Order No. | 6EP1433-2CA00 |
Product | SITOP?PSU300P |
Power supply, type | 24?V/8?A |
Input | - |
Input | 3-phase AC |
Voltage range | 340 ... 550 V |
Supply voltage | |
| |
| - |
| - |
| |
| - |
| - |
| - |
| - |
| |
| - |
| - |
Note | 320?...?340 V for max. 1 min |
Input voltage | |
| |
| - |
| - |
| |
| - |
| - |
| |
| - |
| - |
Wide-range input | Yes |
Overvoltage strength | Implemented internally with varistors |
Mains buffering at Iout rated, min. | 15 ms |
Mains buffering | at Uin = 400 V |
Rated line frequency | |
| 50 Hz |
| 60 Hz |
Line frequency range | 45 ... 66 Hz |
Input current | |
- at rated value of the input voltage 120 V rated value
| - |
- at rated value of the input voltage 230 V rated value
| - |
- at rated value of the input voltage 24 V rated value
| - |
- at rated value of the input voltage 48 V rated value
| - |
- at rated value of the input voltage 110 V rated value
| - |
- at rated value of the input voltage?220 V rated value
| - |
- at rated value of the input voltage 400 V rated value
| 0.5 A |
- at rated value of the input voltage 420 V rated value
| - |
- at rated value of the input voltage 500 V rated value
| - |
Switch-on current limitation (+ 25°C), max. | 40 A |
Duration of the switch-on current limitation at 25°C | |
| - |
| - |
I?t, max. | 3.5 A?·s |
Built-in line-side fuse | Internal, 4 A |
Protection in the main supply conductor (IEC 898) | Required:?Circuit breaker 2.2 ... 3.2 A?3RV1021-1DA10 or?3RV1721-1DD10 (UL 489) |
Output | - |
Output | Controlled, isolated DC voltage |
Rated voltage Uout rated DC | 24 V |
Total tolerance, static? ± | 3% |
Static line compensation, approx. | 0.5% |
Static load compensation, approx. | 0.5% |
Residual ripple, peak-peak, max. | 200 mV |
Residual ripple, peak-peak, typ. | - |
Spikes,?peak-peak, max. (bandwidth approx. 20 MHz) | 250 mV |
Spikes, peak-peak, max. (bandwidth approx. 20 MHz) | - |
Adjustment range min. | - |
Adjustment range?max. | - |
Product function: output voltage is adjustable | No |
Adjustment of the output voltage | - |
Note | - |
Status indicator | Green LED for 24 V OK |
Signaling | max. 30 V, 10 mA; Power-Good (high level 1L+ for Uout in range 21.3 ... 29?V); overtemperature warning at least 30 s before?switch-off (high level 1L+ when exceeding the max. internal temperature) |
On/Off behavior | Overshoot of Uout < 2% |
ON delay, max. | 1.5 s |
Voltage rise, typ. | 40 ms |
Maximum voltage rise time of the output voltage | - |
Rated current Iout rated | 8 A |
Current range | 0 A |
Current range up to +55°C | 8 A |
Note | - |
Active power output, typical | 192 W |
Short-term overload current in the event of a short-circuit during power-up, typical | 50 A |
Duration of the?overload capability overcurrent at short-circuit during power-up | 100 ms |
Constant overload current in the event of a short-circuit during power-up, typical | - |
Short-term overload current in the event of a short-circuit during operation, typical | 50 A |
Duration of the overload capability overcurrent in the event of a short-circuit during operating phase | 100 ms |
Constant overload current in the event of a short-circuit during operation, typical | - |
Parallel switching for enhanced performance | No |
Note | - |
Number of devices that can be switched in parallel to increase performance, units | - |
Efficiency | - |
Efficiency at Uout rated, Iout rated, approx. | 88% |
Efficiency at Uout rated, Iout rated, approx. | 25 W |
Closed-loop control | - |
Dyn. line compensation (Uin rated ±15%), max. | 0,5 % |
Dyn. load compensation (Iout:?50/100/50%), Uout?± typ. | 1% |
Load-step settling time 50 to 100%, typ. | - |
Load-step settling time 100 to 50%, typ. | - |
Settling time, maximum | 2 ms |
Protection and monitoring | - |
Output overvoltage protection | <?33?V |
Current limitation, minimum | - |
Current limitation, maximum | - |
Current limitation, typ. | 9.4 A |
Property of the output, short-circuit-proof | Yes |
Short-circuit protection | Electronic shutdown, automatic restart |
Sustained short-circuit current rms value | |
| 10 A |
| - |
Note | - |
Overload/short-circuit indicator | - |
Safety | - |
Primary/secondary isolation | Yes |
Electrical isolation | Safety extra low output voltage Uout according to EN 60950-1 and EN 50178 |
Safety class | Class I |
Leakage current | |
| 3.5 mA |
| 0.4 mA |
CE mark | Yes |
UL/CSA approval | No |
UL/cUL (CSA) approval | Prepared |
Explosion protection | - |
FM approval | No |
FM approval | - |
CB approval | Yes |
Marine approval | - |
Degree of protection (EN 60529) | IP67, enclosure type 4?indoor |
EMC | - |
Emitted interference | EN 55022 Class A |
Supply harmonics limitation | - |
Noise immunity | EN 61000-6-2 |
Operating data | - |
Ambient temperature | |
| -25 ... +55°C |
Note | with natural convection |
Ambient temperature | |
| -40 ... +70°C |
Ambient temperature | |
| -40 ... +70°C |
Humidity class to EN 60721 | Climate class 3K3, no condensation |
Mechanics | - |
Connection system | Screw connection |
Connections | |
| L1,?L2,?L3,?PE:?Plug connector HAN Q4/2 |
| L+,?M:?1 x?2.5 mm? each (2-pole cable for +/- with open, labeled ends, 2 x 2.5 mm?) |
| Alarm signals:?M12 plug-in connector, 5-pin |
Width of enclosure | 310 mm |
Height of enclosure | 135 mm |
Depth of enclosure | 90 mm |
Width/mounting dimensions | - |
Mounting height | - |
Weight, approx. | 2.8 kg |
Product property of the enclosure:?side-by-side enclosure | No |
Type of mounting | |
| Yes |
| No |
| No |
Mounting | can be mounted on ET200pro mounting rail |
Electrical accessories | Power connector (3RK1911-2BE50 (2.5 mm?)) |
Mechanical accessories | - |
EAN code | 4?042948?510834 |