IE FC TP Cable 2 x 2 Order number
6XV1840-2AH10
6XV1841-2A
6XV1870-2B
6XV1841-2B
Product type designation
IE FC TP Standard Cable GP 2 x 2 (Type A)
IE FC TP Robust Standard Cable GP 2 x 2 (Type A)
IE FC TP Flexible Cable GP 2 x 2 (Type B)
IE FC TP Robust Flexible Cable GP 2 x 2 (Type B)
Product description
Standard bus cable (4-core), sold by the meter, unassembled
Standard bus cable (4-core), sold by the meter, unassembled
Flexible bus cable (4-core), sold by the meter, unassembled
Flexible bus cable (4-core), sold by the meter, unassembled
Suitability for use
Standard cable with rigid cores for fast installation
Standard cable with rigid cores for fast installation
For occasionally moved machine parts
For occasionally moved machine parts
Cable designation
2YY (ST) CY 2x2x0,64/1,5-100 GN SF/UTP
2YH (ST) C99Y 2x2x0,64/1,5-100 GN SF/UTP
2YY (ST) CY 2x2x0,75/1,5-100 LI GN SF/UTP
2YH (ST) C99Y 2x2x0,75/1,5-100 LI GN SF/UTP
Electrical data
Damping ratio per length
52 dB/km
65 dB/km
60 dB/km
65 dB/km
195 dB/km
220 dB/km
210 dB/km
220 dB/km
Impedance
100 ?
100 ?
100 ?
100 ?
Relative symmetrical tolerance
15 %
15 %
15 %
15 %
Near-end crosstalk per length
500 dB/km
500 dB/km
500 dB/km
500 dB/km
Transfer impedance per length at 10 MHz
10 m?/m
10 m?/m
20 m?/m
20 m?/m
Loop resistance per length maximum
115 m?/m
115 m?/m
120 m?/m
120 m?/m
Operating voltage
80 V
80 V
80 V
80 V
NVP value in percent
66 %
66 %
66 %
66 %
Mechanical data
Number of electrical cores
4
4
4
4
Design of the shield
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Type of electrical connection FastConnect
Yes
Yes
Yes
Yes
Core diameter
0.64 mm
0.64 mm
0.75 mm
0.75 mm
Outer diameter
0.64 mm
0.64 mm
0.75 mm
0.75 mm
1.5 mm
1.5 mm
1.5 mm
1.5 mm
3.9 mm
3.9 mm
3.9 mm
3.9 mm
6.5 mm
6.5 mm
6.5 mm
6.5 mm
Symmetrical tolerance of the outer diameter of cable sheath
0.2 mm
0.2 mm
0.2 mm
0.2 mm
Material
PE
PE
PE
PE
PVC
FRNC
PVC
FRNC
PVC
TPE (FR-TPE)
PVC
TPE (FR-TPE)
Color
white/yellow/blue/orange
white/yellow/blue/orange
white/yellow/blue/orange
white/yellow/blue/orange
green
green
green
green
Bending radius
19.5 mm
26 mm
32.5 mm
32.5 mm
49 mm
52 mm
52 mm
52 mm
Tensile load maximum
150 N
150 N
150 N
150 N
Weight per length
67 kg/km
59 kg/km
68 kg/km
68 kg/km
Permitted ambient conditions
Ambient temperature
-40 ... +75 °C
-40 ... +75 °C
-25 ... +75 °C
-40 ... +75 °C
-40 ... +75 °C
-40 ... +75 °C
-25 ... +75 °C
-40 ... +75 °C
-40 ... +75 °C
-40 ... +75 °C
-25 ... +75 °C
-40 ... +75 °C
-20 ... +60 °C
-20 ... +60 °C
-10 ... +60 °C
-20 ... +60 °C
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Burning behavior
flame resistant according to UL 1685 (CSA FT 4)
flame resistant according to IEC 60332-1-2
flame resistant according to UL 1685 (CSA FT 4)
flame resistant according to IEC 60332-1-2
Chemical resistance
oil resistant according to IEC 60811-2-1 (4 h / 70°C)
oil resistant according to DIN EN 50290-2-22 (VDE 0819), (7x24h/90°C), UL13 Sec.40 (96h/100°C)
oil resistant according to IEC 60811-404 (7x24h/90°C)
oil resistant according to DIN EN 50290-2-22 (VDE 0819), (7x24h/90°C), UL13 Sec.40 (96h/100°C)
Conditional resistance
Conditional resistance
Conditional resistance
