SINAMICS DC MASTER for 12-pulse operation For 12-pulse operation, two SINAMICS DC MASTER converters are supplied with voltages displaced by 30 degrees. This configuration reduces the harmonics. Each SINAMICS DC MASTER conducts half of the total current. One of the SINAMICS DC MASTER units is operated with closed-loop speed control, and the second with closed-loop current control. A peer-to-peer connection is used to transfer the current setpoint from the first to the second SINAMICS DC MASTER. Smoothing reactors are required in the DC circuit for 12-pulse operation. Calculating the smoothing reactor
Calculating the required inductance 1. Inductance of the reactor at 0.2 ? IdN (LD1) 2. Inductance of the reactor for Idmax (LD2)
L = Inductance in H IdN half the rated DC current of the DC motor Idmax half the maximum current of the DC motor Vdi = 1.35 ? VN VN rated line supply voltage 12?pulse operation |