RL 260/23
Binary Input, 4 inputs for 12 ... AC/DC 230 V
- 4 Inputs for AC/DC 12...230 V
- Max. cable length, unshielded, twisted 100 m
- Maintenance-free terminals for connection and through-wiring of untreated single-core, stranded or multi-core conductors, 0.5 ... 2.5 mm [/2]
- The following functions can be selected per input:
- Switching state/send binary value
- Switch edge/short/long switch
- Dimming, shading control, single button group control
- 1/8-bit scene control
- 8-bit value edge
- 8-bit value short/long
- 16-bit floating-point value edge
- 16-bit floating-point short/long
- pulse counting with/without limit value monitoring (8/16/32 Bit)
- The following functions can be selected per input pair:
- 2-pushbutton dimming with stop telegram (4 bit) and 2-pushbutton shading control
- Optional blocking of each input by means of the respective blocking object
- Transmission of the input objects after change
- Optional cyclic transmission of input objects
- Bus-powered electronics
- Integrated bus coupling units, bus connection via bus terminal
|
|