SIPLUS SM 336 F analog input module - Safety Integrated
Analog inputs for fail-safe SIPLUS S7 systems
Applicable in the ET 200M distributed I/O device with IM 153-2 HF as well as centrally with SIPLUS S7-31xF-2 DP
Properties of the SM 336; F-AI 6 x 0/4 ... 20 mA HART:
6 analog inputs with galvanic isolation between channels and backplane bus
Input ranges: 0 mA to 20 mA, 4 mA to 20 mA
Short-circuit proof power supply of 2 or 4-wire transmitter via the module
External encoder supply possible
Applicable in safety mode
HART communication
Firmware update using HW Config
Identification data
Temperature range -25 ... +70 °C; (+70 °C when ensuring a forced convection with a minimal air velocity of 0.3 m/s through the module). If a violation of the permissible, specified parameters is detected during maintenance or by automatic diagnostics, the modules must be proof-tested by the manufacturer. Without this measure the temperature range is -25…60°C
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.