? for signal "1" permissible range for 0 to 40 °C, min.
5 mA
10 mA
5 mA
5 mA
? for signal "1" permissible range for 0 to 40 °C, max.
2.4 A
0.6 A
0.6 A
0.6 A
? for signal "1" permissible range for 40 to 60 °C, min.
5 mA
10 mA
5 mA
5 mA
? for signal "1" permissible range for 40 to 60 °C, max.
2.4 A
0.6 A
0.6 A
0.6 A
? for signal "1" minimum load current
5 mA
10 mA
5 mA
5 mA
? for signal "0" residual current, max.
0.5 mA
0.5 mA
0.5 mA
0.5 mA
Switching frequency
? with resistive load, max.
100 Hz
100 Hz
100 Hz
100 Hz
? with inductive load, max.
0.5 Hz
2 Hz
0.5 Hz
? on lamp load, max.
10 Hz
10 Hz
10 Hz
10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.
4 A
4 A
4 A
— up to 60 °C, max.
4 A
3 A
3 A
3 A
— up to 70 °C, max.
4 A
2.5 A; (without diode) & 1.5 A (with diode)
3 A
2 A
vertical installation
— up to 40 °C, max.
4 A
4 A
2 A
2 A
Cable length
? shielded, max.
1 000 m
1 000 m
1 000 m
1 000 m
? unshielded, max.
600 m
600 m
600 m
600 m
Interrupts/diagnostics/status information
Diagnostic functions
No
Yes; Parameterizable
No
No
Alarms
? Diagnostic alarm
No
Yes; Parameterizable
No
No
Potential separation
Potential separation digital outputs
? between the channels
Yes
Yes
Yes
? between the channels, in groups of
4
8
8
8
? between the channels and backplane bus
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Isolation
Isolation tested with
500 V DC
500 V DC
500 V DC
500 V DC
Standards, approvals, certificates
CE mark
Yes
Yes
Yes
Yes
UL approval
Yes; File E239877
Yes; File E239877
Yes; File E239877
Yes; File E239877
FM approval
Yes
Yes; CofC 3028431
Yes; CofC 3028431
Yes; CofC 3028431
RCM (formerly C-TICK)
Yes
Yes
Yes
KC approval
Yes
Yes
Yes
EAC (formerly Gost-R)
Yes
Yes
Yes
Railway application
? EN 50121-4
No
? EN 50155
No
Yes; T1 Category 1 Class A/B horizontal mounting position
Yes; T1 Category 1 Class A/B horizontal mounting position
Yes; T1 Category 1 Class A/B horizontal mounting position
Ambient conditions
Ambient temperature during operation
? min.
-25 °C
-25 °C; = Tmin
-25 °C
-25 °C; = Tmin
? max.
70 °C; = Tmax; 60 °C @ UL/cUL use
70 °C; = Tmax; 60 °C @ UL/cUL use
70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
Ambient temperature during storage/transportation
? min.
-40 °C
-40 °C
-40 °C
? max.
70 °C
70 °C
70 °C
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Connection method
required front connector
20-pin
20-pin
20-pin
40-pin
Dimensions
Width
40 mm
40 mm
40 mm
40 mm
Height
125 mm
125 mm
125 mm
125 mm
Depth
120 mm
120 mm
120 mm
120 mm
Weights
Weight, approx.
190 g
210 g
190 g
260 g
Article number
6AG1322-1CF00-7AA0
6AG1322-1HF10-2AA0
6AG1322-5HF00-4AB0
6AG1322-1FF01-7AA0
SIPLUS SM322 8DA/48-125VDC
SIPLUS SM322 8DA - Relais
SIPLUS_SM322_8RO
SIPLUS S7-300 SM322 8DA/120/220VAC 1A
Supply voltage
Load voltage L+
? Rated value (DC)
48 V; 48 V DC to 125 V DC
120 V
24 V
Load voltage L1
? Rated value (AC)
230 V
230 V
230 V; 120/230V AC
Input current
from supply voltage L+, max.
125 mA
160 mA
from load voltage L+ (without load), max.
2 mA
from load voltage L1 (without load), max.
2 mA
from backplane bus 5 V DC, max.
100 mA
40 mA
100 mA
100 mA
Power loss
Power loss, typ.
7.2 W
4.2 W
3.5 W
8.6 W
Digital outputs
Number of digital outputs
8
8; Relays
8; Relays
8
Limitation of inductive shutdown voltage to
M (-1 V)
Switching capacity of the outputs
? on lamp load, max.