Conditional resistance
conditional resistance
conditional resistance
conditional resistance
conditional resistance
Radiological resistance to UV radiation
resistant
resistant
resistant
resistant
Product properties, functions, components general
Product feature
No
No
No
No
Yes
Yes
Yes
Yes
Wire length for Industrial Ethernet
100 m
100 m
85 m
85 m
Standards, specifications, approvals
UL/ETL listing 300 V Rating
Yes; cULus / CMG / PLTC/ ITC(UL) / Sun Res
Yes; c(ETL)us, CM, PLTC, SUN RES
Yes; c(UL)us, CMG / PLTC / Sun Res / OIL RES
Yes; c(ETL)us, CM, PLTC, SUN RES
UL/ETL style 600 V Rating
Yes
No
No
No
Certificate of suitability
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Standard for structured cabling
Cat5e
Cat5e
Cat5e
Cat5e
Marine classification association
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Order number
6XV1870-2F
6XV1870-2D
6XV1840-3AH10
6XV1871-2S
Product type designation
IE TP Torsion Cable 2 x 2 (Type C)
IE FC TP Trailing Cable GP 2 x 2 (Type C)
IE FC TP Trailing Cable 2 x 2 (Type C)
IE FC TP Festoon Cable GP 2 x 2 (Type B)
Product description
Highly flexible bus cable (4-core), sold by the meter, unassembled
Highly flexible bus cable (4-core), sold by the meter, unassembled
Highly flexible bus cable (4-core), sold by the meter, unassembled
Flexible bus cable (4-core), sold by the meter, unassembled
Suitability for use
Continuous motion control when using robots
Continuous motion control in a cable carrier
Continuous motion control in a cable carrier
For continuous motion in a trailing cable, festoon mounting
Cable designation
02YS C11Y 1x4x0,75/1,5-100 LI VZN FRNC GN SF/UTP
2YY (ST) CY 2x2x0,75/1,5-100 LI GN SF/UTP
2YH (ST) C11Y 2x2x0,75/1,5-100 LI GN VZN FRNC SF/UTP
2YY (ST) CY 2x2x0,75/1,5 LI GN SF/UTP
Electrical data
Damping ratio per length
81 dB/km
63 dB/km
60 dB/km
63 dB/km
410 dB/km
213 dB/km
220 dB/km
213 dB/km
Impedance
100 ?
100 ?
100 ?
100 ?
Relative symmetrical tolerance
15 %
5 %
15 %
5 %
Near-end crosstalk per length
500 dB/km
500 dB/km
500 dB/km
500 dB/km
Transfer impedance per length at 10 MHz
100 m?/m
20 m?/m
10 m?/m
100 m?/m
Loop resistance per length maximum
120 m?/m
120 m?/m
120 m?/m
120 m?/m
Operating voltage
80 V
80 V
80 V
80 V
NVP value in percent
70 %
66 %
66 %
66 %
Mechanical data
Number of electrical cores
4
4
4
4
Design of the shield
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Type of electrical connection FastConnect
No
Yes
Yes
Yes
Core diameter
0.76 mm
0.75 mm
0.75 mm
0.75 mm
Outer diameter
0.76 mm
0.75 mm
0.75 mm
0.75 mm
1.5 mm
1.5 mm
1.5 mm
1.5 mm
3.9 mm
3.9 mm
3.9 mm
6.5 mm
6.5 mm
6.5 mm
6.5 mm
Symmetrical tolerance of the outer diameter of cable sheath
0.2 mm
0.2 mm
0.2 mm
0.2 mm
Material
PE
PE
PE
PE
PVC
FRNC
PVC
PUR (TPE-U)
PVC
PUR (TPE-U)
PVC
Color
white/yellow/blue/orange
white/yellow/blue/orange
white/yellow/blue/orange
white/yellow/blue/orange
green
green
green
green
Bending radius
32.5 mm
32.5 mm
19.5 mm
30 mm
65 mm
49 mm
49 mm
70 mm
100 mm
100 mm
70 mm
Number of bending cycles
Not suitable for garland usage
3 000 000; Drag chain suitable for 3 million bending cycles at a bending radius of 100 mm, a speed of 4 m/s and an acceleration of 4 m/s?
4 000 000; Drag chain suitable for 4 million bending cycles at a bending radius of 100 mm, a speed of 4 m/s and an acceleration of 4 m/s?
5 000 000; 5 million bending cycles at a bending radius of 70 mm and an acceleration of 4 m/s?
Number of torsion cycles with torsion by ± 180° on 1 m cable length
5 000 000
Tensile load maximum
130 N
150 N
150 N
150 N
Weight per length
54 kg/km
68 kg/km
63 kg/km
68 kg/km
Permitted ambient conditions
Ambient temperature
-40 ... +80 °C
-25 ... +75 °C
-40 ... +75 °C
-40 ... +75 °C
-40 ... +80 °C
-25 ... +75 °C
-50 ... +75 °C
-50 ... +75 °C
-40 ... +80 °C
-25 ... +75 °C
-50 ... +75 °C
-50 ... +75 °C
-20 ... +60 °C
-10 ... +60 °C
-20 ... +60 °C
-20 ... +60 °C
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Burning behavior
flame resistant according to IEC 60332-1-2
flame resistant according to UL 1685 (CSA FT 4)
flame resistant according to IEC 60332-1-2
flame resistant according to UL 1685 (CSA FT 4)
Chemical resistance
oil resistant according to IEC 60811-2-1 (7x24h/90°C)
oil resistant according to IEC 60811-404 (7x24h/90°C)
oil resistant according to IEC 60811-2-1 (7x24h/90°C)
conditional resistance
resistant
Conditional resistance
resistant
Conditional resistance
resistant
conditional resistance
resistant
conditional resistance
Radiological resistance to UV radiation
resistant
resistant
resistant
resistant
Product properties, functions, components general
Product feature
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Wire length for Industrial Ethernet
75 m
85 m
85 m
85 m
Standards, specifications, approvals
UL/ETL listing 300 V Rating
Yes; UL Style 21161
Yes; c(UL)us, CMG / PLTC / Sun Res / OIL RES
Yes; cULus / CMX
Yes; c(UL)us, CMG / PLTC / Sun Res / OIL RES
UL/ETL style 600 V Rating
No
Yes
No
Yes
Certificate of suitability
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Standard for structured cabling
Cat5e
Cat5e
Cat5e
Cat5e
Marine classification association
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Order number
6XV1871-2F
6XV1871-2L
6XV1881-2A
6XV1840-4AH10
Product type designation
IE FC TP FRNC Cable GP 2x2 (Type B)
IE FC TP Food Cable 2 x 2 (Type C)
IE FC TP Robust Food Cable GP 2X2 (Typ B)
IE FC TP Marine Cable 2 x 2 (Type B)
Product description
Flexible halogen-free bus cable acc. to IEC 60754-1/2 (4-core), sold by the meter, unassembled
Flexible bus cable (4-core), sold by the meter, unassembled
Robust, flexible bus cable (4-core), sold by the meter, unassembled
Halogen-free bus cable acc. to IEC 60754-1/2 (4-core), sold by the meter, unassembled
Suitability for use
For occasionally moved machine parts
Food and beverages industry
For marine and offshore use
Cable designation
L-9YH (ST) CH 2x2x0,34/1,5-100 GN VZN FRNC SF/UTP
2YH (ST) C2Y 2X2X0,75/1,5-100 LI SF/UTP
2YY(ST)CY6Y 2X2X0.75/1.55 LI VZN
L-9YH (ST) CH 2 x 2 x 0,34/1,5-100 GN VZN FRNC SF/UTP
Electrical data
Damping ratio per length
60 dB/km
63 dB/km
95 dB/km
60 dB/km
220 dB/km
213 dB/km
320 dB/km
220 dB/km
Impedance
100 ?
100 ?
100 ?
100 ?
Relative symmetrical tolerance
15 %
5 %
5 %
15 %
Near-end crosstalk per length
0.5 dB/m
0.5 dB/m
0.353 dB/m
0.5 dB/m
Transfer impedance per length at 10 MHz
10 m?/m
10 m?/m
80 m?/m
10 m?/m
Loop resistance per length maximum
120 m?/m
120 m?/m
120 m?/m
120 m?/m
Operating voltage
80 V
80 V
80 V
80 V
NVP value in percent
66 %
66 %
63 %
66 %
Mechanical data
Number of electrical cores
4
4
4
4
Design of the shield
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Type of electrical connection FastConnect
Yes
Yes
Yes
Yes
Core diameter
0.75 mm
0.75 mm
0.75 mm
0.75 mm
Outer diameter
0.75 mm
0.75 mm
0.75 mm
0.75 mm
1.5 mm
1.5 mm
1.56 mm
1.5 mm
3.9 mm
3.9 mm
4 mm
3.9 mm
6.5 mm
6.5 mm
6.5 mm
6.5 mm
Symmetrical tolerance of the outer diameter of cable sheath
0.2 mm
0.2 mm
0.2 mm
0.2 mm
Material
PP
PE
PE
PP
FRNC
FRNC
PVC
FRNC
FRNC
PE
PVC/FEP; FEP transparent
FRNC
Color
white/yellow/blue/orange
white/yellow/blue/orange
white/yellow/blue/orange
white/yellow/blue/orange
green
Black
green
green
Bending radius
39 mm
20 mm
26 mm
39 mm
97.5 mm
49 mm
52 mm
97.5 mm
100 mm
Number of bending cycles
500 000; Acceleration 4 m/s?
Number of torsion cycles with torsion by ± 180° on 1 m cable length
1 000 000
Tensile load maximum
150 N
150 N
150 N
150 N
Weight per length
68 kg/km
55 kg/km
72 kg/km
68 kg/km
Permitted ambient conditions
Ambient temperature
-25 ... +70 °C
-40 ... +75 °C
-40 ... +80 °C
-25 ... +70 °C
-40 ... +75 °C
-50 ... +75 °C
-40 ... +80 °C
-40 ... +85 °C
-40 ... +75 °C
-50 ... +75 °C
-40 ... +80 °C
-40 ... +85 °C
0 ... 50 °C
-20 ... +60 °C
-40 ... +80 °C
0 ... 50 °C
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Electrical properties measured at 20 °C, tests according to DIN VDE 0472
Ambient condition for operation
Temperature range for permanent installation -40 °C to 85 °C
Burning behavior
flame resistant according to IEC 60332-3-22 (Category A/F), IEC 61034
inflammable
flame resistant according to IEC 60332-1-2
flame resistant according to IEC 60332-3-22 (Category A/F), smoke density according to IEC 61034-1/2
Chemical resistance
oil resistant according to IEC 60811-2-1 (4 h / 70°C)
oil resistant according to IEC 60811-2-1 (4 h / 70°C)
oil resistant according to IEC 60811-404 (7x24 h / 90°C)
conditional resistance, IEC 60811-2-1 (4 hours / 70 °C)
Conditional resistance
Conditional resistance
Conditional resistance
Conditional resistance
conditional resistance
conditional resistance
resistant
conditional resistance
Radiological resistance to UV radiation
resistant
resistant
resistant
resistant
Product properties, functions, components general
Product feature
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Wire length for Industrial Ethernet
85 m
85 m
85 m
85 m
Standards, specifications, approvals
UL/ETL listing 300 V Rating
Yes; c(UL)us, CMG / PLTC / Sun Res / OIL RES
No
Yes; c(ETL)us, CMG, (ETL)us PLTC-ER, SUN RES, OIL RES 1
Yes; cULus / CMG / PLTC / Sun Res
UL/ETL style 600 V Rating
No
No
No
No
Certificate of suitability
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
EHEDG, Installation and layout of the cables must fulfil the requirements of EHEDG published in the Guidelines Doc. 13 'Hygienic Design of open equipment for processing food' and Doc. 44 'Hygienic Design Principles for food factories' to be accessible for cleaning. Also connections must be easily cleanable by using EHEDG certified cable glands or connectors.
Standard for structured cabling
Cat5e
Cat5e
Cat5e
Cat5e
Marine classification association
No
No
No
Yes
No
No
No
Yes
No
No
No
Yes
No
No
No
Yes
No
No
No
Yes
No
No
No
No
No
No
No
No
Order number
6XV1871-2G
6XV1871-2T
Product type designation
IE TP Ground Cable 2x2 (Type C)
IE TP Train Cable 2x2 (Type C, AWG22/7)
Product description
Standard bus cable (4-core), for laying underground, sold by the meter, unassembled
Flexible bus cable with tinned copper leads (4-core) for rail applications, sold by the meter, unassembled
Suitability for use
Standard cable with rigid cores for fast installation
For laying in rail vehicles and buses
Cable designation
2YY(ST)CY2Y2x2x0.64/1.50-100 SF/UTP
SF/UTP
Electrical data
Damping ratio per length
63 dB/km
53 dB/km
213 dB/km
188 dB/km
Impedance
100 ?
100 ?
Relative symmetrical tolerance
5 %
5 %
Near-end crosstalk per length
500 dB/km
500 dB/km
Transfer impedance per length at 10 MHz
10 m?/m
8 m?/m
Loop resistance per length maximum
124 m?/m
124 m?/m
Operating voltage
100 V
125 V
NVP value in percent
64 %
Mechanical data
Number of electrical cores
4
4
Design of the shield
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
Type of electrical connection FastConnect
Yes
No
Core diameter
0.64 mm
0.75 mm
Outer diameter
0.64 mm
0.75 mm
1.5 mm
1.5 mm
4 mm
9 mm
6.6 mm
Cable diameter >6.5 mm because of additional PE outer cover. Cable can only be connected to RJ45/M12 connector after outer cover is removed.
Symmetrical tolerance of the outer diameter of cable sheath
0.2 mm
0.2 mm
Material
PE
PE
PVC
PVC
Elastomer meshed electron beam
Color
white/yellow/blue/orange
white/yellow/blue/orange
Black
Black
Bending radius
80 mm
40 mm
80 mm
40 mm
Tensile load maximum
150 N
150 N
Weight per length
97 kg/km
71 kg/km
Permitted ambient conditions
Ambient temperature
-40 ... +70 °C
-40 ... +80 °C
-40 ... +70 °C
-40 ... +80 °C
-40 ... +70 °C
-40 ... +80 °C
-5 ... +50 °C
-20 ... +60 °C
Electrical properties measured at 20 °C, tests according to EN50288-2-1
For a short duration in case of short-circuit fault 160°C
Ambient condition for operation
Electrical characteristics measured at 20 ?C, tests according to EN50288-2-1
Burning behavior
inflammable
BS6853, DIN5510-2 Brandschutzstufe 1-4, prEN45545-2 Hazard Level HL1-HL3, EN50306-4, NF F 16-101, NFPA130
Chemical resistance
conditional resistance
EN 50306-4 (72h/100 °C, IRM 902, 168h/70 °C, IRM 903)
Conditional resistance
Conditional resistance
Resistant
conditional resistance
Radiological resistance to UV radiation
resistant
resistant
Product properties, functions, components general
Product feature
No
Yes
Yes
Yes
Wire length for Industrial Ethernet
100 m
100 m
Standards, specifications, approvals
UL/ETL listing 300 V Rating
No
No
UL/ETL style 600 V Rating
No
No
Certificate of suitability
Yes
Yes
Yes
Yes
Standard for structured cabling
Cat5e
Cat5
Marine classification association
No
No
No
No
No
No
No
No
No
No
No
No
No
No