SIMATIC NET IE SOFTNET-S7, СЕРВИС АВТОМАТИЧЕСКОГО ОБНОВЛЕНИЯ ПРОГРАММНОГО ОБЕСПЕЧЕНИЯ В ТЕЧЕНИИ 1 ГОДА, НЕОБХОДИМА ТЕКУЩАЯ ВЕРСИЯ ПРОГРАММНОГО ОБЕСПЕЧЕНИЯ
455.80 ?
SIPLUS CP 443-1
Connection of SIMATIC S7-400 to Industrial Ethernet
2 x RJ45 interface for 10/100 Mbit/s full/half-duplex connection with auto-sensing/auto-negotiation and auto-crossover function
Integrated real-time switch ERTEC with two ports
Multi-protocol operation for ISO, TCP/IP, UDP and PROFINET IO protocols
Adjustable Keep Alive function
Communications services:
Open communication (ISO, TCP/IP, and UDP)
PROFINET IO Controller with real-time properties RT and IRT
PG/OP communication: Cross-network by means of S7 routing
S7 communication
Media redundancy (MRP); the CP supports the media redundancy procedure MRP within an Ethernet network with ring topology.
Multicast for UDP
Access protection via configurable access list
Support for fail-safe programmable controllers together with SIMATIC S7-400 CPU 416F-3PN/DP
Module replacement without PG
Operation in the SIMATIC H system for redundant S7-communication
Configuration with STEP 7
Diagnostics possibilities in STEP 7 and via web browser
Automatic CPU-clock setting via Industrial Ethernet with NTP or SIMATIC procedure
Integration of network management systems via SNMP (MIB II diagnostic information)
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
SIPLUS CP 443-1
Article No.
6AG1 443-1EX20-4XE0
Order number based on
6GK7 443-1EX20-0XE0
Ambient temperature range
0 ... +60 °C
Conformal coating
Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies, except for the ambient conditions
Ambient conditions
Relative humidity
100%, condensation/frost permitted. No commissioning in bedewed state.
Biologically active substances, compliance with EN 60721-3-3
Class 3B2 mold spores, fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!
Chemically active substances, compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation!
Mechanically active substances, compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!
Air pressure (depending on the highest positive temperature range specified)
1080 ... 795 hPa (-1000 ... +2000 m) see ambient temperature range