Product characteristic | Chemical and process industry-oriented (Included in Quick Ship Program |
Nominal size | - PTFE: DN 15 … 300 (?" … 12")
|
- PFA: DN 15 … 150 (?" … 6")
|
Measuring principle | Electromagnetic induction |
Excitation frequency (Mains supply: 50 Hz/60 Hz) | - DN 15 … 65 (?" … 2?"): 12.5 Hz/15 Hz
|
- DN 80 … 150 (3" … 6"): 6.25 Hz/7.5 Hz
|
- DN 200 … 300 (8" … 12"): 3.125 Hz/3.75 Hz
|
Process connection | |
Flanges | EN 1092-1, raised face1) (EN 1092-1, DIN 2501 & BS 4504 have the same mating dimensions) |
- DN 15 … 50 (?" … 2"): PN 40 (580 psi)
|
- DN 65 … 300 (2?" … 12"): PN 16 (232 psi)
|
- DN 200 … 300 (8" … 12"): PN 10 (145 psi)
|
ANSI B16.5 (~BS 1560), raised face |
- ?" … 12": Class 150 (20 bar (290 psi))
|
Rated operation conditions | |
Ambient temperature (conditions also dependent on liner characteristiques) | |
| -40 … +100 °C (-40 … +212 °F) |
| -20 … +60 °C (-4 … +140 °F) |
| |
| -20 … +60 °C (-4 … +140 °F) |
| -20 … +60 °C (-4 … +140 °F) |
| -20 … +60 °C (-4 … +140 °F) |
Operating pressure [abs. bar] (maximum operating pressure decreases with increasing operating temperature and with stainless steel flanges) | |
- DN 15 … 300 (?" … 12"): 0.3 … 40 bar (4 … 580 psi)
|
|
- DN 15 … 150 (?" … 6"): Vacuum 0.02 … 50 bar (0.29 … 725 psi)
|
Enclosure rating | IP67 to EN 60529/NEMA 4X/6, 1 mH2O for 30 min |
Option: IP68 to EN 60529/NEMA 6P, 10 mH2O cont. (not for Ex) |
Pressure drop at 3 m/s | As straight pipe |
Test pressure | 1.5 x PN (where applicable) |
Mechanical load (Vibration) | - 18 … 1000 Hz random in x, y, z, directions for 2 hours according to EN 60068-2-36
|
|
- Sensor with compact MAG 5000/6000 mounted transmitter: 3.17 g RMS
|
- Sensor with compact MAG 6000 I/6000 I Ex mounted transmitter: 1.14 g RMS
|
Temperature of medium | - PTFE -20 … +130 °C (-4 … +266 °F)
|
- PFA -20 … +150 °C (-4 … +302 °F)
|
EMC | 2014/30/EU |
Design | |
Weight | See dimensional drawings |
Flange and housing material | Carbon steel ASTM A 105, with corrosion resistant coating (Corrosivity category C4M, according to ISO 12944-2) |
Electrode material | PTFE: Hastelloy C276/2.4819 |
PFA: Hastelloy C22/2.4602 |
Grounding electrode material | PTFE: No grounding electrodes |
PFA: Hastelloy |
Terminal box (remote version only) | - Standard fibre glass reinforced polyamide
|
- Option Stainless steel AISI 316/1.4436
|
- Ex sensor: Stainless steel AISI 316/1.4436
|
Cable entries | - Remote installation 2 x M20 or 2 x ?" NPT
|
|
- MAG 5000/MAG 6000: 4 x M20 or 4 x ?" NPT
|
- MAG 6000 I: 2 x M25 or 2 x ?" NPT (for supply/output)
|
- MAG 6000 I Ex de: 2 x M25 or 2 x ?" NPT (for supply/output)
|
Certificates and approvals | |
Calibration | |
- Standard production calibration
| Zero-point, 2 x 25 % and 2 x 90 % |
Hazardous areas | |
- Ex-sensor in compact or remote version with MAG 6000 I Ex
| - ATEX, FM, CSA, IECEx, EAC Ex, NEPSI
- Zone 1 Ex d e ia IIC T6 Gb
- XP IS Class I Div. 1 Groups A, B, C, D2)
- DIP Class II+III Div. 1 Groups E, F, G2)
|
- Standard sensor with/without MAG 5000/6000/6000 I
| - NI Class I Div. 2 Groups A, B, C, D
- NI Class I Zone 2 Groups IIC
|
Pressure equipment | PED, CRN |
Others | - EAC (Russia, Belarus, Kazakhstan)
- KCC (South Korea)
|