SIPLUS PS PSU300S 20 A | SIPLUS PSU300S 10 A | SIPLUS PSU300S 20 A |
Article No. | 6AG1434-2BA10-7AA0 | 6AG1436-2BA10-7AA0 |
Article No. based on | 6EP1434-2BA10 | 6EP1436-2BA10 |
Ambient temperature range | 0 ... +70 °C | -25 ... +70 °C |
Conformal coating | Coating of the printed circuit boards and the electronic components | Coating of the printed circuit boards and the electronic components |
Technical specifications | The technical specifications of the standard product apply, except for the ambient conditions. | The technical specifications of the standard product apply, except for the ambient conditions. |
Ambient conditions |
Relative humidity | 100 %, condensation/frost permitted. No commissioning in bedewed state. | 100 %, condensation/frost permitted. No commissioning in bedewed state. |
Biologically active substances, compliance with EN 60721-3-3 | Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation. | Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation. |
Chemically active substances, compliance with EN 60721-3-3 | Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation. | Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation. |
Mechanically active substances, compliance with EN 60721-3-3 | Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation. | Class 3S4 incl. sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation. |
Air pressure (depending on the highest positive temperature range specified) | 1080 ... 795 hPa (-1 000 ... +2 000 m) see ambient temperature range 795 ... 658 hPa (+2 000 ... +3 500 m) derating 10 K 658 ... 540 hPa (+3 500 ... +5 000 m) derating 20 K | 1080 ... 795 hPa (-1 000 ... +2 000 m) see ambient temperature range 795 ... 658 hPa (+2 000 ... +3 500 m) derating 10 K 658 ... 540 hPa (+3 500 ... +5 000 m) derating 20 K |