Siemens
ÑÐÅÄÑÒÂÀ ÏÐÎÌÛØËÅÍÍÎÉ ÀÂÒÎÌÀÒÈÇÀÖÈÈ
îôèöèàëüíûé ïàðòíåð Ñèìåíñ
Êàòàëîã ÑÀ01 2017
àðõèâíûé
(4872) 700-366
skenergo@mail.ru

PM230 Power Modules
General technical specifications

 

PM230 Power Modules

Degree of protection

IP55/UL Type 12 (with BOP-2 or blanking cover)
IP54/UL Type 12 with IOP

IP20/UL Open Type
(Standard or Push Through variants)

Power (low overload LO)

0.37 ... 90 kW

0.37 ... 75 kW

Rated output current (low overload LO)

1.3 ... 178 A

1.3 ... 145 A

Power (high overload HO)

0.25 ... 75 kW

0.25 ... 55 kW

Rated output current (high overload HO)

0.9 ... 145 A

0.9 ... 110 A

System operating voltage

380 ... 480 V ±10 % 3 AC

Grid requirement
Short-circuit power RSC

>100

Input frequency

47 ... 63 Hz

Output frequency

 

  • Control mode V/f

0 ... 550 Hz

  • Control type Vector

0 ... 240 Hz

Pulse frequency

4 kHz
for higher pulse frequencies up to 16 kHz, see derating data

Power factor ?

0.9

Output voltage, max.

as % of input voltage

95%

Overload capability

 

  • Low overload (LO)

Note: When the overload capability is used, the base-load current IL is not reduced.

  • Frame sizes FSA to FSC

1.5 ? base-load current IL (i. e. 150 % overload) for 3 s plus
1.1 ? base-load current IL (i. e. 110 % overload) for 57 s within a cycle time of 300 s

  • Frame sizes FSD to FSF

1.1 ? base-load current IL (i. e. 110 % overload) for 60 s within a cycle time of 300 s

  • High overload (HO)

Note: When the overload capability is used, the base-load current IH is not reduced.

  • Frame sizes FSA to FSC

2 ? base-load current IH (i. e. 200 % overload) for 3 s plus
1.5 ? base-load current IH (i. e. 150 % overload) for 57 s within a cycle time of 300 s

  • Frame sizes FSD to FSF

1.5 ? base-load current IH (i. e. 150 % overload) for 60 s within a cycle time of 300 s

Electromagnetic compatibility

  • Devices with line filter class A for applications according to Categories C3 and C2
  • Devices with line filter class B for applications according to Category C2 and compliance with conducted interference requirements of Category C1
  • Devices without line filter
  • Devices with line filter class A for applications according to Categories C3 and C2
  • Devices with line filter class B for applications according to Category C2 and compliance with conducted interference requirements of Category C1

Possible braking methods

DC braking

Operating temperature

 

  • Low overload (LO)

Frame sizes FSA to FSC: -10 ... +40 °C (14 ... 104 °F) without derating
Frame sizes FSD to FSF: 0 ... 40 °C (32 ... 104 °F) without derating

>40 ... 60 °C (104 ... 140 °F) see derating characteristics

  • High overload (HO)

Frame sizes FSA to FSC: -10 ... +50 °C (14 ... 122 °F) without derating
Frame sizes FSD to FSF: 0 ... 50 °C (32 ... 122 °F) without derating

>50 ... 60 ? (122 ... 140 °F) see derating characteristics

Storage temperature

-40 ... +70 °C (-40 ... +158 °F)

Relative humidity

<95 %, condensation not permissible

Cooling

Power units with increased air cooling using integrated fans

Installation altitude

Up to 1000 m (3281 ft) above sea level without derating,
> 1000 m (3281 ft) see derating characteristics

Protection functions

  • Undervoltage
  • Overvoltage
  • Overcurrent/overload
  • Overtemperature
  • Ground fault
  • Short-circuit
  • Stall protection
  • Motor blocking protection
  • Motor overtemperature
  • Inverter overtemperature
  • Parameter locking

Compliance with standards

UL 1), cUL 2), CE, RCM, SEMI F47

Rated short-circuit current SCCR (Short Circuit Current Rating) 3)

Frame sizes FSA to FSC: 40 kA
Frame sizes FSD to FSF: 65 kA

65 kA

CE marking

According to Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU



1) For degree of protection IP55/UL Type 12, the UL approval only applies to frame sizes FSA to FSC.

2) Applies to PM230 Power Modules, frame sizes FSA to FSC.

3) Applies to industrial control panel installations acc. to NEC Article 409 or UL 508A/508C.

 

PM230 Power Modules degree of protection IP55/UL Type 12

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules, degree of protection IP55/UL Type 12

With integrated line filter class A

6SL3223-0DE13-7AA1

6SL3223-0DE15-5AA1

6SL3223-0DE17-5AA1

6SL3223-0DE21-1AA1

6SL3223-0DE21-5AA1

With integrated line filter class B

6SL3223-0DE13-7BA1

6SL3223-0DE15-5BA1

6SL3223-0DE17-5BA1

6SL3223-0DE21-1BA1

6SL3223-0DE21-5BA1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IL1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IH2)

A

0.9

1.3

1.7

2.2

3.1

  • Maximum current Imax

A

2

2.6

3.4

4.7

6.2

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

1.5 (2)

  • Based on IH

kW (hp)

0.25 (0.34)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

 

0.86

0.9

0.92

0.94

0.95

Power loss 3)

at rated current

kW

0.04

0.043

0.047

0.055

0.064

Cooling air requirement

m3/s (ft3/s)

0.007 (0.2)

0.007 (0.2)

0.007 (0.2)

0.007 (0.2)

0.007 (0.2)

Sound pressure level

LpA (1 m/3.28 ft)

dB

61.9

61.9

61.9

61.9

61.9

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

1.3

1.8

2.3

3.2

4.2

  • Based on IH

A

0.9

1.3

1.8

2.3

3.2

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor connection

U2, V2, W2

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection 6)

 

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

154 (6.06)

154 (6.06)

154 (6.06)

154 (6.06)

154 (6.06)

  • Height

mm (in)

460 (18.11)

460 (18.11)

460 (18.1)

460 (18.11)

460 (18.1)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

249 (9.80)

249 (9.80)

249 (9.80)

249 (9.80)

249 (9.80)

  • With operator panel, max.

mm (in)

266 (10.47)

266 (10.47)

266 (10.47)

266 (10.47)

266 (10.47)

Frame size

 

FSA

FSA

FSA

FSA

FSA

Weight, approx.

kg (lb)

4.3 (9.48)

4.3 (9.48)

4.3 (9.48)

4.3 (9.48)

4.3 (9.48)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800?3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For further information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules, degree of protection IP55/UL Type 12

With integrated line filter class A

6SL3223-0DE22-2AA1

6SL3223-0DE23-0AA1

6SL3223-0DE24-0AA1

6SL3223-0DE25-5AA1

6SL3223-0DE27-5AA1

With integrated line filter class B

6SL3223-0DE22-2BA1

6SL3223-0DE23-0BA1

6SL3223-0DE24-0BA1

6SL3223-0DE25-5BA1

6SL3223-0DE27-5BA1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IL1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IH2)

A

4.1

5.9

7.7

10.2

13.2

  • Maximum current Imax

A

8.9

11.8

15.4

20.4

27

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

2.2 (3)

3 (4.02)

4 (5)

5.5 (7.38)

7.5 (16.5)

  • Based on IH

kW (hp)

1.5 (2)

2.2 (3)

3 (4.02)

4 (5)

5.5 (7.38)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

 

0.96

0.96

0.97

0.97

0.97

Power loss 3)

at rated current

kW

0.086

0.11

0.137

0.173

0.235

Cooling air requirement

m3/s (ft3/s)

0.007 (0.2)

0.007 (0.2)

0.009 (0.3)

0.009 (0.3)

0.009 (0.3)

Sound pressure level

LpA (1 m/3.28 ft)

dB

61.9

61.9

62.8

62.8

62.8

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

6.1

8

11

14

19

  • Based on IH

A

4.2

6.1

8

11

14

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

2.5 ... 6

4 ... 6

4 ... 6

Motor connection

U2, V2, W2

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

2.5 ... 6

4 ... 6

4 ... 6

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection 6)

 

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

154 (6.06)

154 (6.06)

180 (7.09)

180 (7.09)

180 (7.09)

  • Height

mm (in)

460 (18.11)

460 (18.11)

540 (21.26)

540 (21.26)

540 (21.26)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

249 (9.80)

249 (9.80)

249 (9.80)

249 (9.80)

249 (9.80)

  • With operator panel, max.

mm (in)

266 (10.47)

266 (10.47)

266 (10.47)

266 (10.47)

266 (10.47)

Frame size

 

FSA

FSA

FSB

FSB

FSB

Weight, approx.

kg (lb)

4.3 (9.48)

4.3 (9.48)

6.3 (14)

6.3 (14)

6.3 (14)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800?3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For further information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules, degree of protection IP55/UL Type 12

With integrated line filter class A

6SL3223-0DE31-1AA1

6SL3223-0DE31-5AA1

6SL3223-0DE31-8AA1

6SL3223-0DE32-2AA0

6SL3223-0DE33-0AA0

With integrated line filter class B

6SL3223-0DE31-1BA1

6SL3223-0DE31-5BA1

6SL3223-0DE31-8BA0

6SL3223-0DE32-2BA0

6SL3223-0DE33-0BA0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

 

  • Rated current Irated1)

A

26

32

38

38

45

60

  • Base-load current IL1)

A

26

32

38

38

45

60

  • Base-load current IH2)

A

18

26

32

32

38

45

  • Maximum current Imax

A

39

52

64

48

57

67

Rated power

 

 

 

 

 

 

 

  • Based on IL

kW (hp)

11 (24.26)

15 (20.12)

18.5 (24.81)

18.5 (24.81)

22 (29.50)

30 (40.23)

  • Based on IH

kW (hp)

7.5 (16.5)

11 (24.26)

15 (20.12)

15 (20.12)

18.5 (24.81)

22 (29.50)

Rated pulse frequency

kHz

4

4

4

4

4

4

Efficiency ?

 

0.97

0.97

0.98

0.97

0.97

0.97

Power loss 3)

at rated current

kW

0.299

0.365

0.435

0.478

0.569

0.784

Cooling air requirement

m3/s (ft3/s)

0.02 (0.7)

0.02 (0.7)

0.02 (0.7)

0.039 (1.4)

0.039 (1.4)

0.039 (1.4)

Sound pressure level

LpA (1 m/3.28 ft)

dB

66.1

66.1

66.1

56

56

56

24 V DC power supply

for Control Unit

A

1

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

 

  • Rated current

A

27

33

39

39

42

56

  • Based on IH

A

19

27

33

33

36

42

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

M6 screw studs

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

10 ... 16

10 ... 16

16 ... 35

16 ... 35

16 ... 35

Motor connection

U2, V2, W2

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

M6 screw studs

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

10 ... 16

10 ... 16

16 ... 35

16 ... 35

16 ... 35

Motor cable length, max. 5)

 

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection 6)

 

IP55/UL Type 12

IP55/UL Type 12

IP55/UL Type 12

IP55

IP55

IP55

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

230 (9.06)

230 (9.06)

230 (9.06)

320 (12.60)

320 (12.60)

320 (12.60)

  • Height

mm (in)

620 (24.41)

620 (24.41)

620 (24.41)

640 (25.20)

640 (25.20)

640 (25.20)

  • Depth

 

 

 

 

 

 

 

  • Without operator panel

mm (in)

249 (9.80)

249 (9.80)

249 (9.80)

329 (12.95)

329 (12.95)

329 (12.95)

  • With operator panel, max.

mm (in)

266 (10.47)

