Input | |
Input | 1-phase AC |
Supply voltage | |
| 120 V |
| 230 V |
| Automatic range selection |
Input voltage | |
| 85 ... 132 V |
| 176 ... 264 V |
Wide-range input | No |
Overvoltage resistance | 2.3 ? Vin rated, 1.3 ms |
Mains buffering at Iout rated, min. | 20 ms; at Vin = 93/187 V |
Rated line frequency | 50 ... 60 Hz |
Rated line range | 47 ... 63 Hz |
Input current | |
| 1.2 A |
| 0.67 A |
Switch-on current limiting (+25 °C), max. | 13 A |
Duration of inrush current limiting at 25 °C | |
| 3 ms |
I?t, max. | 0.5 A?·s |
Built-in incoming fuse | T 3,15 A/250 V (not accessible) |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C |
Output | |
Output | Controlled, isolated DC voltage |
Rated voltage Vout DC | 24 V |
Total tolerance, static ± | 3 % |
Static mains compensation, approx. | 0.1 % |
Static load balancing, approx. | 0.2 % |
Residual ripple peak-peak, max. | 150 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 240 mV |
Product function Output voltage adjustable | No |
Output voltage setting | - |
Status display | Green LED for 24 V OK |
On/off behavior | No overshoot of Vout (soft start) |
Startup delay, max. | 6 s; 2 s at 230 V, 6 s at 120 V |
Voltage rise, typ. | 10 ms |
Rated current value Iout rated | 2.5 A |
Current range | 0 ... 2.5 A |
Active power supplied typical | 60 W |
Short-term overload current | |
| 6 A |
| 6 A |
Duration of overloading capability for excess current | |
| 100 ms |
| 100 ms |
Parallel switching for enhanced performance | Yes |
Numbers of parallel switchable units for enhanced performance | 2 |
Efficiency | |
Efficiency at Vout rated, Iout rated, approx. | 83 % |
Power loss at Vout rated, Iout rated, approx. | 12 W |
Closed-loop control | |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.3 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 3 % |
Load step setting time 50 to 100%, typ. | 5 ms |
Load step setting time 100 to 50%, typ. | 5 ms |
Setting time maximum | 5 ms |
Protection and monitoring | |
Output overvoltage protection | < 33 V |
Current limitation, typ. | 2.65 A |
Property of the output Short-circuit proof | Yes |
Short-circuit protection | Constant current characteristic |
Enduring short circuit current RMS value | |
| 2.7 A |
Overload/short-circuit indicator | - |
Safety | |
Primary/secondary isolation | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class | Class I |
Leakage current | |
| 3.5 mA |
CE mark | Yes |
UL/CSA approval | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950-1, CSA C22.2 No. 60950-1) File E151273 |
Explosion protection | ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 |
Certificate of suitability IECEx | No |
Certificate of suitability NEC Class 2 | No |
FM approval | Class I, Div. 2, Group ABCD, T4 |
CB approval | Yes |
Marine approval | GL, ABS, BV, DNV, LRS, NK |
Degree of protection (EN 60529) | IP20 |
EMC | |
Emitted interference | EN 55022 Class B |
Supply harmonics limitation | not applicable |
Noise immunity | EN 61000-6-2 |
Operating data | |
Ambient temperature | |
| 0 ... 60 °C |
| with natural convection |
| -40 ... +85 °C |
| -40 ... +85 °C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation |
Mechanics | |
Connection technology | screw-type terminals |
Connections | |
| L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm? |
| L+, M: 2 screw terminals each for 0.5 ... 2.5 mm? |
| - |
Width of the enclosure | 70 mm |
Height of the enclosure | 100 mm |
Depth of the enclosure | 75 mm |
Weight, approx. | 0.3 kg |
Product property of the enclosure housing for side-by-side mounting | Yes |
Installation | Snaps onto DIN rail EN 60715 35x7.5/15, wall mounting |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |