Product type designation | |
General information | |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V12 |
| V5.5 SP3 / - |
| V2.3 |
| V2.31 |
Supply voltage | |
Type of supply voltage | 24 V DC |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Output voltage | |
Type of output voltage | DC |
Encoder supply | |
Number of outputs | 2 |
short-circuit protection | Yes; Electronic (response threshold 0.7 A to 2.1 A) |
Output current | |
| 0.3 A |
24 V encoder supply | |
| Yes; min. L+ (-1.5 V) |
| Yes |
| 600 mA |
Digital inputs | |
Number of digital inputs | 2 |
m/p-reading | Yes; p-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input voltage | |
| DC |
| 24 V |
| -30 to +5V |
| +15 to +30V |
Input current | |
| 3.7 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| Yes |
for counter/technological functions | |
| No |
Cable length | |
| 1 000 m |
| 500 m |
Digital outputs | |
Number of digital outputs | 1 |
Digital outputs, configurable | Yes |
short-circuit protection | Yes |
Open-circuit detection | Yes |
Overload protection | Yes |
Limitation of inductive shutdown voltage to | max. 1.5 V |
Switching capacity of the outputs | |
| 8 A |
| 100 W |
Load resistance range | |
| 3 ? |
| 2 000 ? |
Output voltage | |
| 24 V; L+ (-0.5 V) |
Output current | |
| 8 A |
| 1.5 mA; PP-switching: max. 1.5 mA; PM-switching: max. 1 mA |
Switching frequency | |
| 10 Hz; Symmetrical |
| 0.1 Hz; according to IEC 947-5-1, DC-13, symmetrical |
| 4 Hz; Symmetrical |
Aggregate current of the outputs | |
| 8 A; Note derating data in the manual |
| 8 A; Note derating data in the manual |
Cable length | |
| 1 000 m |
| 500 m |
Interrupts/diagnostics/status information | |
Substitute values connectable | No |
Alarms | |
| Yes |
| No |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes; green PWR LED |
| Yes; Green LED |
| Yes; Red LED |
| Yes; green/red DIAG LED |
Potential separation | |
Potential separation channels | |
| Yes |
Isolation | |
Isolation checked with | 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety functions | Yes |
Highest safety class achievable in safety mode | |
| PLe |
| SIL 3 |
| < 2.00E-05 1/h |
| < 1.00E-09 1/h |
Ambient conditions | |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 20 mm |
Height | 72 mm |
Depth | 55 mm |
Weights | |
Weight, approx. | 70 g |