266 (10.47)

266 (10.47)

346 (13.62)

346 (13.62)

346 (13.62)

Frame size

 

FSC

FSC

FSC

FSD

FSD

FSD

Weight, approx.

kg (lb)

9.5 (20.95)

9.5 (20.95)

9.5 (20.95)

31 (68.36)

31 (68.36)

31 (68.36)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800?3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For further information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules, degree of protection IP55/UL Type 12

With integrated line filter class A

6SL3223-0DE33-7AA0

6SL3223-0DE34-5AA0

6SL3223-0DE35-5AA0

6SL3223-0DE37-5AA0

6SL3223-0DE38-8AA0

With integrated line filter class B

6SL3223-0DE33-7BA0

6SL3223-0DE34-5BA0

6SL3223-0DE35-5BA0

6SL3223-0DE37-5BA0

6SL3223-0DE38-8BA0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

75

90

110

145

178

  • Base-load current IL1)

A

75

90

110

145

178

  • Base-load current IH2)

A

60

75

90

110

145

  • Maximum current Imax

A

90

112

135

165

217

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

37 (49.62)

45 (60.35)

55 (73.76)

75 (100.58)

90 (120.69)

  • Based on IH

kW (hp)

30 (40.23)

37 (81.59)

45 (99.23)

55 (73.76)

75 (165.38)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

 

0.97

0.97

0.97

0.97

0.97

Power loss 3)

at rated current

kW

0.855

1.073

1.122

1.542

1.98

Cooling air requirement

m3/s (ft3/s)

0.039 (1.4)

0.039 (1.4)

0.117 (4.1)

0.117 (4.1)

0.117 (4.1)

Sound pressure level

LpA (1 m/3.28 ft)

dB

56

56

61

61

61

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

70

84

102

135

166

  • Based on IH

A

56

70

84

102

135

Line supply connection

U1/L1, V1/L2, W1/L3

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

35 ... 120

Motor connection

U2, V2, W2

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

35 ... 120

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection 6)

 

IP55

IP55

IP55

IP55

IP55

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

320 (12.60)

320 (12.60)

410 (16.14)

410 (16.14)

410 (16.14)

  • Height

mm (in)

751 (29.57)

751 (29.57)

915 (36.02)

915 (36.02)

915 (36.02)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

329 (12.95)

329 (12.95)

416 (16.38)

416 (16.38)

416 (16.38)

  • With operator panel, max.

mm (in)

346 (13.62)

346 (13.62)

433 (17.05)

433 (17.05)

433 (17.05)

Frame size

 

FSE

FSE

FSF

FSF

FSF

Weight, approx.

kg (lb)

37 (with filter cl. A)
38 (with filter cl. B)

37 (with filter cl. A)
38 (with filter cl. B)

70

70

70



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800?3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.

6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For further information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.

 

PM230 Power Modules degree of protection IP20 standard variant

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 standard variant

Without integrated line filter

6SL3210-1NE11-3UL1

6SL3210-1NE11-7UL1

6SL3210-1NE12-2UL1

6SL3210-1NE13-1UL1

6SL3210-1NE14-1UL1

With integrated line filter class A

6SL3210-1NE11-3AL1

6SL3210-1NE11-7AL1

6SL3210-1NE12-2AL1

6SL3210-1NE13-1AL1

6SL3210-1NE14-1AL1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IL1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IH2)

A

0.9

1.3

1.7

2.2

3.1

  • Maximum current Imax

A

2

2.6

3.4

4.7

6.2

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

1.5 (2)

  • Based on IH

kW (hp)

0.25 (0.34)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

 

0.89

0.93

0.93

0.94

0.95

Power loss 3)

at rated current

kW

0.031

0.034

0.041

0.049

0.06

Cooling air requirement

m3/s (ft3/s)

0.002 (0.1)

0.002 (0.1)

0.005 (0.2)

0.005 (0.2)

0.005 (0.2)

Sound pressure level

LpA (1 m/3.28 ft)

dB

<50

<50

<50

<50

<50

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

1.3

1.8

2.3

3.2

4.2

  • Based on IH

A

0.9

1.3

1.8

2.3

3.2

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor connection

U2, V2, W2

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

  • Height

mm (in)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

Frame size

 

FSA

FSA

FSA

FSA

FSA

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

  • With integrated line filter

kg (lb)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 standard variant

Without integrated line filter

6SL3210-1NE15-8UL1

6SL3210-1NE17-7UL1

6SL3210-1NE21-0UL1

6SL3210-1NE21-3UL1

6SL3210-1NE21-8UL1

With integrated line filter class A

6SL3210-1NE15-8AL1

6SL3210-1NE17-7AL1

6SL3210-1NE21-0AL1

6SL3210-1NE21-3AL1

6SL3210-1NE21-8AL1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IL1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IH2)

A

4.1

5.9

7.7

10.2

13.2

  • Maximum current Imax

A

8.9

11.8

15.4

20.4

27

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

2.2 (3)

3 (4.02)

4 (5)

5.5 (7.38)

7.5 (16.5)

  • Based on IH

kW (hp)

1.5 (2)

2.2 (3)

3 (4.02)

4 (5)

5.5 (7.38)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

 

0.96

0.96

0.97

0.97

0.97

Power loss 3)

at rated current

kW

0.078

0.102

0.13

0.165

0.224

Cooling air requirement

m3/s (ft3/s)

0.005 (0.2)

0.005 (0.2)

0.009 (0.3)

0.009 (0.3)

0.009 (0.3)

Sound pressure level

LpA (1 m/3.28 ft)

dB

<50

<50

<62

<62

<62

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

6.1

8

11

14

19

  • Based on IH

A

4.2

6.1

8

11

14

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 2.5

1.5 ... 6

1.5 ... 6

1.5 ... 6

Motor connection

U2, V2, W2

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 2.5

1.5 ... 6

1.5 ... 6

1.5 ... 6

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

73 (2.87)

73 (2.87)

100 (328.10)

100 (328.10)

100 (328.10)

  • Height

mm (in)

196 (7.72)

196 (7.72)

292 (11.50)

292 (11.50)

292 (11.50)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

Frame size

 

FSA

FSA

FSB

FSB

FSB

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

1.4 (3.09)

1.4 (3.09)

2.8 (6.17)

2.8 (6.17)

2.8 (6.17)

  • With integrated line filter

kg (lb)

1.6 (3.53)

1.6 (3.53)

3 (4.02)

3 (4.02)

3 (4.02)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 standard variant

Without integrated line filter

6SL3210-
1NE22-6UL1

6SL3210-
1NE23-2UL1

6SL3210-
1NE23-8UL1

6SL3210-
1NE24-5UL0

6SL3210-
1NE26-0UL0

With integrated line filter class A

6SL3210-
1NE22-6AL1

6SL3210-
1NE23-2AL1

6SL3210-
1NE23-8AL1

6SL3210-
1NE24-5AL0

6SL3210-
1NE26-0AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated1)

A

26

32

38

45

60

  • Base-load current IL1)

A

26

32

38

45

60

  • Base-load current IH2)

A

18

26

32

38

45

  • Maximum current Imax

A

39

52

64

57

67

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

11 (14.8)

15 (20.1)

18.5 (24.8)

22 (29.5)

30 (40.2)

  • Based on IH

kW (hp)

7.5 (10.1)

11 (14.8)

15 (20.1)

18.5 (24.8)

22 (29.5)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

 

0.97

0.97

0.98

0.98

0.97

Power loss 3)

at rated current

kW

0.291

0.355

0.423

0.539

0.726

Cooling air requirement

m3/s (ft3/s)

0.019 (0.7)

0.019 (0.7)

0.019 (0.7)

0.08 (2.8)

0.08 (2.8)

Sound pressure level

LpA (1 m/3.28 ft)

dB

<65

<65

<65

<60

<60

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

27

33

39

42

56

  • Based on IH

A

19

27

33

36

42

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

6 ... 16

16 ... 35

16 ... 35

Motor connection

U2, V2, W2

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

6 ... 16

16 ... 35

16 ... 35

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

140 (5.51)

140 (5.51)

140 (5.51)

275 (10.83)

275 (10.83)

  • Height

 

 

 

 

 

 

  • Without integrated line filter

mm (in)

355 (13.98)

355 (13.98)

355 (13.98)

419 (16.50)

419 (16.50)

  • With integrated line filter

mm (in)

355 (13.98)

355 (13.98)

355 (13.98)

512 (20.16)

512 (20.16)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

204 (8.03)

204 (8.03)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

275 (10.83)

275 (10.83)

Frame size

 

FSC

FSC

FSC

FSD

FSD

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

4.5 (9.92)

4.5 (9.92)

4.5 (9.92)

11 (24.26)

11 (24.26)

  • With integrated line filter

kg (lb)

5.1 (11.25)

5.1 (11.25)

5.1 (11.25)

14 (30.87)

14 (30.87)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 standard variant

Without integrated line filter

6SL3210-1NE27-5UL0

6SL3210-1NE28-8UL0

6SL3210-1NE31-1UL0

6SL3210-1NE31-5UL0

With integrated line filter class A

6SL3210-1NE27-5AL0

6SL3210-1NE28-8AL0

6SL3210-1NE31-1AL0

6SL3210-1NE31-5AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

  • Rated current Irated1)

A

75

90

110

145

  • Base-load current IL1)

A

75

90

110

145

  • Base-load current IH2)

A

60

75

90

110

  • Maximum current Imax

A

90

112

135

165

Rated power

 

 

 

 

 

  • Based on IL

kW (hp)

37 (49.6)

45 (60.3)

55 (73.8)

75 (101)

  • Based on IH

kW (hp)

30 (40.23)

37 (49.62)

45 (60.35)

55 (73.8)

Rated pulse frequency

kHz

4

4

4

4

Efficiency ?

 

0.97

0.97

0.97

0.97

Power loss 3)

at rated current

kW

0.791

0.976

1.237

1.69

Cooling air requirement

m3/s (ft3/s)

0.08 (2.8)

0.08 (2.8)

0.15 (5.3)

0.15 (5.3)

Sound pressure level

LpA (1 m/3.28 ft)

dB

<60

<60

<60

<60

24 V DC power supply

for Control Unit

A

1

1

1

1

Input current 4)

 

 

 

 

 

  • Rated current

A

70

84

102

135

  • Based on IH

A

56

70

84

102

Line supply connection

U1/L1, V1/L2, W1/L3

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

Motor connection

U2, V2, W2

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

Motor cable length, max. 5)

 

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection

 

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

  • Width

mm (in)

275 (10.83)

275 (10.83)

350 (13.78)

350 (13.78)

  • Height

 

 

 

 

 

  • Without integrated line filter

mm (in)

499 (19.65)

499 (19.65)

634 (24.96)

634 (24.96)

  • With integrated line filter

mm (in)

635 (25)

635 (25)

934 (36.77)

934 (36.77)

  • Depth

 

 

 

 

 

  • Without operator panel

mm (in)

204 (8.03)

204 (8.03)

316 (12.44)

316 (12.44)

  • With operator panel, max.

mm (in)

275 (10.83)

275 (10.83)

387 (15.24)

387 (15.24)

Frame size

 

FSE

FSE

FSF

FSF

Weight, approx.

 

 

 

 

 

  • Without integrated line filter

kg (lb)

15 (20.12)

15 (20.12)

34 (74.97)

34 (74.97)

  • With integrated line filter

kg (lb)

22 (29.50)

22 (29.50)

46 (101.43)

46 (101.43)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

PM230 Power Modules degree of protection IP20 push-through variant

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 push-through variant

Without integrated line filter

6SL3211-1NE17-7UL1

6SL3211-1NE21-8UL1

6SL3211-1NE23-8UL1

With integrated line filter class A

6SL3211-1NE17-7AL1

6SL3211-1NE21-8AL1

6SL3211-1NE23-8AL1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

  • Rated current Irated1)

A

7.7

18

38

  • Base-load current IL1)

A

7.7

18

38

  • Base-load current IH2)

A

5.9

13.2

32

  • Maximum current Imax

A

11.8

27

64

Rated power

 

 

 

 

  • Based on IL

kW (hp)

3 (4.02)

7.5 (10.1)

18.5 (24.8)

  • Based on IH

kW (hp)

2.2 (2.95)

5.5 (7.38)

15 (20.12)

Rated pulse frequency

kHz

4

4

4

Efficiency ?

 

0.96

0.97

0.98

Power loss 3)

at rated current

kW

0.102

0.224

0.423

Cooling air requirement

m3/s (ft3/s)

0.005 (0.2)

0.009 (0.3)

0.019 (0.7)

Sound pressure level

LpA (1 m/3.28 ft)

dB

<56

<62

<65

24 V DC power supply

for Control Unit

A

1

1

1

Input current 4)

 

 

 

 

  • Rated current

A

8

19

39

  • Based on IH

A

6.1

14

33

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

4 ... 6

6 ... 16

Motor connection

U2, V2, W2

 

Screw terminals, plug-in

Screw terminals, plug-in

Screw terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

4 ... 6

10 ... 16

Motor cable length, max. 5)

 

 

 

 

  • Shielded

m (ft)

25 (82.03)

25 (82.03)

25 (82.03)

  • Unshielded

m (ft)

100 (328.10)

100 (328.10)

100 (328.10)

Degree of protection

 

IP20

IP20

IP20

Dimensions

 

 

 

 

  • Width

mm (in)

126 (4.96)

154 (6.06)

200 (7.87)

  • Height

mm (in)

238 (9.37)

345 (13.58)

411 (16.18)

  • Depth

 

 

 

 

  • Without operator panel

mm (in)

171 (6.73)

171 (6.73)

171 (6.73)

  • With operator panel, max.

mm (in)

251 (9.88)

251 (9.88)

251 (9.88)

Frame size

 

FSA

FSB

FSC

Weight, approx.

With integrated line filter

 

 

 

 

  • Without integrated line filter

kg (lb)

1.7 (3.75)

3.4 (7.50)

5.4 (11.91)

  • With integrated line filter

kg (lb)

1.9 (4.19)

3.6 (7.94)

6 (13.23)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
Êàòàëîã îáîðóäîâàíèÿ 2017
Siemens Industry Catalog Drive Technology Converters AC Low-voltage converters SINAMICS V basic performance converters General performance converters SINAMICS G SINAMICS G110 standard inverters SINAMICS G120C compact inverters SINAMICS G120P and G120P Cabinet pump, fan, compressor converters Highlights Introduction SINAMICS G120P and G120P Cabinet pump, fan, compressor converters Integrated Drive Systems SINAMICS G120P, built-in and wall-mounted units, IP20/IP54/IP55 CU230P-2 Control Units PM230 Power Modules, 0.37 kW to 90 kW PM230 Power Modules Line-side components Output-side power components PM240 Power Modules, 90 kW to 132 kW PM330 Power Modules, 160 kW to 630 kW Supplementary system components Spare parts SINAMICS G120P Cabinet, cabinet units, IP20 to IP54 Selection and engineering tools Services and documentation SINAMICS G120 standard inverters SINAMICS G110M distributed inverters SINAMICS G110D distributed inverters SINAMICS G120D distributed inverters SINAMICS G130 Drive converter chassis units SINAMICS G150 Drive converter cabinet units SINAMICS G180 High performance converters SINAMICS S Frequency inverters MICROMASTER SIPLUS POSMO A LOHER DYNAVERT Drive System Medium-Voltage AC Converter DC converter units Motors Generators Geared Motors Flender Gear Units Couplings Selection and engineering tools Further Components Automation Technology Energy Building Technologies Low-Voltage Controls and Distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services ... and everything else you need




  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà