Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2016
архивный
(4872) 700-366
skenergo@mail.ru

Управляемые коммутаторы SIPLUS SCALANCE X-200

Order number

6GK5204-2BB10-2AA3

6GK5204-2BB11-2AA3

6GK5204-2BB10-2CA2

Product type designation

SCALANCE X204-2

SCALANCE X204-2FM

SCALANCE X204-2TS

Transmission rate

 

 

 

Transfer rate

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

Interfaces

 

 

 

Number of electrical/optical connections

 

 

 

  • ? for network components or terminal equipment maximum

6

6

6

Number of electrical connections

 

 

 

  • ? for network components or terminal equipment

4

4

4

Type of electrical connection

 

 

 

  • ? for network components or terminal equipment

RJ45 port

RJ45 port

RJ45 port

Number of optical interfaces

 

 

 

  • ? for fiber optic cable at 100 Mbit/s

2

2

2

Design of the optical interface

 

 

 

  • ? for fiber optic cable at 100 Mbit/s

BFOC port (multimode up to 5 km)

BFOC port (multimode up to 5 km)

BFOC port (multimode up to 5 km)

Connectable optical power relative to 1 mW

 

 

 

  • ? of the transmitter output

-19 ... -14

-19 ... -14

-19 ... -14

Optical sensitivity relating to 1 mW of the receiver input minimum

-34 dB

-34 dB

-34 dB

Damping ratio of the FOC transmission link minimum necessary

0 dB

0 dB

0 dB

Range at the optical interface depending on the optical fiber used

0 ... 5 km

0 ... 5 km

0 ... 5 km

Interfaces for communication integrated

 

 

 

Number of 100 Mbit/s ST(BFOC) ports

 

 

 

  • ? for multimode

2

2

2

Number of 100 Mbit/s SC ports

 

 

 

  • ? for multimode

0

0

0

Number of 1000 Mbit/s LC ports

 

 

 

  • ? for multimode

0

0

0

  • ? for single mode (LD)

0

0

0

Interfaces others

 

 

 

Number of electrical connections

 

 

 

  • ? for signaling contact

1

1

1

  • ? for power supply

1

1

1

  • ? for redundant voltage supply

1

1

1

Type of electrical connection

 

 

 

  • ? for signaling contact

2-pole terminal block

2-pole terminal block

2-pole terminal block

  • ? for power supply

4-pole terminal block

4-pole terminal block

4-pole terminal block

design of the removable storage

 

 

 

  • ? C-PLUG

Yes

Yes

Yes

Signal-Inputs/outputs

 

 

 

Operating voltage of the signaling contacts

 

 

 

  • ? for DC Rated value

24 V

24 V

24 V

Operating current of the signaling contacts

 

 

 

  • ? for DC maximum

0.1 A

0.1 A

0.05 A

Supply voltage, current consumption, power loss

 

 

 

Type of voltage of the supply voltage

DC

DC

DC

Supply voltage

 

 

 

  • ? external

24 V

24 V

12 V

  • ? external

18 ... 32 V

18 ... 32 V

10 ... 30 V

Supply voltage

 

 

 

  • ? for DC

24 V

  • ? for DC Rated value minimum

10 V

  • ? for DC Rated value maximum

30 V

Product component fusing at power supply input

Yes

Yes

Yes

Fuse protection type at input for supply voltage

0.6 A / 60 V

0.6 A / 60 V

3 A / 32 V

Consumed current maximum

0.265 A

0.265 A

0.6 A

Active power loss

 

 

 

  • ? for DC at 24 V

6.36 W

6.36 W

6.6 W

Permitted ambient conditions

 

 

 

Ambient temperature

 

 

 

  • ? during operation

-40 ... +60 °C

-40 ... +60 °C

-40 ... +70 °C

  • ? during storage

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

  • ? during transport

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

  • ? Note

If the IE switch X-204-2TS is installed horizontally, a maximum ambient temperature of +40 °C is permitted

Relative humidity

 

 

 

  • ? at 25 °C without condensation during operation maximum

95 %

95 %

95 %

Ambient condition

 

 

 

  • ? for operation

Conformal coating, yes

Coating

Conformal Coating, yes

Protection class IP

IP30

IP30

IP20

Design, dimensions and weight

 

 

 

Design

compact

compact

compact

Width

60 mm

60 mm

60 mm

Height

125 mm

125 mm

125 mm

Depth

124 mm

124 mm

124 mm

Net weight

0.78 kg

0.78 kg

0.78 kg

Mounting type

  • ? 35 mm DIN rail mounting

Yes

Yes

Yes

  • ? wall mounting

Yes

Yes

Yes

  • ? S7-300 rail mounting

Yes

Yes

Yes

  • ? S7-1500 rail mounting

No

No

No

Product properties, functions, components general

 

 

 

Cascading in the case of a redundant ring at reconfiguration time of <\~0.3\~s

100

100

100

Cascading in cases of star topology

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Product functions management, configuration

 

 

 

Product function

 

 

 

