Article?No. | 6EP1334-3BA00 | 6EP1334-3BA10 |
Technical?specifications | | |
Product | SITOP?modular | SITOP?modular |
Power?supply,?type | 24?V/10?A | 24?V/10?A |
Input | | |
Input | 1-phase?and?2-phase?AC | 1-phase?and?2-phase?AC |
Rated?voltage?value?Vin?rated?min. | | |
Supply?voltage | | |
- 1?with?AC?minimum?rated?value
| 120 V | 120 V |
- 2?with?AC?minimum?rated?value
| 230 V | 230 V |
Rated?voltage?value?Vin?rated?max. | | |
Supply?voltage | | |
- 1?with?AC?maximum?rated?value
| 230 V | 230 V |
- 2?at?AC?maximum?nominal?value
| 500 V | 500 V |
| | |
| | |
| | |
| Set?by?means?of?selector?switch?on?the?device | Set?by?means?of?selector?switch?on?the?device |
Voltage?range | | |
Input?voltage | | |
| | |
| 85 … 264 V | 85 … 264 V |
| | |
| 176 … 550 V | 176 … 550 V |
| | |
Overvoltage?resistance | 1300?Vpeak,?1.3?ms | 1300?Vpeak,?1.3?ms |
Mains?buffering?at?Iout?rated,?min. | 25 ms | 25 ms |
Mains?buffering | at?Vin?=?120/230?V,?typ.?150?ms?at?Vin?=?400?V | at?Vin?=?120/230?V,?typ.?150?ms?at?Vin?=?400?V |
Rated?line?frequency | | |
| 50 Hz | 50 Hz |
| 60 Hz | 60 Hz |
Rated?line?range | 47 … 63 Hz | 47 … 63 Hz |
Input?current | | |
- at?nominal?level?of?the?input?voltage?120?V?nominal?value
| 4.4 A | 4.4 A |
- at?nominal?level?of?the?input?voltage?230?V?nominal?value
| 2.4 A | 2.4 A |
- at?nominal?level?of?the?input?voltage?400?V?nominal?value
| | |
- at?nominal?level?of?the?input?voltage?500?V?nominal?value
| 1.1 A | 1.1 A |
- at?DC?at?nominal?level?of?the?input?voltage?600?V?nominal?value
| | |
Switch-on?current?limiting?(+25?°C),?max. | 35 A | 35 A |
I?t,?max. | 4 A?·s | 4 A?·s |
Built-in?incoming?fuse | T?6.3?A?(not?accessible) | T?6.3?A?(not?accessible) |
Protection?in?the?mains?power?input?(IEC?898) | Recommended?miniature?circuit?breaker?at?1-phase?operation:?from?6?A?(10?A)?characteristic?C?(B);?required?at?2-phase?operation:?circuit?breaker?2-pole?connected?or?circuit?breaker?3RV2011-1EA10?(setting?3.8?A)?or?3RV2711-1ED10?(UL?489)?at?230?V;?3RV2011-1DA10?(setting?3?A)?or?3RV2711-1DD10?(UL?489)?at?400/500?V | Recommended?miniature?circuit?breaker?at?1-phase?operation:?from?6?A?(10?A)?characteristic?C?(B);?required?at?2-phase?operation:?circuit?breaker?2-pole?connected?or?circuit?breaker?3RV2011-1EA10?(setting?3.8?A)?or?3RV2711-1ED10?(UL?489)?at?230?V;?3RV2011-1DA10?(setting?3?A)?or?3RV2711-1DD10?(UL?489)?at?400/500?V |
Output | | |
Output | Controlled,?isolated?DC?voltage | Controlled,?isolated?DC?voltage |
Rated?voltage?Vout?DC | 24 V | 24 V |
Total?tolerance,?static?± | 3 % | 3 % |
Static?mains?compensation,?approx. | 0.1 % | 0.1 % |
Static?load?balancing,?approx. | 0.1 % | 0.1 % |
Residual?ripple?peak-peak,?max. | 50 mV | 50 mV |
Residual?ripple?peak-peak,?typ. | | |
Spikes?peak-peak,?max.?(bandwidth:?20?MHz) | 200 mV | 200 mV |
Spikes?peak-peak,?typ.?(bandwidth:?20?MHz) | | |
Adjustment?range | 24 … 28.8 V | 24 … 28.8 V |
Product?feature?output?voltage?adjustable | Yes | Yes |
Output?voltage?setting | via?potentiometer | via?potentiometer |
Note | | |
Status?display | Green?LED?for?24?V?OK | Green?LED?for?24?V?OK |
Signaling | via?signaling?module?(6EP1961-3BA10) | Relay?contact?(NO?contact,?rating?60?V?DC/?0.3?A)?for?"24?V?OK" |
On/off?behavior | Overshoot?of?Vout?approx.?3?% | Overshoot?of?Vout?approx.?3?% |
Startup?delay,?max. | 1 s | 1 s |
Note | | |
Voltage?rise,?typ. | 50 ms | 50 ms |
Voltage?increase?time?of?the?output?voltage?maximum | | |
Rated?current?value?Iout?rated | 10 A | 10 A |
Current?range | 0 … 10 A | 0 … 10 A |
Note | +60?...?+70?°C:?Derating?2%/K?(at?120?V,?230?V)?or?3.5%/K?(at?400?V) | +60?...?+70?°C:?Derating?2%/K?(at?120?V,?230?V)?or?3.5%/K?(at?400?V) |
delivered?active?power?typ. | 240 W | 240 W |
short-term?overload?current?at?short-circuit?during?run-up?typical | | |
Duration?of?overloading?ability?for?excess?current?on?short-circuiting?during?the?start-up | | |
Constant?overload?current?in?the?event?of?a?short?circuit?during?startup?/typical | 12 A | 12 A |
short-term?overload?current?at?short-circuit?during?operation?typical | 30 A | 30 A |
Duration?of?overloading?ability?for?excess?current?on?short-circuiting?during?the?operational?phase | 25 ms | 25 ms |
constant?overload?current?at?short-circuit?during?operation?typical | | |
Parallel?switching?for?enhanced?performance | Yes | Yes |
Note | switchable?characteristic | switchable?characteristic |
Numbers?of?parallel?switchable?units?for?enhanced?performance | 2 | 2 |
Efficiency | | |
Efficiency?at?Vout?rated,?Iout?rated,?approx. | 87 % | 91 % |
Power?loss?at?Vout?rated,?Iout?rated,?approx. | 36 W | 24 W |
Closed-loop?control | | |
Dynamic?mains?compensation?(Vin?rated?±15?%),?max. | 0.1 % | 0.1 % |
Dynamic?load?smoothing?(Iout:?50/100/50?%),?Uout?±?typ. | 3 % | 3 % |
Load?step?setting?time?50?to?100%,?typ. | 2 ms | 2 ms |
Load?step?setting?time?100?to?50%,?typ. | 2 ms | 2 ms |
Setting?time?maximum | 5 ms | 5 ms |
Protection?and?monitoring | | |
?Output?overvoltage?protection | <?35?V | <?35?V |
Current?limitation,?typ. | 12 A | 12 A |
Characteristic?feature?of?the?output?short-circuit?protected | Yes | Yes |
Short-circuit?protection | Alternatively,?constant?current?characteristic?approx.?12?A?or?latching?shutdown | Alternatively,?constant?current?characteristic?approx.?12?A?or?latching?shutdown |
Enduring?short?circuit?current?Effective?level?typical | 12 A | 12 A |
Note | | |
Overload/short-circuit?indicator | LED?yellow?for?"overload",?LED?red?for?"latching?shutdown" | LED?yellow?for?"overload",?LED?red?for?"latching?shutdown" |
Safety | | |
Primary/secondary?isolation | Yes | Yes |
Potential?separation | Safety?extra-low?output?voltage?Uout?acc.?to?EN?60950-1?and?EN?50178 | Safety?extra-low?output?voltage?Uout?acc.?to?EN?60950-1?and?EN?50178 |
Protection?class | Class?I | Class?I |
stray?current | | |
| 3.5 mA | 3.5 mA |
| 0.32 mA | 0.32 mA |
CE?mark | Yes | Yes |
UL/CSA?approval | Yes | Yes |
UL/cUL?(CSA)?approval | cULus-Listed?(UL?508,?CSA?C22.2?No.?107.1),?File?E197259 | cULus-Listed?(UL?508,?CSA?C22.2?No.?107.1),?File?E197259 |
Explosion?protection | ATEX?(EX)?II?3G?Ex?nA?nC?IIC?T3?Gc;?cCSAus?(CSA?C22.2?No.?213,?ANSI/ISA-12.12.01)?Class?I,?Div.?2,?Group?ABCD,?T3 | ATEX?(EX)?II?3G?Ex?nA?nC?IIC?T3?Gc;?cCSAus?(CSA?C22.2?No.?213,?ANSI/ISA-12.12.01)?Class?I,?Div.?2,?Group?ABCD,?T3 |
FM?approval | No | No |
FM?approval | - | |
CB?approval | No | Yes |
Marine?approval | GL,?ABS | GL,?ABS |
Degree?of?protection?(EN?60529) | IP20 | IP20 |
EMC | | |
Emitted?interference | EN?55022?Class?B | EN?55022?Class?B |
Supply?harmonics?limitation | EN?61000-3-2 | EN?61000-3-2 |
Noise?immunity | EN?61000-6-2 | EN?61000-6-2 |
Operating?data | | |
Ambient?temperature | | |
| -25 … +70 °C | -25 … +70 °C |
| with?natural?convection | with?natural?convection |
Ambient?temperature | | |
| -40 … +85 °C | -40 … +85 °C |
Ambient?temperature | | |
| -40 … +85 °C | -40 … +85 °C |
Humidity?class?according?to?EN?60721 | Climate?class?3K3,?no?condensation | Climate?class?3K3,?no?condensation |
Mechanics | | |
Connection?technology | screw-type?terminals | screw-type?terminals |
Connections | | |
| L,?N,?PE:?1?screw?terminal?each?for?0.2?...?2.5?mm??single-core/finely?stranded | L,?N,?PE:?1?screw?terminal?each?for?0.2?...?2.5?mm??single-core/finely?stranded |
| +,?-:?2?screw?terminals?each?for?0.2?...?2.5?mm? | +,?-:?2?screw?terminals?each?for?0.2?...?2.5?mm? |
| - | 13,?14?(alarm?signal):?1?screw?terminal?each?for?0.14?...?1.5?mm? |
Width?of?the?housing | 90 mm | 70 mm |
Height?of?the?housing | 125 mm | 125 mm |
Depth?of?the?housing | 125 mm | 121 mm |
Installation?width | 90 mm | 70 mm |
Installation?height | 225 mm | 225 mm |
Weight,?approx. | 1.4 kg | 0.8 kg |
Product?feature?of?the?housing?housing?for?side-by-side?mounting | Yes | Yes |
Type?of?mounting | | |
| No | No |
| Yes | Yes |
| No | No |
Installation | Snaps?onto?DIN?rail?EN?60715?35x7.5/15 | Snaps?onto?DIN?rail?EN?60715?35x7.5/15 |
Electrical?accessories | Buffer?module,?signaling?module | Buffer?module |
Mechanical?accessories | | |