Station controller for SIMATIC PCS 7 PowerControl- IEC 61850 MMS client protocol with support for up to 64 server connections
- IEC 61850 MMS client functionality:
- Reading/writing of tags
- Select/operate
- Buffered reporting
- IEC 61850 MMS server protocol with support for up to 5 client connections
- Importing of ICD and SCD files of the protective equipment
- Original time stamp from the protective equipment
- Update cycle of < 500 ms is possible (depends on the CPU cycle time, data volume)
- Configuration tool and SC_DRV library in the product package
- IEC 60870?5 104 communication possible (upon request using address under "More information")
|
|