Input | | | |
Input | DC voltage | DC voltage | DC voltage |
Supply voltage | | | |
| 24 ... 24 V | 24 ... 24 V | 24 ... 24 V |
Input voltage | | | |
| 19 ... 29 V | 19 ... 29 V | 24 ... 28.8 V |
Output | | | |
Output | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage |
Rated voltage Vout DC | 24 V | 24 V | 24 V |
Output voltage | Vin - approx. 0.5 V | Vin - approx. 0.5 V | Vin - approx. 0.5 V |
Product function Output voltage adjustable | No | No | No |
Status display | Green LED for "both input voltages > switching threshold"; red LED for "at least one input voltage < switching threshold" or "output switched off" | Green LED for "both Input voltages > switching threshold"; red LED: for "at least one input voltage < switching threshold" | Green LED for "both Input voltages > switching threshold"; red LED: for "at least one input voltage < switching threshold" |
Signaling | Isolated relay contact (contact rating 6 A/42 V AC, 30 V DC, but max. 100 VA): Contact closed if one or both input voltages < switching threshold or output is switched off. Setting range of switching threshold 20 V ±0.5 V to 25 V ±0.5 V | Isolated relay contact (contact rating 6 A/42 V AC, 30 V DC): Contact closed if both input voltages > switching threshold, setting range of switching threshold 20 V ± 0.5V to 25 V ± 0.5V | Isolated relay contact (changeover contacts, rating 8 A/240 V AC, 24 V DC): Signals OK if both input voltages > switching threshold, setting range of threshold 20 ... 25 V |
Rated current value Iout rated | 3.8 A | 10 A | 40 A |
Current range | 4.6 A | 10 A | 40 A |
| Maximum aggregate current in the event of an error according to NEC class 2 limit 8 A | max. aggregate current 10 A | max. aggregate current 40 A |
Efficiency | | | |
Efficiency at Vout rated, Iout rated, approx. | 94.8 % | 97.1 % | |
Power loss at Vout rated, Iout rated, approx. | 5 W | 3.6 W | |
Active power loss during no-load operation maximum | 2 W | 1 W | |
Safety | | | |
Galvanic isolation | yes, SELV acc. to EN 60950-1 (relay contact) | yes, SELV acc. to EN 60950-1 (relay contact) | yes, SELV acc. to EN 60950-1 (relay contact) |
Protection class | Class III | Class III | Class I |
CE mark | Yes | Yes | Yes |
UL/CSA approval | Yes | Yes | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; UL-Recognized (UL 60950-1, NEC class 2), File E151273 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
Explosion protection | - | - | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nAC IIC T4; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4 |
Certificate of suitability IECEx | No | No | No |
Certificate of suitability NEC Class 2 | Yes | No | No |
FM approval | - | - | - |
CB approval | No | No | No |
Approvals | No | No | No |
Marine approval | - | - | GL, ABS |
Degree of protection (EN 60529) | IP20 | IP20 | IP20 |
EMC | | | |
Emitted interference | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B |
Noise immunity | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 |
Operating data | | | |
Ambient temperature | | | |
| -20 ... +70 °C | -20 ... +70 °C | 0 ... 60 °C |
| with natural convection | with natural convection | with natural convection |
| -40 ... +85 °C | -40 ... +85 °C | -40 ... +85 °C |
| -40 ... +85 °C | -40 ... +85 °C | -40 ... +85 °C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation | Climate class 3K3, no condensation | Climate class 3K3, no condensation |
Mechanics | | | |
Connection technology | screw-type terminals | screw-type terminals | screw-type terminals |
Connections | | | |
| Input, output and ground: removable screw terminal, each 1 x 0.5 ... 2.5 mm? single-core/finely stranded | Input, output and ground: removable screw terminal, each 1 x 0.5 ... 2.5 mm? single-core/finely stranded | Input, output and ground: 1 screw terminal each for 0.33 ... 10 mm? single-core/finely stranded |
| Relay contact: 1 screw terminal each for 0.5 ... 2.5 mm? single-core/finely stranded | Relay contact: 1 screw terminal each for 0.5 ... 2.5 mm? single-core/finely stranded | Relay contact: 1 screw terminal each for 0.5 ... 2.5 mm? single-core/finely stranded |
Width of the enclosure | 30 mm | 30 mm | 70 mm |
Height of the enclosure | 80 mm | 80 mm | 125 mm |
Depth of the enclosure | 100 mm | 100 mm | 125 mm |
Weight, approx. | 0.125 kg | 0.125 kg | 0.5 kg |
Product property of the enclosure housing for side-by-side mounting | Yes | Yes | Yes |
Installation | Snaps onto DIN rail EN 60715 35x7.5/15 | Snaps onto DIN rail EN 60715 35x7.5/15 | Snaps onto DIN rail EN 60715 35x7.5/15 |
Electrical accessories | Removable spring-type terminal 6EP1971-5BA00 | Removable spring-type terminal 6EP1971-5BA00 | |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |