SIPLUS SM 322 digital output module

Article number

6AG1322-1BF01-2XB0

6AG1322-8BF00-2AB0

6AG1322-1BH01-2AA0

6AG1322-1BL00-2AA0

SIPLUS S7-300 SM322 8DO/24VDC 2A

SIPLUS SM322 8DA/24VDC

SIPLUS S7-300 SM322 16DA/24VDC 0.5A

SIPLUS S7-300 SM322 32DO/24VDC 0.5A

Supply voltage

 

 

 

 

Load voltage L+

 

 

 

 

  • ? Rated value (DC)

24 V

24 V

24 V

24 V

Input current

 

 

 

 

from load voltage L+ (without load), max.

60 mA

90 mA

80 mA

160 mA

from backplane bus 5 V DC, max.

40 mA

70 mA

80 mA

110 mA

Power loss

 

 

 

 

Power loss, typ.

6.8 W

5 W

4.9 W

6.6 W

Digital outputs

 

 

 

 

Number of digital outputs

8

8

16

32

Limitation of inductive shutdown voltage to

L+ (-48 V)

L+ (-45 V)

L+ (-53 V)

L+ (-53 V)

Switching capacity of the outputs

 

 

 

 

  • ? on lamp load, max.

10 W

5 W

5 W

5 W

Load resistance range

 

 

 

 

  • ? lower limit

12 ?

48 ?

48 ?

48 ?

  • ? upper limit

4 k?

3 k?

4 k?

4 k?

Output voltage

 

 

 

 

  • ? for signal "1", min.

L+ (-0.8 V)

L+ (-0.8 to -1.6 V)

L+ (-0.8 V)

L+ (-0.8 V)

Output current

 

 

 

 

  • ? for signal "1" rated value

2 A

0.5 A

0.5 A

0.5 A

  • ? for signal "1" permissible range for 0 to 40 °C, min.

5 mA

10 mA

5 mA

5 mA

  • ? for signal "1" permissible range for 0 to 40 °C, max.

2.4 A

0.6 A

0.6 A

0.6 A

  • ? for signal "1" permissible range for 40 to 60 °C, min.

5 mA

10 mA

5 mA

5 mA

  • ? for signal "1" permissible range for 40 to 60 °C, max.

2.4 A

0.6 A

0.6 A

0.6 A

  • ? for signal "1" minimum load current

5 mA

10 mA

5 mA

5 mA

  • ? for signal "0" residual current, max.

0.5 mA

0.5 mA

0.5 mA

0.5 mA

Switching frequency

 

 

 

 

  • ? with resistive load, max.

100 Hz

100 Hz

100 Hz

100 Hz

  • ? with inductive load, max.

0.5 Hz

2 Hz

0.5 Hz

  • ? on lamp load, max.

10 Hz

10 Hz

10 Hz

10 Hz

Total current of the outputs (per group)

 

 

 

 

horizontal installation

 

 

 

 

  • up to 40 °C, max.

4 A

4 A

4 A

  • up to 60 °C, max.

4 A

3 A

3 A

3 A

  • up to 70 °C, max.

4 A

2.5 A; (without diode) & 1.5 A (with diode)

3 A

2 A

vertical installation

 

 

 

 

  • up to 40 °C, max.

4 A

4 A

2 A

2 A

Cable length

 

 

 

 

  • ? shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

  • ? unshielded, max.

600 m

600 m

600 m

600 m

Interrupts/diagnostics/status information

 

 

 

 

Diagnostic functions

No

Yes; Parameterizable

No

No

Alarms

 

 

 

 

  • ? Diagnostic alarm

No

Yes; Parameterizable

No

No

Potential separation

 

 

 

 

Potential separation digital outputs

 

 

 

 

  • ? between the channels

Yes

Yes

Yes

  • ? between the channels, in groups of

4

8

8

8

  • ? between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Isolation

 

 

 

 

Isolation tested with

500 V DC

500 V DC

500 V DC

500 V DC

Standards, approvals, certificates

 

 

 

 

CE mark

Yes

Yes

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

Yes; File E239877

Yes; File E239877

FM approval

Yes

Yes; CofC 3028431

Yes; CofC 3028431

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Yes

Railway application

 

 

 

 

  • ? EN 50121-4

No

  • ? EN 50155

No

Yes; T1 Category 1 Class A/B horizontal mounting position

Yes; T1 Category 1 Class A/B horizontal mounting position

Yes; T1 Category 1 Class A/B horizontal mounting position

Ambient conditions

 

 

 

 

Ambient temperature during operation

 

 

 

 

  • ? min.

-25 °C

-25 °C; = Tmin

-25 °C

-25 °C; = Tmin

  • ? max.

70 °C; = Tmax; 60 °C @ UL/cUL use

70 °C; = Tmax; 60 °C @ UL/cUL use

70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies

70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies

Ambient temperature during storage/transportation

 

 

 

 

  • ? min.

-40 °C

-40 °C

-40 °C

  • ? max.

70 °C

70 °C

70 °C

Extended ambient conditions

 

 

 

 

  • ? relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

 

 

 

 

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

 

 

 

 

  • against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

  • against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

 

 

 

 

required front connector

20-pin

20-pin

20-pin

40-pin

Dimensions

 

 

 

 

Width

40 mm

40 mm

40 mm

40 mm

Height

125 mm

125 mm

125 mm

125 mm

Depth

120 mm

120 mm

120 mm

120 mm

Weights

 

 

 

 

Weight, approx.

190 g

210 g

190 g

260 g


Article number

6AG1322-1CF00-7AA0

6AG1322-1HF10-2AA0

6AG1322-5HF00-4AB0

6AG1322-1FF01-7AA0

SIPLUS SM322 8DA/48-125VDC

SIPLUS SM322 8DA - Relais

SIPLUS_SM322_8RO

SIPLUS S7-300 SM322 8DA/120/220VAC 1A

Supply voltage

 

 

 

 

Load voltage L+

 

 

 

 

  • ? Rated value (DC)

48 V; 48 V DC to 125 V DC

120 V

24 V

Load voltage L1

 

 

 

 

  • ? Rated value (AC)

230 V

230 V

230 V; 120/230V AC

Input current

 

 

 

 

from supply voltage L+, max.

125 mA

160 mA

from load voltage L+ (without load), max.

2 mA

from load voltage L1 (without load), max.

2 mA

from backplane bus 5 V DC, max.

100 mA

40 mA

100 mA

100 mA

Power loss

 

 

 

 

Power loss, typ.

7.2 W

4.2 W

3.5 W

8.6 W

Digital outputs

 

 

 

 

Number of digital outputs

8

8; Relays

8; Relays

8

Limitation of inductive shutdown voltage to

M (-1 V)

Switching capacity of the outputs

 

 

 

 

  • ? on lamp load, max.

15 W; 15 W (48 V) or 40 W (125 V)

1 500 W; 230 V AC

1 500 W; 230 V AC

50 W

Output voltage

 

 

 

 

  • ? for signal "1", min.

L+ (-1.2 V)

L1 (-1.5 V)

Output current

 

 

 

 

  • ? for signal "1" rated value

1.5 A

5 A

5 A

2 A

  • ? for signal "1" permissible range for 0 to 40 °C, min.

10 mA

10 mA

  • ? for signal "1" permissible range for 0 to 40 °C, max.

1.5 A

2 A

  • ? for signal "1" permissible range for 40 to 60 °C, min.

10 mA

10 mA

  • ? for signal "1" permissible range for 40 to 60 °C, max.

1.5 A

1 A

  • ? for signal "1" minimum load current

10 mA

5 mA

10 mA

10 mA

  • ? for signal "1" permissible surge current, max.

3 A; for 10 ms

20 A; max. 1 AC cycle

  • ? for signal "0" residual current, max.

0.5 mA

2 mA

Switching frequency

 

 

 

 

  • ? with resistive load, max.

25 Hz

2 Hz

2 Hz

10 Hz

  • ? with inductive load, max.

0.5 Hz

0.5 Hz

0.5 Hz

0.5 Hz

  • ? on lamp load, max.

10 Hz

2 Hz

2 Hz

1 Hz

  • ? mechanical, max.

