Input | | |
Input | 1-phase AC or DC | 1-phase AC or DC |
Rated voltage value Vin rated | 100 ... 230 V | 100 ... 230 V |
Voltage range AC | 85 ... 264 V | 85 ... 264 V |
Input voltage | | |
| 110 ... 300 V | 110 ... 300 V |
Wide-range input | Yes | Yes |
Overvoltage resistance | 2.3 ? Vin rated, 1.3 ms | 2.3 ? Vin rated, 1.3 ms |
Mains buffering at Iout rated, min. | 20 ms; at Vin = 230 V | 20 ms; at Vin = 230 V |
Rated line frequency | 50 ... 60 Hz | 50 ... 60 Hz |
Rated line range | 47 ... 63 Hz | 47 ... 63 Hz |
Input current | | |
| 0.63 A | 1.6 A |
| 0.31 A | 0.8 A |
Switch-on current limiting (+25 °C), max. | 33 A | 31 A |
I?t, max. | 1.2 A?·s | 3 A?·s |
Built-in incoming fuse | internal | internal |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 16 A characteristic B or from 10 A characteristic C | Recommended miniature circuit breaker: from 16 A characteristic B or from 10 A characteristic C |
Output | | |
Output | Controlled, isolated DC voltage | Controlled, isolated DC voltage |
Rated voltage Vout DC | 12 V | 12 V |
Total tolerance, static ± | 3 % | 3 % |
Residual ripple peak-peak, max. | 200 mV | 200 mV |
Residual ripple peak-peak, typ. | 40 mV | 80 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 300 mV | 300 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) | 50 mV | 80 mV |
Adjustment range | 10.5 ... 12.9 V | 10.5 ... 12.9 V |
Product function Output voltage adjustable | Yes | Yes |
Output voltage setting | via potentiometer | via potentiometer |
Status display | Green LED for output voltage OK | Green LED for output voltage OK |
On/off behavior | Overshoot of Vout approx. 5 % | Overshoot of Vout approx. 1 % |
Startup delay, max. | 0.6 s | 1 s |
Voltage rise, typ. | 10 ms | 500 ms |
Rated current value Iout rated | 2 A | 6.5 A |
Current range | 0 ... 2 A | 0 ... 6.5 A |
| +55 ... +70 °C: Derating 3%/K | +50 ... +70 °C: Derating 3.5%/K |
Active power supplied typical | 24 W | 78 W |
Parallel switching for enhanced performance | Yes; Start-up with single nominal load only | Yes; Start-up with single nominal load only |
Numbers of parallel switchable units for enhanced performance | 2 | 2 |
Efficiency | | |
Efficiency at Vout rated, Iout rated, approx. | 82 % | 86 % |
Power loss at Vout rated, Iout rated, approx. | 5.8 W | 12.5 W |
Active power loss during no-load operation maximum | 0.75 W | 0.75 W |
Closed-loop control | | |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.1 % | 0.1 % |
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ. | 3 % | 3 % |
Load step setting time 10 to 90%, typ. | 4 ms | 3 ms |
Load step setting time 90 to 10%, typ. | 3 ms | 3 ms |
Protection and monitoring | | |
Output overvoltage protection | Yes, according to EN 60950-1 | Yes, according to EN 60950-1 |
Current limitation, typ. | 2.4 A | 7.2 A |
Property of the output Short-circuit proof | Yes | Yes |
Short-circuit protection | Electronic shutdown, automatic restart | Electronic shutdown, automatic restart |
Overload/short-circuit indicator | - | - |
Safety | | |
Primary/secondary isolation | Yes | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class | Class I | Class I |
Leakage current | | |
| 3.5 mA | 3.5 mA |
| 0.4 mA | 0.4 mA |
CE mark | Yes | Yes |
UL/CSA approval | Yes | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) |
Explosion protection | ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 | ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 |
Certificate of suitability IECEx | No | No |
Certificate of suitability NEC Class 2 | No | No |
FM approval | - | - |
CB approval | Yes | Yes |
Marine approval | GL, ABS | GL, ABS |
Degree of protection (EN 60529) | IP20 | IP20 |
EMC | | |
Emitted interference | EN 55022 Class B | EN 55022 Class B |
Supply harmonics limitation | not applicable | EN 61000-3-2 |
Noise immunity | EN 61000-6-2 | EN 61000-6-2 |
Operating data | | |
Ambient temperature | | |
| -20 ... +70 °C | -20 ... +70 °C |
| with natural convection | with natural convection |
| -40 ... +85 °C | -40 ... +85 °C |
| -40 ... +85 °C | -40 ... +85 °C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation | Climate class 3K3, no condensation |
Mechanics | | |
Connection technology | screw-type terminals | screw-type terminals |
Connections | | |
| L, N, PE: Removable screw terminal, each for 1 x 0.5 ... 2.5 mm? | L, N, PE: Removable screw terminal, each for 1 x 0.5 ... 2.5 mm? |
| +: 1 screw terminal for 0.5 ... 2.5 mm?; -: 2 screw terminals for 0.5 ... 2.5 mm? | +: 1 screw terminal for 0.5 ... 2.5 mm?; -: 2 screw terminals for 0.5 ... 2.5 mm? |
| - | - |
Width of the enclosure | 30 mm | 52.5 mm |
Height of the enclosure | 80 mm | 80 mm |
Depth of the enclosure | 100 mm | 100 mm |
Weight, approx. | 0.12 kg | 0.32 kg |
Product property of the enclosure housing for side-by-side mounting | Yes | Yes |
Installation | Snaps onto DIN rail EN 60715 35x7.5/15 | Snaps onto DIN rail EN 60715 35x7.5/15 |
Electrical accessories | Removable spring-type terminal 6EP1971-5BA00 | Removable spring-type terminal 6EP1971-5BA00 |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |