The one-phase SIPLUS smart are the universal and powerful standard power supplies for machinery and plant engineering. Despite their compact design, they offer an excellent overload response: Thanks to a power boost of 150%, loads with high power consumption can be connected without any problems and the permanent overload capability of 120% offers power reserves in case of expansions. The high degree of efficiency results in low energy consumption and minimal heat generation inside the control cabinet.
To further increase 24 V availability, the SIPLUS smart power supplies can be combined with buffer, DC UPS, redundancy and selectivity modules.
Main product highlights
1-phase, 24 V DC/10 A
Input voltage 120 V and 230 V AC with automatic range switching
Compact design - no lateral clearances required
Extra power with 1.5 times the rated current (5 s/min) for brief, operational overload
Permanent overload capability with 1.2 times the rated current up to 45 °C ambient temperature
Adjustable output voltage for compensating voltage drops
Signaling contact for easy integration in the plant monitoring system
Wide temperature range from -25 or -10 to +70 °C
Comprehensive certifications, such as cULus, ATEX and GL
Note:
SIPLUS extreme products are based on Siemens standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.
SIPLUS PS PSU100S 24 V/10 A
Article No.
6AG1 334-2BA20-4AA0
Article No. based on
6EP1 334-2BA20
Ambient temperature range
-25 ... +70 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical specifications
The technical specifications of the standard product apply, except for the ambient conditions.
Ambient conditions
Relative humidity
100%, condensation/frost permitted. No commissioning in bedewed state.
Biologically active substances, compliance with EN 60721-3-3
Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation.
Chemically active substances, compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation.
Mechanically active substances, compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
Air pressure (depending on the highest positive temperature range specified)
1080 ... 795 hPa (-1 000 ... +2 000 m) see ambient temperature range
795 ... 658 hPa (+2 000 ... +3 500 m) derating 10 K
658 ... 540 hPa (+3 500 ... +5 000 m) derating 20 K