  • ? CLI

Yes

Yes

Yes

  • ? web-based management

Yes

Yes

Yes

  • ? MIB support

Yes

Yes

Yes

  • ? TRAPs via email

Yes

Yes

Yes

  • ? Configuration with STEP 7

Yes

Yes

Yes

  • ? Port mirroring

Yes

Yes

Yes

  • ? multiport mirroring

No

No

No

  • ? with IRT PROFINET IO switch

No

No

No

  • ? PROFINET IO diagnosis

Yes

Yes

Yes

  • ? switch-managed

Yes

Yes

Yes

Protocol is supported

 

 

 

  • ? Telnet

Yes

Yes

Yes

  • ? HTTP

Yes

Yes

Yes

  • ? HTTPS

Yes

Yes

Yes

  • ? TFTP

Yes

Yes

Yes

  • ? FTP

Yes

Yes

Yes

  • ? BOOTP

No

No

No

  • ? DCP

Yes

Yes

Yes

  • ? LLDP

Yes

Yes

Yes

Identification & maintenance function

 

 

 

  • ? I&M0 - device-specific information

Yes

Yes

Yes

  • ? I&M1 – higher-level designation/location designation

Yes

Yes

Yes

Protocol is supported

 

 

 

  • ? SNMP v1

Yes

Yes

Yes

  • ? SNMP v2

Yes

Yes

Yes

  • ? SNMP v3

Yes

Yes

Yes

Product functions Diagnosis

 

 

 

Product function

 

 

 

  • ? Port diagnostics

Yes

Yes

Yes

  • ? Statistics Packet Size

Yes

Yes

Yes

  • ? Statistics packet type

Yes

Yes

Yes

  • ? Error statistics

Yes

Yes

Yes

Product functions DHCP

 

 

 

Product function

 

 

 

  • ? DHCP client

Yes

Yes

Yes

Product functions Redundancy

 

 

 

Product function

 

 

 

  • ? Ring redundancy

Yes

Yes

Yes

  • ? High Speed Redundancy Protocol (HRP)

Yes

Yes

Yes

  • ? high speed redundancy protocol (HRP) with redundancy manager

Yes

Yes

Yes

  • ? high speed redundancy protocol (HRP) with standby redundancy

No

No

No

Protocol is supported Media Redundancy Protocol (MRP)

Yes

Yes

Yes

Product function

 

 

 

  • ? media redundancy protocol (MRP) with redundancy manager

Yes

Yes

Yes

  • ? Passive listening

Yes

Yes

Yes

Product functions Security

 

 

 

Protocol is supported

 

 

 

  • ? SSH

Yes

Yes

Yes

Product functions Time

 

 

 

Product function

 

 

 

  • ? SICLOCK support

Yes

Yes

Yes

Protocol is supported

 

 

 

  • ? NTP

No

No

No

  • ? SNTP

Yes

Yes

Yes

Standards, specifications, approvals

 

 

 

Standard

 

 

 

  • ? for FM

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

  • ? for hazardous zone

EN 60079-0: 2006, EN60079-15: 2005, II 3 (2) G Ex nA [op is] IIC T4, KEMA 07 ATEX 0145 X

EN 60079-0: 2006, EN60079-15: 2005, II 3 (2) G Ex nA [op is] IIC T4, KEMA 07 ATEX 0145 X

EN 60079-0: 2006, EN60079-15: 2005, II 3 (2) G Ex nA [op is] IIC T4, KEMA 07 ATEX 0145 X

  • ? for safety from CSA and UL

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

  • ? for hazardous zone from CSA and UL

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

  • ? for emitted interference

EN 61000-6-4:2001 (Class A)

EN 61000-6-4:2001 (Class A)

EN 61000-6-4 (Class A)

  • ? for interference immunity

EN 61000-6-4:2001

EN 61000-6-4:2001

EN 61000-6-2

Certificate of suitability

EN 61000-6-4:2001

EN 61000-6-4:2001

EN 61000-6-2, EN 61000-6-4

  • ? CE marking

Yes

Yes

Yes

  • ? C-Tick

Yes

Yes

Yes

  • ? KC approval

Yes

Yes

Yes

  • ? Railway application in accordance with EN 50155

No

No

Yes

  • ? Railway application in accordance with EN 50124-1

No

No

No

Marine classification association

 

 

 

  • ? American Bureau of Shipping Europe Ltd. (ABS)

Yes

Yes

No

  • ? Bureau Veritas (BV)

Yes

Yes

No

  • ? Det Norske Veritas (DNV)

Yes

Yes

No

  • ? Germanische Lloyd (GL)

Yes

Yes

No

  • ? Lloyds Register of Shipping (LRS)

Yes

Yes

No

  • ? Nippon Kaiji Kyokai (NK)

Yes

Yes

No

  • ? Polski Rejestr Statkow (PRS)

Yes

Yes

No

MTBF at 40 °C

74.64 y

87.19 y

72.99 y


Order number

6GK5204-2BC10-2AA3

6GK5204-2BC10-2CA2

Product type designation

SCALANCE X204-2LD

SCALANCE X204-2LD TS

Transmission rate

 

 

Transfer rate

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

Interfaces

 

 

Number of electrical/optical connections

 

 

  • ? for network components or terminal equipment maximum

6

6

Number of electrical connections

 

 

  • ? for network components or terminal equipment

4

4

Type of electrical connection

 

 

  • ? for network components or terminal equipment

RJ45 port

RJ45 port

Number of optical interfaces

 

 

  • ? for fiber optic cable at 100 Mbit/s

2

2

Design of the optical interface

 

 

  • ? for fiber optic cable at 100 Mbit/s

BFOC port (singlemode up to 26 km)

BFOC port (singlemode up to 26 km)

Connectable optical power relative to 1 mW

 

 

  • ? of the transmitter output

-15 ... -7

-15 ... -7

Optical sensitivity relating to 1 mW of the receiver input minimum

-34 dB

-34 dB

Damping ratio of the FOC transmission link minimum necessary

0 dB

0 dB

Range at the optical interface depending on the optical fiber used

0 ... 26 km

0 ... 26 km

Interfaces for communication integrated

 

 

Number of 100 Mbit/s ST(BFOC) ports

 

 

  • ? for multimode

2

2

Number of 100 Mbit/s SC ports

 

 

  • ? for multimode

0

0

Number of 1000 Mbit/s LC ports

 

 

  • ? for multimode

0

0

  • ? for single mode (LD)

0

0

Interfaces others

 

 

Number of electrical connections

 

 

  • ? for signaling contact

1

1

  • ? for power supply

1

1

  • ? for redundant voltage supply

1

1

Type of electrical connection

 

 

  • ? for signaling contact

2-pole terminal block

2-pole terminal block

  • ? for power supply

4-pole terminal block

4-pole terminal block

design of the removable storage

 

 

  • ? C-PLUG

Yes

Yes

Signal-Inputs/outputs

 

 

Operating voltage of the signaling contacts

 

 

  • ? for DC Rated value

24 V

24 V

Operating current of the signaling contacts

 

 

  • ? for DC maximum

0.1 A

0.05 A

Supply voltage, current consumption, power loss

 

 

Type of voltage of the supply voltage

DC

DC

Supply voltage

 

 

  • ? external

24 V

12 V

  • ? external

18 ... 32 V

10 ... 30 V

Supply voltage

 

 

  • ? for DC

24 V

  • ? for DC Rated value minimum

10 V

  • ? for DC Rated value maximum

30 V

Product component fusing at power supply input

Yes

Yes

Fuse protection type at input for supply voltage

0.6 A / 60 V

3 A / 32 V

Consumed current maximum

0.265 A

0.6 A

Active power loss

 

 

  • ? for DC at 24 V

6.36 W

6.6 W

Permitted ambient conditions

 

 

Ambient temperature

 

 

  • ? during operation

-40 ... +60 °C

-40 ... +60 °C

  • ? during storage

-40 ... +70 °C

-40 ... +70 °C

  • ? during transport

-40 ... +70 °C

-40 ... +70 °C

  • ? Note

If the IE switch X-204-2LD TS is installed horizontally a maximum ambient temperature of +40 °C is permitted

Relative humidity

 

 

  • ? at 25 °C without condensation during operation maximum

95 %

95 %

Ambient condition

 

 

  • ? for operation

Conformal coating, yes

Coating

Conformal Coating, yes

Protection class IP

IP30

IP20

Design, dimensions and weight

 

 

Design

compact

compact

Width

60 mm

60 mm

Height

125 mm

125 mm

Depth

124 mm

124 mm

Net weight

0.78 kg

0.78 kg

Mounting type

  • ? 35 mm DIN rail mounting

Yes

Yes

  • ? wall mounting

Yes

Yes

  • ? S7-300 rail mounting

Yes

Yes

  • ? S7-1500 rail mounting

No

No

Product properties, functions, components general

 

 

Cascading in the case of a redundant ring at reconfiguration time of <\~0.3\~s

100

100

Cascading in cases of star topology

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Product functions management, configuration

 

 

Product function

 

 

  • ? CLI

Yes

Yes

  • ? web-based management

Yes

Yes

  • ? MIB support

Yes

Yes

  • ? TRAPs via email

Yes

Yes

  • ? Configuration with STEP 7

Yes

Yes

  • ? Port mirroring

Yes

Yes

  • ? multiport mirroring

No

No

  • ? with IRT PROFINET IO switch

No

No

  • ? PROFINET IO diagnosis

Yes

Yes

  • ? switch-managed

Yes

Yes

Protocol is supported

 

 

  • ? Telnet

Yes

Yes

  • ? HTTP

Yes

Yes

  • ? HTTPS

Yes

Yes

  • ? TFTP

Yes

Yes

  • ? FTP

Yes

Yes

  • ? BOOTP

No

No

  • ? DCP

Yes

Yes

  • ? LLDP

Yes

Yes

Identification & maintenance function

 

 

  • ? I&M0 - device-specific information

Yes

Yes

  • ? I&M1 – higher-level designation/location designation

Yes

Yes

Protocol is supported

 

 

  • ? SNMP v1

Yes

Yes

  • ? SNMP v2

Yes

Yes

  • ? SNMP v3

Yes

Yes

Product functions Diagnosis

 

 

Product function

 

 

  • ? Port diagnostics

Yes

Yes

  • ? Statistics Packet Size

Yes

Yes

  • ? Statistics packet type

Yes

Yes

  • ? Error statistics

Yes

Yes

Product functions DHCP

 

 

Product function

 

 

  • ? DHCP client

Yes

Yes

Product functions Redundancy

 

 

Product function

 

 

  • ? Ring redundancy

Yes

Yes

  • ? High Speed Redundancy Protocol (HRP)

Yes

Yes

  • ? high speed redundancy protocol (HRP) with redundancy manager

Yes

Yes

  • ? high speed redundancy protocol (HRP) with standby redundancy

No

No

Protocol is supported Media Redundancy Protocol (MRP)

Yes

Yes

Product function

 

 

  • ? media redundancy protocol (MRP) with redundancy manager

Yes

Yes

  • ? Passive listening

Yes

Yes

Product functions Security

 

 

Protocol is supported

 

 

  • ? SSH

Yes

Yes

Product functions Time

 

 

Product function

 

 

  • ? SICLOCK support

Yes

Yes

Protocol is supported

 

 

  • ? NTP

No

No

  • ? SNTP

Yes

Yes

Standards, specifications, approvals

 

 

Standard

 

 

  • ? for FM

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

  • ? for hazardous zone

EN 60079-0 : 2006, EN 60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X

EN 60079-0 : 2006, EN 60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X

  • ? for safety from CSA and UL

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

  • ? for hazardous zone from CSA and UL

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

  • ? for emitted interference

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

  • ? for interference immunity

EN 61000-6-2

EN 61000-6-2

Certificate of suitability

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

  • ? CE marking

Yes

Yes

  • ? C-Tick

Yes

Yes

  • ? KC approval

Yes

Yes

  • ? Railway application in accordance with EN 50155

No

Yes

  • ? Railway application in accordance with EN 50121-4

Yes

  • ? Railway application in accordance with EN 50124-1

No

No

Marine classification association

 

 

  • ? American Bureau of Shipping Europe Ltd. (ABS)

Yes

No

  • ? Bureau Veritas (BV)

Yes

No

  • ? Det Norske Veritas (DNV)

Yes

No

  • ? Germanische Lloyd (GL)

Yes

No

  • ? Lloyds Register of Shipping (LRS)

Yes

No

  • ? Nippon Kaiji Kyokai (NK)

Yes

No

  • ? Polski Rejestr Statkow (PRS)

Yes

No

MTBF at 40 °C

74.64 y

85.01 y


Order number

6GK5206-1BB10-2AA3

6GK5206-1BC10-2AA3

6GK5208-0BA10-2AA3

6GK5208-0HA10-2AA6

Product type designation

SCALANCE X206-1

SCALANCE X206-1LD

SCALANCE X208

SCALANCE X208PRO

Transmission rate

 

 

 

 

Transfer rate

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

Interfaces

 

 

 

 

Number of electrical/optical connections

 

 

 

 

  • ? for network components or terminal equipment maximum

7

7

8

8

Number of electrical connections

 

 

 

 

  • ? for network components or terminal equipment

6

6

8

8

Type of electrical connection

 

 

 

 

  • ? for network components or terminal equipment

RJ45 port

RJ45 port

RJ45 port

M12 port, 4-pin, D-coded

Number of optical interfaces

 

 

 

 

  • ? for fiber optic cable at 100 Mbit/s

1

1

Design of the optical interface

 

 

 

 

  • ? for fiber optic cable at 100 Mbit/s

BFOC port (multimode up to 5 km)

BFOC port (singlemode up to 26 km)

Connectable optical power relative to 1 mW

 

 

 

 

  • ? of the transmitter output

-19 ... -14

-15 ... -7

Optical sensitivity relating to 1 mW of the receiver input minimum

-34 dB

Damping ratio of the FOC transmission link minimum necessary

0 dB

0 dB

Range at the optical interface depending on the optical fiber used

0 ... 5 km

0 ... 26 km

Interfaces for communication integrated

 

 

 

 

Number of 100 Mbit/s ST(BFOC) ports

 

 

 

 

  • ? for multimode

1

1

Number of 100 Mbit/s SC ports

 

 

 

 

  • ? for multimode

0

0

0

0

Number of 1000 Mbit/s LC ports

 

 

 

 

  • ? for multimode

0

0

0

0

  • ? for single mode (LD)

0

0

0

0

Interfaces others

 

 

 

 

Number of electrical connections

 

 

 

 

  • ? for signaling contact

1

1

1

1

  • ? for power supply

1

1

1

1

  • ? for redundant voltage supply

1

1

1

1

Type of electrical connection

 

 

 

 

  • ? for signaling contact

2-pole terminal block

2-pole terminal block

2-pole terminal block

5-pin M12 socket (b-coded)

  • ? for power supply

4-pole terminal block

4-pole terminal block

4-pole terminal block

4-pin M12 interface (A-coded)

design of the removable storage

 

 

 

 

  • ? C-PLUG

Yes

Yes

Yes

Yes

Signal-Inputs/outputs

 

 

 

 

Operating voltage of the signaling contacts

 

 

 

 

  • ? for DC Rated value

24 V

24 V

24 V

24 V

Operating current of the signaling contacts

 

 

 

 

  • ? for DC maximum

0.1 A

0.1 A

0.1 A

0.1 A

Supply voltage, current consumption, power loss

 

 

 

 

Type of voltage of the supply voltage

DC

DC

DC

DC

Supply voltage

 

 

 

 

  • ? external

24 V

24 V

24 V

24 V

  • ? external

18 ... 32 V

18 ... 32 V

18 ... 32 V

18 ... 32 V

Product component fusing at power supply input

Yes

Yes

Yes

Yes

Fuse protection type at input for supply voltage

0.6 A / 60 V

0.6 A / 60 V

0.6 A / 60 V

0.6 A / 60 V

Consumed current maximum

0.22 A

0.2 A

0.185 A

0.185 A

Active power loss

 

 

 

 

  • ? for DC at 24 V

5.28 W

5.28 W

3.84 W

4.4 W

Permitted ambient conditions

 

 

 

 

Ambient temperature

 

 

 

 

  • ? during operation

-40 ... +60 °C

-40 ... +60 °C

-40 ... +60 °C

-40 ... +70 °C

  • ? during storage

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

  • ? during transport

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

Relative humidity

 

 

 

 

  • ? at 25 °C without condensation during operation maximum

95 %

95 %

95 %

95 %

Protection class IP

IP30

IP30

IP30

IP65/67

Design, dimensions and weight

 

 

 

 

Design

compact

compact

compact

compact

Width

60 mm

60 mm

60 mm

90 mm

Height

125 mm

125 mm

125 mm

125 mm

Depth

124 mm

124 mm

124 mm

124 mm

Net weight

0.78 kg

0.78 kg

0.78 kg

1 kg

Mounting type

  • ? 35 mm DIN rail mounting

Yes

Yes

Yes

Yes

  • ? wall mounting

Yes

Yes

Yes

Yes

  • ? S7-300 rail mounting

Yes

Yes

Yes

Yes

  • ? S7-1500 rail mounting

No

No

No

No

Product properties, functions, components general

 

 

 

 

Cascading in the case of a redundant ring at reconfiguration time of <\~0.3\~s

100

100

100

100

Cascading in cases of star topology

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Product functions management, configuration

 

 

 

 

Product function

 

 

 

 

  • ? CLI

Yes

Yes

Yes

Yes

  • ? web-based management

Yes

Yes

Yes

Yes

  • ? MIB support

Yes

Yes

Yes

Yes

  • ? TRAPs via email

Yes

Yes

Yes

Yes

  • ? Configuration with STEP 7

Yes

Yes

Yes

Yes

  • ? Port mirroring

Yes

Yes

Yes

Yes

  • ? multiport mirroring

No

No

No

No

  • ? with IRT PROFINET IO switch

No

No

No

No

  • ? PROFINET IO diagnosis

Yes

Yes

Yes

Yes

  • ? switch-managed

Yes

Yes

Yes

Yes

Protocol is supported

 

 

 

 

  • ? Telnet

Yes

Yes

Yes

Yes

  • ? HTTP

Yes

Yes

Yes

Yes

  • ? HTTPS

Yes

Yes

Yes

Yes

  • ? TFTP

Yes

Yes

Yes

Yes

  • ? FTP

Yes

Yes

Yes

Yes

  • ? BOOTP

No

No

No

No

  • ? DCP

Yes

Yes

Yes

Yes

  • ? LLDP

Yes

Yes

Yes

Yes

Identification & maintenance function

 

 

 

 

  • ? I&M0 - device-specific information

Yes

Yes

Yes

Yes

  • ? I&M1 – higher-level designation/location designation

Yes

Yes

Yes

Yes

Protocol is supported

 

 

 

 

  • ? SNMP v1

Yes

Yes

Yes

Yes

  • ? SNMP v2

Yes

Yes

Yes

Yes

  • ? SNMP v3

Yes

Yes

Yes

Yes

Product functions Diagnosis

 

 

 

 

Product function

 

 

 

 

  • ? Port diagnostics

Yes

Yes

Yes

Yes

  • ? Statistics Packet Size

Yes

Yes

Yes

Yes

  • ? Statistics packet type

Yes

Yes

Yes

Yes

  • ? Error statistics

Yes

Yes

Yes

Yes

Product functions DHCP

 

 

 

 

Product function

 

 

 

 

  • ? DHCP client

Yes

Yes

Yes

Yes

Product functions Redundancy

 

 

 

 

Product function

 

 

 

 

  • ? Ring redundancy

Yes

Yes

Yes

Yes

  • ? High Speed Redundancy Protocol (HRP)

Yes

Yes

Yes

Yes

  • ? high speed redundancy protocol (HRP) with redundancy manager

Yes

Yes

Yes

Yes

  • ? high speed redundancy protocol (HRP) with standby redundancy

No

No

No

No

Protocol is supported Media Redundancy Protocol (MRP)

Yes

Yes

Yes

Yes

Product function

 

 

 

 

  • ? media redundancy protocol (MRP) with redundancy manager

Yes

Yes

Yes

Yes

  • ? Passive listening

Yes

Yes

Yes

Yes

Product functions Security

 

 

 

 

Protocol is supported

 

 

 

 

  • ? SSH

Yes

Yes

Yes

Yes

Product functions Time

 

 

 

 

Product function

 

 

 

 

  • ? SICLOCK support

Yes

Yes

Yes

Yes

Protocol is supported

 

 

 

 

  • ? NTP

No

No

No

No

  • ? SNTP

Yes

Yes

Yes

Yes

Standards, specifications, approvals

 

 

 

 

Standard

 

 

 

 

  • ? for FM

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

  • ? for hazardous zone

EN 60079-0: 2006, EN60079-15: 2005, II 3 (2) G Ex nA [op is] IIC T4, KEMA 07 ATEX 0145 X

EN 60079-0 : 2006, EN 60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X

EN 60079-0 : 2006, EN 60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X

EN 60079-0 : 2006, EN 60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X

  • ? for safety from CSA and UL

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

  • ? for hazardous zone from CSA and UL

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

  • ? for emitted interference

EN 61000-6-4:2001 (Class A)

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

EN 61000-6-4 (Class A)

  • ? for interference immunity

EN 61000-6-2:2001

EN 61000-6-2

EN 61000-6-2

EN 61000-6-2

Certificate of suitability

EN 61000-6-2:2001, EN 61000-6-4:2001

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-4

  • ? CE marking

Yes

Yes

Yes

Yes

  • ? C-Tick

Yes

Yes

Yes

Yes

  • ? KC approval

Yes

Yes

Yes

Yes

  • ? Railway application in accordance with EN 50155

No

No

No

No

  • ? Railway application in accordance with EN 50124-1

No

No

No

No

Marine classification association

 

 

 

 

  • ? American Bureau of Shipping Europe Ltd. (ABS)

Yes

Yes

Yes

No

  • ? Bureau Veritas (BV)

Yes

Yes

Yes

No

  • ? Det Norske Veritas (DNV)

Yes

Yes

Yes

No

  • ? Germanische Lloyd (GL)

Yes

Yes

Yes

No

  • ? Lloyds Register of Shipping (LRS)

Yes

Yes

Yes

No

  • ? Nippon Kaiji Kyokai (NK)

Yes

Yes

Yes

No

  • ? Polski Rejestr Statkow (PRS)

Yes

Yes

Yes

No

MTBF at 40 °C

78.71 y

78.71 y

83.71 y

83 y

Accessories

 

 

 

 

Product expansion optional C-PLUG

Yes


Order number

6GK5212-2BB00-2AA3

6GK5212-2BC00-2AA3

6GK5216-0BA00-2AA3

6GK5224-0BA00-2AA3

Product type designation

SCALANCE X212-2

SCALANCE X212-2LD

SCALANCE X216

SCALANCE X224

Transmission rate

 

 

 

 

Transfer rate

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

10 Mbit/s, 100 Mbit/s

Interfaces

 

 

 

 

Number of electrical/optical connections

 

 

 

 

  • ? for network components or terminal equipment maximum

14

14

16

24

Number of electrical connections

 

 

 

 

  • ? for network components or terminal equipment

12

12

16

24

Type of electrical connection

 

 

 

 

  • ? for network components or terminal equipment

RJ45 port

RJ45 port

RJ45 port

RJ45 port

Number of optical interfaces

 

 

 

 

  • ? for fiber optic cable at 100 Mbit/s

2

2

Design of the optical interface

 

 

 

 

  • ? for fiber optic cable at 100 Mbit/s

BFOC port (multimode up to 5 km)

BFOC port (singlemode up to 26 km)

Connectable optical power relative to 1 mW

 

 

 

 

  • ? of the transmitter output

-19 ... -14

-15 ... -7

Optical sensitivity relating to 1 mW of the receiver input minimum

-34 dB

-34 dB

Damping ratio of the FOC transmission link minimum necessary

0 dB

0 dB

Range at the optical interface depending on the optical fiber used

0 ... 5 km

0 ... 26 km

Interfaces for communication integrated

 

 

 

 

Number of 100 Mbit/s ST(BFOC) ports

 

 

 

 

  • ? for multimode

2

2

Number of 100 Mbit/s SC ports

 

 

 

 

  • ? for multimode

0

0

0

0

Number of 1000 Mbit/s LC ports

 

 

 

 

  • ? for multimode

0

0

0

0

  • ? for single mode (LD)

0

0

0

0

Interfaces others

 

 

 

 

Number of electrical connections

 

 

 

 

  • ? for signaling contact

1

1

1

1

  • ? for power supply

1

1

1

1

  • ? for redundant voltage supply

1

1

1

1

Type of electrical connection

 

 

 

 

  • ? for signaling contact

2-pole terminal block

2-pole terminal block

2-pole terminal block

2-pole terminal block

  • ? for power supply

4-pole terminal block

4-pole terminal block

4-pole terminal block

4-pole terminal block

design of the removable storage

 

 

 

 

  • ? C-PLUG

Yes

Yes

Yes

Yes

Signal-Inputs/outputs

 

 

 

 

Operating voltage of the signaling contacts

 

 

 

 

  • ? for DC Rated value

24 V

24 V

24 V

24 V

Operating current of the signaling contacts

 

 

 

 

  • ? for DC maximum

0.1 A

0.1 A

0.1 A

0.1 A

Supply voltage, current consumption, power loss

 

 

 

 

Type of voltage of the supply voltage

DC

DC

DC

DC

Supply voltage

 

 

 

 

  • ? external

24 V

24 V

24 V

24 V

  • ? external

18 ... 32 V

18 ... 32 V

18 ... 32 V

18 ... 32 V

Product component fusing at power supply input

Yes

Yes

Yes

Yes

Fuse protection type at input for supply voltage

1.1 A / 33 V

1.1 A / 33 V

1.1 A / 33 V

1.1 A / 33 V

Consumed current maximum

0.33 A

0.33 A

0.24 A

0.35 A

Active power loss

 

 

 

 

  • ? for DC at 24 V

7.92 W

7.92 W

5.76 W

8.4 W

Permitted ambient conditions

 

 

 

 

Ambient temperature

 

 

 

 

  • ? during operation

-40 ... +60 °C

-40 ... +60 °C

-40 ... +60 °C

-40 ... +60 °C

  • ? during storage

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

  • ? during transport

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

-40 ... +70 °C

Relative humidity

 

 

 

 

  • ? at 25 °C without condensation during operation maximum

95 %

95 %

95 %

95 %

Protection class IP

IP30

IP30

IP30

IP30

Design, dimensions and weight

 

 

 

 

Design

compact

compact

compact

compact

Width

120 mm

120 mm

120 mm

180 mm

Height

125 mm

125 mm

125 mm

125 mm

Depth

124 mm

124 mm

124 mm

124 mm

Net weight

1.2 kg

1.2 kg

1.2 kg

1.6 kg

Mounting type

  • ? 35 mm DIN rail mounting

Yes

Yes

Yes

Yes

  • ? wall mounting

Yes

Yes

Yes

Yes

  • ? S7-300 rail mounting

Yes

Yes

Yes

Yes

  • ? S7-1500 rail mounting

No

No

No

No

Product properties, functions, components general

 

 

 

 

Cascading in the case of a redundant ring at reconfiguration time of <\~0.3\~s

100

100

100

100

Cascading in cases of star topology

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Any (depending only on signal propagation time)

Product functions management, configuration

 

 

 

 

Product function

 

 

 

 

  • ? CLI

Yes

Yes

Yes

Yes

  • ? web-based management

Yes

Yes

Yes

Yes

  • ? MIB support

Yes

Yes

Yes

Yes

  • ? TRAPs via email

Yes

Yes

Yes

Yes

  • ? Configuration with STEP 7

Yes

Yes

Yes

Yes

  • ? Port mirroring

Yes

Yes

Yes

Yes

  • ? multiport mirroring

No

No

No

No

  • ? with IRT PROFINET IO switch

No

No

No

No

  • ? PROFINET IO diagnosis

Yes

Yes

Yes

Yes

  • ? switch-managed

Yes

Yes

Yes

Yes

Protocol is supported

 

 

 

 

  • ? Telnet

Yes

Yes

Yes

Yes

  • ? HTTP

Yes

Yes

Yes

Yes

  • ? HTTPS

Yes

Yes

Yes

Yes

  • ? TFTP

Yes

Yes

Yes

Yes

  • ? FTP

Yes

Yes

Yes

Yes

  • ? BOOTP

No

No

No

No

  • ? DCP

Yes

Yes

Yes

Yes

  • ? LLDP

Yes

Yes

Yes

Yes

Identification & maintenance function

 

 

 

 

  • ? I&M0 - device-specific information

Yes

Yes

Yes

Yes

  • ? I&M1 – higher-level designation/location designation

Yes

Yes

Yes

Yes

Protocol is supported

 

 

 

 

  • ? SNMP v1

Yes

Yes

Yes

Yes

  • ? SNMP v2

Yes

Yes

Yes

Yes

  • ? SNMP v3

Yes

Yes

Yes

Yes

Product functions Diagnosis

 

 

 

 

Product function

 

 

 

 

  • ? Port diagnostics

Yes

Yes

Yes

Yes

  • ? Statistics Packet Size

Yes

Yes

Yes

Yes

  • ? Statistics packet type

Yes

Yes

Yes

Yes

  • ? Error statistics

Yes

Yes

Yes

Yes

Product functions DHCP

 

 

 

 

Product function

 

 

 

 

  • ? DHCP client

Yes

Yes

Yes

Yes

Product functions Redundancy

 

 

 

 

Product function

 

 

 

 

  • ? Ring redundancy

Yes

Yes

Yes

Yes

  • ? High Speed Redundancy Protocol (HRP)

Yes

Yes

Yes

Yes

  • ? high speed redundancy protocol (HRP) with redundancy manager

Yes

Yes

Yes

Yes

  • ? high speed redundancy protocol (HRP) with standby redundancy

No

No

No

No

Protocol is supported Media Redundancy Protocol (MRP)

Yes

Yes

Yes

Yes

Product function

 

 

 

 

  • ? media redundancy protocol (MRP) with redundancy manager

Yes

Yes

Yes

Yes

  • ? Passive listening

Yes

Yes

Yes

Yes

Product functions Security

 

 

 

 

Protocol is supported

 

 

 

 

  • ? SSH

Yes

Yes

Yes

Yes

Product functions Time

 

 

 

 

Product function

 

 

 

 

  • ? SICLOCK support

Yes

Yes

Yes

Yes

Protocol is supported

 

 

 

 

  • ? NTP

No

No

No

No

  • ? SNTP

Yes

Yes

Yes

Yes

Standards, specifications, approvals

 

 

 

 

Standard

 

 

 

 

  • ? for FM

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

FM3611: Class 1, Divison 2, Group A, B, C, D / T4, CL.1, Zone 2, GP. IIC, T4

  • ? for hazardous zone

EN 60079-0: 2006, EN60079-15: 2005, II 3 (2) G Ex nA [op is] IIC T4, KEMA 07 ATEX 0145 X

EN 60079-0 : 2006, EN 60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X

EN 60079-0 : 2006, EN 60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X

EN 60079-0 : 2006, EN 60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0145X

  • ? for safety from CSA and UL

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

UL 60950-1, CSA C22.2 No. 60950-1

  • ? for hazardous zone from CSA and UL

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

ANSI / ISA 12.12.01, CSA C22.2 No. 213-M1987, CL. 1 / Div. 2 / GP. A, B, C, D T4, CL. 1 / Zone 2 / GP. IIC, T4

  • ? for emitted interference

EN 61000-6-4:2001 (Class A)

EN 61000-6-4:2001 (Class A)

EN 61000-6-4:2001 (Class A)

EN 61000-6-4:2001 (Class A)

  • ? for interference immunity

EN 61000-6-2:2001

EN 61000-6-2:2001

EN 61000-6-2:2001

EN 61000-6-2:2001

Certificate of suitability

EN 61000-6-2:2001, EN 61000-6-4:2001

EN 61000-6-2:2001, EN 61000-6-4:2001

EN 61000-6-2:2001, EN 61000-6-4:2001

EN 61000-6-2:2001, EN 61000-6-4:2001

  • ? CE marking

Yes

Yes

Yes

Yes

  • ? C-Tick

Yes

Yes

Yes

Yes

  • ? KC approval

Yes

Yes

Yes

Yes

  • ? Railway application in accordance with EN 50155

No

No

No

No

  • ? Railway application in accordance with EN 50124-1

No

No

No

No

Marine classification association

 

 

 

 

  • ? American Bureau of Shipping Europe Ltd. (ABS)

Yes

Yes

Yes

Yes

  • ? Bureau Veritas (BV)

Yes

Yes

Yes

Yes

  • ? Det Norske Veritas (DNV)

Yes

Yes

Yes

Yes

  • ? Germanische Lloyd (GL)

Yes

Yes

Yes

Yes

  • ? Lloyds Register of Shipping (LRS)

Yes

Yes

Yes

Yes

  • ? Nippon Kaiji Kyokai (NK)

Yes

Yes

Yes

Yes

  • ? Polski Rejestr Statkow (PRS)

No

No

No

No

MTBF at 40 °C

51.18 y

51.18 y

52.07 y

45.87 y


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания
Каталог оборудования 2016
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Введение Industrial Ethernet Введение Передача данных Обзор коммуникаций Топологии Критерии выбора типа сети Сетевые компоненты для Industrial Ethernet Промышленные конверторы каналов связи Industrial Ethernet коммутаторы Обзор Компактные коммутаторы CSM Неуправляемые коммутаторы SCALANCE X-000 Неуправляемые коммутаторы/конверторы SCALANCE X-100 Управляемые коммутаторы SCALANCE X-200 Управляемые коммутаторы SCALANCE X-200 Управляемые коммутаторы SIPLUS SCALANCE X-200 SCALANCE X-200PRO managed SCALANCE XB-200 managed Управляемые коммутаторы SCALANCE XF-200 Управляемая точка доступа SCALANCE X204RNA HSR Управляемые коммутаторы SCALANCE X-200IRT Управляемые коммутаторы SCALANCE X-300 RUGGEDCOM i800 unmanaged or managed RUGGEDCOM RS900 / M900 managed RUGGEDCOM RS950 RNA managed RUGGEDCOM RSG2xxx RUGGEDCOM RSG2100 / M2100 managed RUGGEDCOM RSG2200 / M2200 managed RUGGEDCOM RSG2300 managed RUGGEDCOM RSG2488 managed RUGGEDCOM RS1600 managed RUGGEDCOM RS8000 managed RUGGEDCOM Accessories RUGGEDCOM Technology Modules Коммутаторы Industrial Ethernet уровня 3/ маршрутизаторы Serial Device Servers Аксессуары Активные сетевые компоненты Безопасность передачи данных в промышленных сетях Системные интерфейсы Аксессуары RUGGEDCOM Accessories Управление сетью Сетевые переходы Обслуживание промышленных сетей Решения партнеров PROFINET PROFIBUS AS-интерфейс IO-Link Промышленная беспроводная связь SINAUT ST7 Информационная безопасность в промышленности Сетевые переходы ECOFAST Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Системы управления процессом Датчики Блоки питания Продукты для специальных требований Автоматизация и безопасность зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо




  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика