I?n ? 30 mA: Additional protection in the case of direct contact
I?n ? 300 mA: Preventative fire protection in the case of ground fault currents
Product standards: IEC/EN 61008-1 (VDE 0664, Part 10); IEC 61008-2-1 (VDE 0664, Part 11) ; IEC/EN 61543 (VDE 0664, Part 30)
Un 230/400 V; 50 bis 60 Hz; applicable in networks of up to 240/415 V AC
Un 500 V; 50 to 60 Hz; applicable in 500 V AC networks
Definition of surge current withstand capability with current waveform 8/20 ?s according to DIN VDE 0432, Part 2.
[S] S-type: Can be used as an upstream group switch for selective tripping of a downstream standard miniature circuit breaker. Very high surge current withstand capability: > 5 kA
[K] K-type: For short-time delayed tripping at the occurrence of transient leakage currents. High surge current withstand capability: > 3 kA
Version with 50 … 400 Hz applicable for line frequencies between 50 and 400 Hz