ATEX II 2G/3G control unit, continuous purgingControl unit ATEX II 2G, continuous purging | | Guidelines | EC EMC directive 89/336/EEC, EC low voltage, RL 73/23/EEC, Ex directive 94/9/EC | Design | Explosion-protected enclosure (EEx e) with viewing window in the cover | Degree of protection | IP65 | Terminals | 2.5 mm, finely stranded | Pressure sensors | MIN A = 0 … 25 hPa, MIN B = 0 … 25 hPa, MAX = 0 … 25 hPa, MAX 1 = 0 … 25 hPa, DIFF A = 0 … 25 hPa, DIFF B = 0 … 25 hPa | Prepurging time | 0 … 99 min; 5 sec dropout delayed | Weight | 10 kg | Electrical data | | Supply voltage | 230 V AC (115 V AC) ± 10%, 48 … 62 Hz | Power consumption | 21 W /230 V | NO contacts | K2/3; max. 250 V, 5 A with cos ? = 1, K4/K5; supply voltage or floating, max. 250 V, 5 A with cos ? = 1 | Communication | RS 485 interface | Temperature switching value (option) | 0 … +40 °C | Explosion protection | | Marking | EEx e d ib [ia p] IIC T4/T6 | Test certification | DMT 99 ATEX E 082 | Ambient temperature | -20 … +40 °C |
|
|