10 Hz

10 Hz

Total current of the outputs (per group)

 

 

 

 

horizontal installation

 

 

 

 

  • up to 40 °C, max.

6 A

4 A

  • up to 60 °C, max.

3 A

5 A

5 A

2 A

  • up to 70 °C, max.

1 A

5 A

1.5 A

vertical installation

 

 

 

 

  • up to 40 °C, max.

4 A

5 A

5 A

2 A

Relay outputs

 

 

 

 

  • ? Rated supply voltage of relay coil L+ (DC)

24 V

  • ? Number of operating cycles, max.

300 000; 300000 (24 V DC, at 2 A); 200000 (120 V AC, at 3 A); 100000 (230 V AC, at 3 A)

100 000; 100000 (24 V DC, at 5 A), 100000 (230 V AC, at 5 A)

Switching capacity of contacts

 

 

 

 

  • with inductive load, max.

3 A; 3 A (230 V DC), 2 A (24 V AC)

5 A; 5 A (230 V DC), 5 A (24 V AC)

  • with resistive load, max.

8 A; 8 A (230 V DC), 5 A (24 V AC)

5 A; 5 A (230 V DC), 5 A (24 V AC)

Cable length

 

 

 

 

  • ? shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

  • ? unshielded, max.

600 m

600 m

600 m

600 m

Interrupts/diagnostics/status information

 

 

 

 

Diagnostic functions

No

No

Yes; Parameterizable

Yes; Fuse blown or load voltage missing

Alarms

 

 

 

 

  • ? Diagnostic alarm

No

No

Yes; Parameterizable

No

Potential separation

 

 

 

 

Potential separation digital outputs

 

 

 

 

  • ? between the channels

Yes

Yes

Yes

Yes

  • ? between the channels, in groups of

4

1

1

4

  • ? between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Isolation

 

 

 

 

Isolation tested with

1500 V AC

2000 V AC

1500 V AC

1500 V AC

Standards, approvals, certificates

 

 

 

 

CE mark

Yes

Yes

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

Yes; File E239877

Yes; File E239877

FM approval

Yes; CofC 3028431

Yes; CofC 3028431

Yes; CofC 3028431

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Yes

Yes

Railway application

 

 

 

 

  • ? EN 50155

Yes; T1 Category 1 Class A/B horizontal mounting position

Yes; T1 Category 1 Class A/B horizontal mounting position

Yes; T1 Category 1 Class A/B horizontal mounting position

Ambient conditions

 

 

 

 

Ambient temperature during operation

 

 

 

 

  • ? min.

-25 °C

-25 °C

0 °C; = Tmin

-40 °C

  • ? max.

70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies

60 °C

60 °C; = Tmax

70 °C; = Tmax; for use on railway vehicles according to EN 50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/UL hazardous use applies

Ambient temperature during storage/transportation

 

 

 

 

  • ? min.

-40 °C

-40 °C

-40 °C

-40 °C

  • ? max.

70 °C

70 °C

70 °C

70 °C

Extended ambient conditions

 

 

 

 

  • ? relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

 

 

 

 

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

 

 

 

 

  • against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

  • against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

 

 

 

 

required front connector

20-pin

40-pin

40-pin

20-pin

Dimensions

 

 

 

 

Width

40 mm

40 mm

40 mm

40 mm

Height

125 mm

125 mm

125 mm

125 mm

Depth

120 mm

120 mm

120 mm

120 mm

Weights

 

 

 

 

Weight, approx.

250 g

320 g

320 g

275 g


Article number

6AG1322-5FF00-4AB0

6AG1322-1FH00-7AA0

6AG1322-1HH01-2AA0

SIPLUS S7-300 SM322 8DO

SIPLUS S7-300 SM 322 16DO 120/230VAC 1A

SIPLUS SM322

Supply voltage

 

 

 

Load voltage L+

 

 

 

  • ? Rated value (DC)

120 V

Load voltage L1

 

 

 

  • ? Rated value (AC)

230 V; 120/230V AC

230 V; 120/230V AC

230 V

Input current

 

 

 

from supply voltage L+, max.

250 mA

from load voltage L1 (without load), max.

2 mA

2 mA

from backplane bus 5 V DC, max.

100 mA

200 mA

100 mA

Power loss

 

 

 

Power loss, typ.

8.6 W

8.6 W

4.5 W

Digital outputs

 

 

 

Number of digital outputs

8

16

16; Relays

Switching capacity of the outputs

 

 

 

  • ? on lamp load, max.

50 W

50 W

50 W; 230 V AC

Output voltage

 

 

 

  • ? for signal "1", min.

L1 (-8.5 V)

Output current

 

 

 

  • ? for signal "1" rated value

2 A

1 A

2 A

  • ? for signal "1" permissible range for 0 to 40 °C, min.

10 mA

10 mA

  • ? for signal "1" permissible range for 0 to 40 °C, max.

2 A

1 A

  • ? for signal "1" permissible range for 40 to 60 °C, min.

10 mA

10 mA

  • ? for signal "1" permissible range for 40 to 60 °C, max.

1 A

0.5 A

  • ? for signal "1" minimum load current

10 mA

10 mA

10 mA

  • ? for signal "1" permissible surge current, max.

20 A; with 2 half waves

20 A; with 2 half waves

  • ? for signal "0" residual current, max.

2 mA

2 mA

Switching frequency

 

 

 

  • ? with resistive load, max.

10 Hz

10 Hz

1 Hz

  • ? with inductive load, max.

0.5 Hz

0.5 Hz

0.5 Hz

  • ? on lamp load, max.

1 Hz

1 Hz

1 Hz

  • ? mechanical, max.

10 Hz

Total current of the outputs (per group)

 

 

 

horizontal installation

 

 

 

  • up to 40 °C, max.

8 A

4 A

  • up to 60 °C, max.

4 A

2 A

8 A

  • up to 70 °C, max.

1 A

vertical installation

 

 

 

  • up to 40 °C, max.

4 A

2 A

8 A

Relay outputs

 

 

 

  • ? Rated supply voltage of relay coil L+ (DC)

24 V

  • ? Number of operating cycles, max.

100 000; 50000 (24 V DC, at 2 A); 700000 (120 V AC, at 2 A); 100000 (230 V AC, at 2 A)

Switching capacity of contacts

 

 

 

  • with inductive load, max.

2 A; 2 A (230 V AC), 2 A (24 V DC)

  • with resistive load, max.

2 A; 2 A (230 V AC), 2 A (24 V DC)

Cable length

 

 

 

  • ? shielded, max.

1 000 m

1 000 m

1 000 m

  • ? unshielded, max.

600 m

600 m

600 m

Interrupts/diagnostics/status information

 

 

 

Diagnostic functions

Yes; Parameterizable

Yes; Fuse blown or load voltage missing

No

Alarms

 

 

 

  • ? Diagnostic alarm

Yes; Parameterizable

No

No

Potential separation

 

 

 

Potential separation digital outputs

 

 

 

  • ? between the channels

Yes

Yes

  • ? between the channels, in groups of

1

8

8

  • ? between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Isolation

 

 

 

Isolation tested with

1500 V AC

4 000 V DC

1500 V AC

Standards, approvals, certificates

 

 

 

CE mark

Yes

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

Yes; File E239877

FM approval

Yes; CofC 3028431

Yes; CofC 3028431

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Yes

Railway application

 

 

 

  • ? EN 50121-4

No

  • ? EN 50155

No

No

Yes; T1 Category 1 Class A/B horizontal mounting position

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • ? min.

0 °C; = Tmin

-40 °C; = Tmin

-40 °C

  • ? max.

60 °C; = Tmax

70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use

70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use

Ambient temperature during storage/transportation

 

 

 

  • ? min.

-40 °C

-40 °C

-40 °C

  • ? max.

70 °C

70 °C

70 °C

Extended ambient conditions

 

 

 

  • ? relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

 

 

 

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

 

 

 

  • against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

  • against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

 

 

 

required front connector

40-pin

20-pin

20-pin

Dimensions

 

 

 

Width

40 mm

40 mm

40 mm

Height

125 mm

125 mm

125 mm

Depth

120 mm

120 mm

120 mm

Weights

 

 

 

Weight, approx.

275 g

275 g

250 g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà