Optimization run6RA70 converters are supplied with parameters set to the factory settings. Automatic optimization runs can be selected by means of special key numbers to support setting of the controllers. The following controller functions can be set in an automatic optimization run:
Furthermore, all parameters set automatically during optimization runs can be altered afterwards on the operator panel. Monitoring and diagnosisDisplay of operational data The operating status of the converter is displayed via parameter r000. Approximately 50 parameters are provided for displaying measured values. An additional 300 signals from the closed-loop control can be selected in the software (connectors) for output on the display unit. Examples of displayable measured values: Setpoints, actual values, status of binary inputs/outputs, line voltage, line frequency, firing angle, inputs/outputs of analog terminals, input/output of controllers, display of limitations. Trace function The trace function can be selected to store up to 8 measured quantities with 128 measuring points each. A measured quantity or the activation of a fault message can be parameterized as a trigger condition. It is possible to record the pre-event and post-event history by programming a trigger delay. The sampling time for the measured value memory can be parameterized to between 3 and 300 ms. Measured values can be output via the operator panels or serial interfaces. Fault messages A number is allocated to each fault message. The time at which the event occurred is also stored with the fault message. This allows the cause of the fault to be pinpointed promptly. The most recent eight fault messages are stored with fault number, fault value and hours count for diagnostic purposes. When a fault occurs
Automatic restart: The system can be restarted automatically within a parameterizable time period of 0 to 2s. If this time is set to zero, a fault message is activated immediately (on power failure) without a restart. Automatic restart can be parameterized in connection with the following fault messages: Phase failure (field or armature), undervoltage, overvoltage, failure of electronics power supply, undervoltage on parallel SIMOREG unit.
Fault messages can be deactivated individually. The default setting for some fault messages is “deactivated” so they need to be activated in the appropriate parameter. Alarms Special states that do not lead to drive shutdown are indicated by alarms. Alarms do not need to be acknowledged, but are automatically reset when the cause of the problem has been eliminated. When one or several alarms occur
Safety shutdown (E-STOP)The task of the E-STOP function is to open the relay contacts (terminals 109/110) for energizing the main contactor within about 15 ms, independently of semiconductor components and the functional status of the microprocessor board (basic electronics). If the basic electronics are operating correctly, the closed-loop control outputs an I = 0 command to de-energize the main contactor. When an E-STOP command is given, the drive coasts to a standstill. The E-STOP function can be triggered by one of the following methods:
When the E-STOP function is reset, the drive switches to the “Starting lockout” state. This status needs to be acknowledged through activation of the “Shutdown” function, e.g. by opening terminal 37. Note: The E-STOP function is not an EMERGENCY STOP function according to EN 60204-1. Serial interfacesThe following serial interfaces are available:
Physical characteristics of interfaces RS 232: ±12 V interface for point-to-point operation. RS 485: 5 V normal mode interface, noise-proof, for an additional bus connection with a maximum of 31 bus nodes. USS protocol Disclosed SIEMENS protocol, easy to program on external systems, e.g. on a PC, any master interfaces can be used. The drives operate as slaves on a master. The drives are selected via a slave number. The following data can be exchanged via the USS protocol: PKW data for writing and reading parameters. PZD data (process data) such as control words, setpoints, status words, actual values. Connector numbers are entered in parameters to select the transmit data (actual values), the receive data (setpoints) represent connector numbers that can be programmed to act at any intervention points. Peer-to-peer protocol The peer-to-peer protocol is used to link one converter to another. With this mode, data are exchanged between converters, e.g. to build a setpoint cascade, via a serial interface. Since a serial interface is employed as a four-wire line, it is possible to receive data from the upstream converter, condition them (e.g. through multiplicative weighting) and then send them to the downstream converter. Only one serial interface is used for the whole operation. The following data can be exchanged between converters:
Up to five data words are transmitted in each direction. Data are exchanged on the basis of connector numbers and intervention points. The serial interfaces can be operated simultaneously. For example, the first interface can be used as an automation link (USS protocol) for open-loop control, diagnostics and specification of the master setpoint. A second interface operates in conjunction with the peer-to-peer protocol to act as a setpoint cascade. Control terminal block
|