? |
| 2 000 ? |
Output voltage | |
| DC |
| 24 V; L+ (-0.5 V) |
Output current | |
| 2 A |
| 0.5 mA |
Switching frequency | |
| 30 Hz; Symmetrical |
| 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
| 10 Hz; Symmetrical |
Total current of the outputs | |
| 2 A; Note derating data in the manual |
| 6 A; Note derating data in the manual |
Cable length | |
| 1 000 m |
| 500 m |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes, "Alarms/diagnostic messages" section in the manual |
Substitute values connectable | No |
Alarms | |
| Yes |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes; green PWR LED |
| Yes; Green LED |
| Yes; Red LED |
| Yes; green/red DIAG LED |
Potential separation | |
Potential separation channels | |
| Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety functions | Yes |
Highest safety class achievable in safety mode | |
| PLe |
| SIL 3 |
Probability of failure (for service life of 20 years and repair time of 100 hours) | |
| < 2.00E-05 1/h |
| < 1.00E-09 1/h |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C |
| 60 °C |
| -25 °C |
| 50 °C |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 15 mm |
Weights | |
Weight, approx. | 57 g |