Supply voltage | |
Load voltage L+ | |
| 24 V |
| Yes |
Input current | |
from load voltage L+ (without load), max. | 180 mA |
from backplane bus 5 V DC, max. | 100 mA |
Output voltage | |
Power supply to the transmitters | |
| Yes |
| 15 V; at 22 mA |
| Yes; approx. 30 mA |
| 29.6 V |
Power loss | |
Power loss, typ. | 4.5 W |
Analog inputs | |
Number of analog inputs | 2 |
permissible input current for current input (destruction limit), max. | 40 mA |
Input ranges | |
| Yes |
Input ranges (rated values), currents | |
| Yes |
| 50 ? |
| Yes |
| 50 ? |
Cable length | |
| 400 m |
Analog value generation for the inputs | |
Measurement principle | Sigma Delta |
Integration and conversion time/resolution per channel | |
| 16 bit; 10 bit to 15 bit + sign |
| Yes |
| 2,5 / 16,67 / 20 / 100 ms |
| 2.5 / 16.67 / 20 / 100 (1 channel enabled); 7.5 / 50 / 60 / 300 (2 channels enabled) |
| 10 / 50 / 60 / 400 Hz |
Encoder | |
Connection of signal encoders | |
| Yes |
| Yes |
Errors/accuracies | |
Linearity error (relative to input range), (+/-) | 0.01 % |
Temperature error (relative to input range), (+/-) | 0.01 %/K |
Crosstalk between the inputs, min. | 130 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range | |
| 0.55 %; From 0/4 to 20 mA |
Basic error limit (operational limit at 25 °C) | |
| 0.1 %; From 0/4 to 20 mA |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
| 60 dB |
| 130 dB |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes; can be set in parameters, red LED, alarm message |
Alarms | |
| Yes; Parameterizable |
| Yes; Parameterizable, channels 0 and 1 |
Diagnostic messages | |
| Yes |
| Yes; Red LED, signal |
| Yes; Red LED, signal |
| Yes; Red LED, signal |
| Yes; green LED (H) |
Diagnostics indication LED | |
| Yes |
| Yes |
Ex(i) characteristics | |
Module for Ex(i) protection | Yes |
Maximum values of input circuits (per channel) | |
| 62 nF |
| 96.1 mA |
| 3 mH |
| 511 mW |
| 26 V |
| 250 V; DC |
| 0.6 °C |
Potential separation | |
Potential separation analog inputs | |
| Yes |
| Yes |
Permissible potential difference | |
between the inputs (UCM) | 60 V DC/30 V AC |
Isolation | |
tested with | |
| 1500 V AC |
| 1500 V AC |
| 500 V DC |
Standards, approvals, certificates | |
CE mark | Yes |
UL approval | Yes; File E239877 |
FM approval | Yes; CofC 3028431 |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
Use in hazardous areas | |
| KEMA 09 ATEX 0082X |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 40 mm |
Height | 125 mm |
Depth | 120 mm |
Weights | |
Weight, approx. | 260 g |