Construction of optical PROFIBUS networks (line, star, ring) with glass, PCF and plastic fiber-optic cables
High availability can be achieved using a redundant power supply and redundant cable routing
Function monitoring by means of signaling contact
All PROFIBUS data transmission rates from 9.6 Kbit/s to 12 Mbit/s including 45.45 Kbit/s for PROFIBUS PA
Monitoring of the fiber-optic cable routes on LEDs for channel monitoring or using a voltmeter across measurement terminals
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were adopted from the respective standard products. SIPLUS extreme specific information was added.
SIPLUS PROFIBUS
OLM/P11
OLM/G11
OLM/G11-1300
Article No.
6AG1 503-2CA00-2AA0
6AG1 503-2CB00-2AA0
6AG1 503-2CC00-2AA0
Article No. based on
6GK1 503-2CA00
6GK1 503-2CB00
6GK1 503-2CC00
Ambient temperature range
-25 … +60 °C
-25 … +60 °C
-25 … +60 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical specifications
The technical data of the standard product applies except for the ambient conditions.
SIPLUS PROFIBUS
OLM/P12
OLM/G12
OLM/G12-1300
Article No.
6AG1 503-3CA00-2AA0
6AG1 503-3CB00-2AA0
6AG1 503-3CC00-4AA0
Article No. based on
6GK1 503-3CA00
6GK1 503-3CB00
6GK1 503-3CC00
Ambient temperature range
-25 … +60 °C
-25 … +60 °C
0 … +60 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical specifications
The technical data of the standard product applies except for the ambient conditions.
Ambient conditions
Relative humidity
100%, condensation/frost permitted. No commissioning in bedewed state.
Biologically active substances, compliance with EN 60721-3-3
Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!
Chemically active substances, compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation!
Mechanically active substances, compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!
Air pressure (depending on the highest positive temperature range specified)
1 080 ... 795 hPa (-1 000 ... +2 000 m) see ambient temperature range