15 W; 15 W (48 V) or 40 W (125 V)
1 500 W; 230 V AC
1 500 W; 230 V AC
50 W
Output voltage
? for signal "1", min.
L+ (-1.2 V)
L1 (-1.5 V)
Output current
? for signal "1" rated value
1.5 A
5 A
5 A
2 A
? for signal "1" permissible range for 0 to 40 °C, min.
10 mA
10 mA
? for signal "1" permissible range for 0 to 40 °C, max.
1.5 A
2 A
? for signal "1" permissible range for 40 to 60 °C, min.
10 mA
10 mA
? for signal "1" permissible range for 40 to 60 °C, max.
1.5 A
1 A
? for signal "1" minimum load current
10 mA
5 mA
10 mA
10 mA
? for signal "1" permissible surge current, max.
3 A; for 10 ms
20 A; max. 1 AC cycle
? for signal "0" residual current, max.
0.5 mA
2 mA
Switching frequency
? with resistive load, max.
25 Hz
2 Hz
2 Hz
10 Hz
? with inductive load, max.
0.5 Hz
0.5 Hz
0.5 Hz
0.5 Hz
? on lamp load, max.
10 Hz
2 Hz
2 Hz
1 Hz
? mechanical, max.
10 Hz
10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.
6 A
4 A
— up to 60 °C, max.
3 A
5 A
5 A
2 A
— up to 70 °C, max.
1 A
5 A
1.5 A
vertical installation
— up to 40 °C, max.
4 A
5 A
5 A
2 A
Relay outputs
? Rated supply voltage of relay coil L+ (DC)
24 V
? Number of operating cycles, max.
300 000; 300000 (24 V DC, at 2 A); 200000 (120 V AC, at 3 A); 100000 (230 V AC, at 3 A)
100 000; 100000 (24 V DC, at 5 A), 100000 (230 V AC, at 5 A)
Switching capacity of contacts
— with inductive load, max.
3 A; 3 A (230 V DC), 2 A (24 V AC)
5 A; 5 A (230 V DC), 5 A (24 V AC)
— with resistive load, max.
8 A; 8 A (230 V DC), 5 A (24 V AC)
5 A; 5 A (230 V DC), 5 A (24 V AC)
Cable length
? shielded, max.
1 000 m
1 000 m
1 000 m
1 000 m
? unshielded, max.
600 m
600 m
600 m
600 m
Interrupts/diagnostics/status information
Diagnostic functions
No
No
Yes; Parameterizable
Yes; Fuse blown or load voltage missing
Alarms
? Diagnostic alarm
No
No
Yes; Parameterizable
No
Potential separation
Potential separation digital outputs
? between the channels
Yes
Yes
Yes
Yes
? between the channels, in groups of
4
1
1
4
? between the channels and backplane bus
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Isolation
Isolation tested with
1500 V AC
2000 V AC
1500 V AC
1500 V AC
Standards, approvals, certificates
CE mark
Yes
Yes
Yes
Yes
UL approval
Yes; File E239877
Yes; File E239877
Yes; File E239877
Yes; File E239877
FM approval
Yes; CofC 3028431
Yes; CofC 3028431
Yes; CofC 3028431
Yes; CofC 3028431
RCM (formerly C-TICK)
Yes
Yes
Yes
Yes
KC approval
Yes
Yes
Yes
Yes
EAC (formerly Gost-R)
Yes
Yes
Yes
Yes
Railway application
? EN 50155
Yes; T1 Category 1 Class A/B horizontal mounting position
Yes; T1 Category 1 Class A/B horizontal mounting position
Yes; T1 Category 1 Class A/B horizontal mounting position
Ambient conditions
Ambient temperature during operation
? min.
-25 °C
-25 °C
0 °C; = Tmin
-40 °C
? max.
70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
60 °C
60 °C; = Tmax
70 °C; = Tmax; for use on railway vehicles according to EN 50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/UL hazardous use applies
Ambient temperature during storage/transportation
? min.
-40 °C
-40 °C
-40 °C
-40 °C
? max.
70 °C
70 °C
70 °C
70 °C
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Connection method
required front connector
20-pin
40-pin
40-pin
20-pin
Dimensions
Width
40 mm
40 mm
40 mm
40 mm
Height
125 mm
125 mm
125 mm
125 mm
Depth
120 mm
120 mm
120 mm
120 mm
Weights
Weight, approx.
250 g
320 g
320 g
275 g
Article number
6AG1322-5FF00-4AB0
6AG1322-1FH00-7AA0
6AG1322-1HH01-2AA0
SIPLUS S7-300 SM322 8DO
SIPLUS S7-300 SM 322 16DO 120/230VAC 1A
SIPLUS SM322
Supply voltage
Load voltage L+
? Rated value (DC)
120 V
Load voltage L1
? Rated value (AC)
230 V; 120/230V AC
230 V; 120/230V AC
230 V
Input current
from supply voltage L+, max.
250 mA
from load voltage L1 (without load), max.
2 mA
2 mA
from backplane bus 5 V DC, max.
100 mA
200 mA
100 mA
Power loss
Power loss, typ.
8.6 W
8.6 W
4.5 W
Digital outputs
Number of digital outputs
8
16
16; Relays
Switching capacity of the outputs
? on lamp load, max.
50 W
50 W
50 W; 230 V AC
Output voltage
? for signal "1", min.
L1 (-8.5 V)
Output current
? for signal "1" rated value
2 A
1 A
2 A
? for signal "1" permissible range for 0 to 40 °C, min.
10 mA
10 mA
? for signal "1" permissible range for 0 to 40 °C, max.
2 A
1 A
? for signal "1" permissible range for 40 to 60 °C, min.
10 mA
10 mA
? for signal "1" permissible range for 40 to 60 °C, max.
1 A
0.5 A
? for signal "1" minimum load current
10 mA
10 mA
10 mA
? for signal "1" permissible surge current, max.
20 A; with 2 half waves
20 A; with 2 half waves
? for signal "0" residual current, max.
2 mA
2 mA
Switching frequency
? with resistive load, max.
10 Hz
10 Hz
1 Hz
? with inductive load, max.
0.5 Hz
0.5 Hz
0.5 Hz
? on lamp load, max.
1 Hz
1 Hz
1 Hz
? mechanical, max.
10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.
8 A
4 A
— up to 60 °C, max.
4 A
2 A
8 A
— up to 70 °C, max.
1 A
vertical installation
— up to 40 °C, max.
4 A
2 A
8 A
Relay outputs
? Rated supply voltage of relay coil L+ (DC)
24 V
? Number of operating cycles, max.
100 000; 50000 (24 V DC, at 2 A); 700000 (120 V AC, at 2 A); 100000 (230 V AC, at 2 A)
Switching capacity of contacts
— with inductive load, max.
2 A; 2 A (230 V AC), 2 A (24 V DC)
— with resistive load, max.
2 A; 2 A (230 V AC), 2 A (24 V DC)
Cable length
? shielded, max.
1 000 m
1 000 m
1 000 m
? unshielded, max.
600 m
600 m
600 m
Interrupts/diagnostics/status information
Diagnostic functions
Yes; Parameterizable
Yes; Fuse blown or load voltage missing
No
Alarms
? Diagnostic alarm
Yes; Parameterizable
No
No
Potential separation
Potential separation digital outputs
? between the channels
Yes
Yes
? between the channels, in groups of
1
8
8
? between the channels and backplane bus
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Isolation
Isolation tested with
1500 V AC
4 000 V DC
1500 V AC
Standards, approvals, certificates
CE mark
Yes
Yes
Yes
UL approval
Yes; File E239877
Yes; File E239877
Yes; File E239877
FM approval
Yes; CofC 3028431
Yes; CofC 3028431
Yes; CofC 3028431
RCM (formerly C-TICK)
Yes
Yes
Yes
KC approval
Yes
Yes
Yes
EAC (formerly Gost-R)
Yes
Yes
Yes
Railway application
? EN 50121-4
No
? EN 50155
No
No
Yes; T1 Category 1 Class A/B horizontal mounting position
Ambient conditions
Ambient temperature during operation
? min.
0 °C; = Tmin
-40 °C; = Tmin
-40 °C
? max.
60 °C; = Tmax
70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
? min.
-40 °C
-40 °C
-40 °C
? max.
70 °C
70 °C
70 °C
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Connection method
required front connector
40-pin
20-pin
20-pin
Dimensions
Width
40 mm
40 mm
40 mm
Height
125 mm
125 mm
125 mm
Depth
120 mm
120 mm
120 mm
Weights
Weight, approx.
275 g
275 g
250 g
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