General information | |
Engineering with | |
| V5.5 + SP1 or higher or V5.2 + SP1 or higher + HSP 219 + Distributed Safety |
Supply voltage | |
Rated value (DC) | 24 V |
Power loss | |
Power loss, typ. | 4.2 W |
Memory | |
Work memory | |
| 192 kbyte |
| 64 kbyte |
Load memory | |
| 8 Mbyte |
CPU processing times | |
for bit operations, typ. | 0.06 µs |
for word operations, typ. | 0.12 µs |
for fixed point arithmetic, typ. | 0.16 µs |
for floating point arithmetic, typ. | 0.59 µs |
Counters, timers and their retentivity | |
S7 counter | |
| 256 |
IEC counter | |
| Yes |
S7 times | |
| 256 |
IEC timer | |
| Yes |
Data areas and their retentivity | |
Flag | |
| 256 byte |
Address area | |
I/O address area | |
| 2 048 byte |
| 2 048 byte |
Process image | |
| 2 048 byte |
| 2 048 byte |
Time of day | |
Clock | |
| Yes |
Operating hours counter | |
| 1 |
1. Interface | |
Interface type | Integrated RS 485 interface |
Physics | RS 485 |
Functionality | |
| Yes |
| No |
| Yes; active / passive |
| No |
2. Interface | |
Interface type | External interface via master module 6ES7138-4HA00-0AB0 |
Physics | RS 485 |
Functionality | |
| No |
| Yes |
| No |
DP master | |
| 32; Per station |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Communication functions | |
PG/OP communication | Yes |
Data record routing | Yes; With DP master module |
Global data communication | |
| Yes |
S7 basic communication | |
| Yes |
S7 communication | |
| Yes |
Number of connections | |
| 12 |
Programming | |
Programming language | |
| Yes |
| Yes |
| Yes |
| Yes; Optional |
| Yes; Optional |
| Yes; Optional |
| Yes; Optional |
Know-how protection | |
| Yes |
| Yes; With S7 block Privacy |
Dimensions | |
Width | 60 mm; DP master module: 35 mm |
Height | 119.5 mm |
Depth | 75 mm |
Weights | |
Weight, approx. | 200 g; DP master module: Approx. 100 g |