Rating of three-phase motors at 50 Hz and and 400 V
Connection method
Type
Screw terminals
Spring-type terminals
kW
Power contactors for switching motors
AC operation
Basic unit
S00
3 ... 7.5
?
?
3RT201.?.A.0.
With permanently mounted auxiliary switch block (SUVA-certified safety contactor)
?
?
3RT201.?..P04?3MA0
Basic unit
S0
4 ... 18.5
?
?
3RT202.?.A.00
With removable auxiliary switch block
?
?
3RT202.?.A.04
With permanently mounted auxiliary switch block (SUVA-certified safety contactor)
?
?
3RT202.?.CL24?3MA0
Basic unit
S2
18.5 … 37
?
?
3RT203.?.A.00
With removable auxiliary switch block
?
--
3RT203.?1A.04
With permanently mounted auxiliary switch block
?
?
3RT203.?.CL24?3MA0
Basic unit
S3
37 ... 55
?
?
3RT204.?.A.00
With removable auxiliary switch block
?
--
3RT204.?1A.04
With permanently mounted auxiliary switch block
?
--
3RT204.?1CL24?3MA0
DC operation
Basic unit
S00
3 ... 7.5
?
?
3RT201.?..B4.
With integrated coil circuit (diode)
?
?
3RT201.?.FB4.
With permanently mounted auxiliary switch block (SUVA-certified safety contactor) and integrated coil circuit (diode)
?
?
3RT201.?..B44?3MA0
With voltage tap-off
?
?
3RT201.?.BB4.?0CC0
Basic unit
S0
4 ... 18.5
?
?
3RT202.?.B.40
With coil circuit plugged in on the front (diode assembly)
?
?
3RT202.?.FB40
With removable auxiliary switch block
?
?
3RT202.?.BB44
With permanently mounted auxiliary switch block (SUVA-certified safety contactor)
?
?
3RT202.?..B44?3MA0
With voltage tap-off
?
?
3RT202.?.BB40?0CC0
DC operation for direct control by PLC (coupling relays)
Basic unit with and without integrated coil circuit
S00
3 ... 5.5
?
?
3RT201.?..B4.
Basic unit with integrated coil circuit
S0
4 ... 15
?
?
3RT202.?.KB40
Basic unit with integrated coil circuit
S2
18.5 … 37
?
?
3RT203.?.KB40
Basic unit with integrated coil circuit
S3
37 and 45
?
?
3RT204.?.KB40
AC/DC operation (50/60 Hz AC and DC)
Basic unit with integrated coil circuit
S0
5.5 ... 18.5
?
?
3RT202.?.N.30
Basic unit with integrated coil circuit
S2
18.5 … 37
?
?
3RT203.?.N.30
With removable auxiliary switch block
?
--
3RT203.?1N.34
With permanently mounted auxiliary switch block
?
?
3RT203.?.NB34?3MA0
With voltage tap-off
?
?
3RT203.?.NB30?0CC0
Basic unit with integrated coil circuit
S3
37 ... 55
?
?
3RT204.?.N.30
With removable auxiliary switch block
?
--
3RT204.?1N.34
With permanently mounted auxiliary switch block
?
?
3RT204.?.NB34?3MA0
With voltage tap-off
?
?
3RT204.?.NB30?0CC0
Basic unit
S6 ... S12
55 ... 250
Conventional operating mechanisms
?1)
?
3RT10..?.A.36
Solid-state operating mechanism
With 24 V DC control signal input e.g. for control by PLC
?1)
?
3RT10..?.N.36
With 24 V DC control signal input · with indication of remaining lifetime (RLT), e.g. for control by PLC
?1)
--
3RT10..?.P.35
-- Version not possible
? Version possible
1) Screw terminal optionally with box terminals or with bar connections.
Contactors with screw terminals: 3RT2 (sizes S00 to S3) and 3RT1 (sizes S6 to S12)
3RT contactors, sizes S00 to S12
Our power range:
Contactors for switching motors:
Size S00: 3RT201 up to 7.5 kW
Size S0: 3RT202 up to 18.5 kW
Size S2: 3RT203 up to 37 kW
Size S3: 3RT204 up to 55 kW
Sizes S6 to S12: 3RT10 up to 250 kW
Vacuum contactors for switching motors: see "SIRIUS 3RT12 and 3TF6 Vacuum Contactors":
Sizes S10 and S12: 3RT12 up to 250 kW
Size 14: 3TF6 up to 450 kW
Standards
IEC 60947-1, EN 60947-1, IEC 60947-4-1, EN 60947-4-1, IEC 60947-5-1, EN 60947-5-1 (auxiliary switch)
3RT contactors
The 3RT2 contactors are climate-proof and are suitable and tested for use worldwide.
If the devices are used in ambient conditions which deviate from common industrial conditions (IEC 60721-3-3 "Stationary Use, Weather-Protected"), information must be obtained about possible restrictions with regard to the reliability and endurance of the device and possible protective measures. In this case contact our Technical Assistance, Tel.: +49 (911) 895-5900 E-mail: technical-assistance@siemens.com.
Auxiliary contact complement
Size S00: an auxiliary contact is integrated in the basic device.
Sizes S0 to S3: The basic units contain two integrated auxiliary contacts (1 NO + 1 NC). All basic units, with the exception of coupling relays S00 and S0, can be expanded using auxiliary switch blocks.
Sizes S6 to S12: These contactors are supplied with two laterally mounted auxiliary switch blocks. The fitting of auxiliary switches is possible on the front and on the side (the 3RT12 vacuum contactor is an exception: only lateral fitting of auxiliary switches is possible here).
For detailed information on the fitting of auxiliary switches, see the asset "Selection guide for mountable auxiliary switch blocks" under "Accessories and Spare Parts" > "for SIRIUS 3RT2 Contactors and SIRIUS 3RH2 Contactor Relays" > “Auxiliary switch blocks" > "Instantaneous".
Contact reliability
If voltages ? 110 V and currents ? 100 mA are to be switched, the auxiliary contacts of the 3RT contactors or 3RH contactor relays should be used as they guarantee a high level of contact reliability.
These auxiliary contacts are suitable for solid-state circuits with currents ? 1 mA at a voltage of ? 17 V and higher.
Connection method
Main circuit
Sizes S00 and S0: screw or spring-type terminal, spring-type terminal with convenient plug-in design for device connectors
Size S2: Screw terminals
Sizes S3 to S12: screw terminal with or without box terminal; with the box terminal removed: connection with bar or cable lugs on the device connection bar possible
Auxiliary circuit
Sizes S00 to S12: Screw or spring-type terminals
Electromagnetic compatibility (EMC)
The 3RT contactors fulfill the requirements for environment category A.
Note:
When the contactors are used in an environment with frequency converters, the information in the manuals must be observed, see topic "Technical specifications" > "More information".
Short-circuit protection
For short-circuit protection of the contactors without overload relay, see "Technical Specifications" of the relevant contactor.
Refer to the manuals for details of short-circuit protection of the contactors with overload relays; see above under "More information".
For the fuseless assembly of motor feeders consisting of a 3RV2 motor starter protector and a 3RT2 contactor, selection guides are available as described in "3RA2 Load Feeders"; see "Load Feeders and Motor Starters" > "for Use in the Control Cabinet".
Motor protection
3RT2 contactors
3RU2 thermal overload relays or 3RB3 electronic overload relays can be fitted to the 3RT2 contactors for protection against overload. For overload relays, see "Protection devices".
3RT1 contactors
3RB2 electronic overload relays can be fitted to the 3RT1 contactors for protection against overload. For overload relays, see "Protection devices".
Plant and application monitoring
3RR2 monitoring relays can be fitted to the 3RT2 contactors for monitoring and measuring in the application. See "Monitoring and Control Devices" > "Relays" > "SIRIUS 3RR21, 3RR22 Monitoring Relays for Mounting on 3RT2 Contactors".
Ratings of three-phase motors
The quoted rating (in kW) refers to the output power on the motor shaft (according to the nameplate).
The power rating specifications of the contactors in kW (in accordance with IEC 60947-4-1, Table G) are guide values for 4-pole standard motors at 50 Hz AC and specified voltage (e.g. 400 V AC). The actual starting and rated data of the motor to be switched must be considered when selecting the units.
Surge suppression
3RT contactors supplied without a coil circuit can be retrofitted with RC elements, varistors, diodes or diode assemblies (assembly of diode and Zener diode for short break times) for damping opening surges in the coil.
Size S00: the surge suppressors are plugged onto the front of the contactors here. Space is provided for them next to a snap-on auxiliary switch block.
Sizes S0 and S3: the surge suppressors can be plugged onto the front of the devices. In the case of size S3 contactors, surge suppressors can only be used as from product version E03.
Sizes S6 to S12: withdrawable coils with integrated coil switch (varistor)
Note:
The OFF-delay of the NO contact and the ON-delay of the NC contact are increased if the contactor coils are attenuated against voltage peaks (for details see the relevant manual > topic "Technical specifications" > "More information").
Contactors with voltage tap-off
Sizes S00 to S3
The S00 to S3 contactors with voltage tap-off are special versions for mounting the SIRIUS function modules for connection to the control system through IO-Link or AS-Interface. See "Accessories and Spare Parts" > "for SIRIUS 3RT2 Contactors and SIRIUS 3RH2 Contactor Relays" > "Modules for Contactor Adaptation".
Without a function module, the contactors can be used like the standard versions.
For more information on IO-Link and AS-Interface see "Industrial Communication".
Control supply voltage
Different versions of operating mechanisms are available depending on the contactor size:
AC or DC operation for sizes S00 to S3
AC/DC operating mechanism for sizes S0 to S12 that can operate on AC (50 to 60 Hz) or DC.
Operating mechanism types
Sizes S6 to S12
Two types of solenoid operation are available:
Conventional operating mechanisms
Solid-state operating mechanism
The operating mechanism for the contactors features solid-state control of the contactor coil. Overvoltage damping of the operating mechanism coil is already integrated in the electronics. The operating mechanisms are powered via a supply voltage with an operating range from 0.7 to 1.25 x Us, optionally also controlled depending on the chosen mode of operation. Alternatively, control is via the separate 24 V DC control signal input. Various rated voltage ranges for AC/DC control are available.
This version is additionally available with a 24 V DC PLC relay output and a remaining lifetime indicator (RLT).
Solenoid coils
Sizes S0 to S3: coil replacement is possible.
As from size S6: For simple coil replacement, e. g. if the application is replaced, the solenoid coil can be pulled out upwards after the release mechanism has been actuated and can be replaced by any other coil of the same size.
Article No. scheme
Product versions
Article number
SIRIUS power contactors
3RT2
?
?
?
–
?
?
?
?
?
–
?
?
?
?
Device type
e. g. 0 = 3-pole motor contactor
?
Size of the contactor
e. g. 4 = S3
?
Power dependent on size
e. g. 37 kW in the case of S3
?
Connection type
e. g. 1 = screw terminals (main and auxiliary circuits)
?
Operating range/solenoid coil circuit
e.g. A = AC standard/without coil circuit
?
Rated control supply voltage
e.g. P0 = 230 V AC, 50 Hz
?
?
Auxiliary switches
e. g. 0 = in the case of S3: 1 NO + 1 NC integrated
?
Special version
?
?
?
?
Example
3RT2
0
4
5
–
1
A
P
0
0
Note:
The Article No. scheme shows an overview of product versions for better understanding of the logic behind the article numbers.