Suitable line-side power components are assigned depending on the power rating of the Power Modules.
The following tables list recommended components and apply for ambient temperatures up to 40 °C (104 °F).
Further information about the line contactors, switch disconnectors, circuit breakers and fuses specified in the table can be found in Catalogs LV 10.1 and IC 10.
Assignment of line-side power components to Power Modules in blocksize format
|
Rated output current
|
Type rating
|
Suitable for Power Module, blocksize format
|
Line contactor
|
Circuit breaker
IEC 60947 and UL489/CSA C22.2 No. 5-02
|
UL/CSA fuse, Class J
Available from: Mersen http://www.ep.mersen.com
|
|
A
|
kW (HP)
|
Type 6SL3210-
|
Type
|
Order No.
|
Rated current
|
Size mm
|
Reference No.
|
|
Line voltage 200 ... 240 V 1 AC
|
|
0.9
|
0.12 (0.2)
|
1SB11-0...
|
5TT57…
|
5SJ4206-7HG41
|
6 A
|
21 ? 57
|
AJT6
|
|
2.3
|
0.37 (0.5)
|
1SB12-3...
|
5TT57…
|
5SJ4210-7HG41
|
10 A
|
21 ? 57
|
AJT10
|
|
3.9
|
0.75 (0.75)
|
1SB14-0...
|
5TT57…
|
5SJ4216-7HG41
|
15 A
|
21 ? 57
|
AJT15
|
|
Rated output current
|
Type rating
|
Suitable for Power Module, blocksize format
|
Line contactor
|
Circuit breaker
IEC 60947
|
Circuit breaker
UL489/CSA C22.2 No. 5-02
|
Main switch
|
|
A
|
kW (HP)
|
Type 6SL3210-
|
Type
|
Order No.
|
|
Order No.
|
|
Line voltage 380 ... 480 V 3 AC
|
|
1.3
|
0.37 (0.5)
|
1SE11-3UA0
|
3RT2015-...
|
3RV2011-1DA10
|
–
|
3LD2003-1TP51
|
|
1.7
|
0.55 (0.75)
|
1SE11-7UA0
|
3RT2015-...
|
3RV2011-1DA10
|
–
|
3LD2003-1TP51
|
|
2.2
|
0.75 (1)
|
1SE12-2UA0
|
3RT2015-...
|
3RV2011-1FA10
|
–
|
3LD2003-1TP51
|
|
3.1
|
1.1 (1.5)
|
1SE13-1UA0
|
3RT2015-...
|
3RV2011-1GA10
|
–
|
3LD2003-1TP51
|
|
4.1
|
1.5 (2)
|
1SE14-1UA0
|
3RT2015-...
|
3RV2011-1HA10
|
–
|
3LD2003-1TP51
|
|
5.9
|
2.2 (3)
|
1SE16-0...
|
3RT2015-...
|
3RV2011-1KA10
|
–
|
3LD2003-1TP51
|
|
7.7
|
3 (5)
|
1SE17-7...
|
3RT2015-...
|
3RV2011-4AA10
|
–
|
3LD2003-1TP51
|
|
10
|
4 (5)
|
1SE21-0...
|
3RT2016-...
|
3RV2021-4BA10
|
–
|
3LD2103-1TP51
|
|
18
|
7.5 (10)
|
1SE21-8...
|
3RT1025-...
|
3RV1031-4EA10
|
–
|
3LD2203-0TK51
|
|
25
|
11 (15)
|
1SE22-5...
|
3RT1026-...
|
3RV1031-4FA10
|
–
|
3LD2504-0TK51
|
|
32
|
15 (20)
|
1SE23-2...
|
3RT1034-...
|
3RV1031-4HA10
|
–
|
3LD2504-0TK51
|
|
38
|
18.5 (25)
|
1SE23-8...
|
3RT1035-...
|
3RV1042-4JA10
|
–
|
3LD2504-0TK51
|
|
45
|
22 (30)
|
1SE24-5...
|
3RT1036-...
|
3RV1042-4KA10
|
–
|
3LD2504-0TK51
|
|
60
|
30 (37)
|
1SE26-0...
|
3RT1044-...
|
3RV1042-4MA10
|
3VL2191-3KN30-....
|
3LD2704-0TK51
|
|
75
|
37 (50)
|
1SE27-5...
|
3RT1045-...
|
3VL1712-1DD33-....
|
3VL2110-3KN30-....
|
3LD2704-0TK51
|
|
90
|
45 (60)
|
1SE31-0...
|
3RT1046-...
|
3VL1716-1DD33-....
|
3VL2112-3KN30-....
|
3LD2804-0TK51
|
|
110
|
55 (75)
|
1SE31-1...
|
3RT1054-...
|
3VL3720-1DC36-....
|
3VL2115-3KN30-....
|
3KA5330-1GE01
|
|
145
|
75 (100)
|
1SE31-5...
|
3RT1056-...
|
3VL3720-1DC36-....
|
3VL3120-3KN30-....
|
3KA5530-1GE01
|
|
178
|
90 (125)
|
1SE31-8...
|
3RT1064-...
|
3VL4725-1DC36-....
|
3VL3125-3KN30-....
|
3KA5530-1GE01
|
|
Rated output current
|
Type rating
|
Suitable for Power Module, blocksize format
|
Fuse switch disconnector
|
Switch disconnector with fuse holders
|
Fuse
|
UL/CSA fuse, Class J 1)
Available from: Mersen http://www.ep.mersen.com
|
|
A
|
kW (HP)
|
Type 6SL3210-
|
Order No.
|
Order No.
|
Order No.
|
Rated current
|
Size mm
|
Reference No.
|
|
Line voltage 380 … 480 V 3 AC
|
|
1.3
|
0.37 (0.5)
|
1SE11-3UA0
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3804
|
4 A
|
21 ? 57
|
AJT4
|
|
1.7
|
0.55 (0.75)
|
1SE11-7UA0
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3804
|
4 A
|
21 ? 57
|
AJT4
|
|
2.2
|
0.75 (1)
|
1SE12-2UA0
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3801
|
6 A
|
21 ? 57
|
AJT6
|
|
3.1
|
1.1 (1.5)
|
1SE13-1UA0
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3803
|
8 A
|
21 ? 57
|
AJT8
|
|
4.1
|
1.5 (2)
|
1SE14-1UA0
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3803
|
10 A
|
21 ? 57
|
AJT10
|
|
5.9
|
2.2 (3)
|
1SE16-0...
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3803
|
10 A
|
21 ? 57
|
AJT10
|
|
7.7
|
3 (5)
|
1SE17-7...
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3805
|
12 A
|
21 ? 57
|
AJT12
|
|
10
|
4 (5)
|
1SE21-0...
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3805
|
15 A
|
21 ? 57
|
AJT15
|
|
18
|
7.5 (10)
|
1SE21-8...
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3810
|
25 A
|
21 ? 57
|
AJT25
|
|
25
|
11 (15)
|
1SE22-5...
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3814
|
35 A
|
27 ? 60
|
AJT35
|
|
32
|
15 (20)
|
1SE23-2...
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3817
|
45 A
|
27 ? 60
|
AJT45
|
|
38
|
18.5 (25)
|
1SE23-8...
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3820
|
50 A
|
27 ? 60
|
AJT50
|
|
45
|
22 (30)
|
1SE24-5...
|
3NP4010-0CH01
|
3KL5030-1GB01
|
3NA3822
|
60 A
|
27 ? 60
|
AJT60
|
|
60
|
30 (37)
|
1SE26-0...
|
3NP4010-0CH01
|
3KL5230-1GB01
|
3NA3824
|
90 A
|
29 ? 117
|
AJT90
|
|
75
|
37 (50)
|
1SE27-5...
|
3NP4010-0CH01
|
3KL5230-1GB01
|
3NA3830
|
100 A
|
29 ? 117
|
AJT100
|
|
90
|
45 (60)
|
1SE31-0...
|
3NP4070-0CH01
|
3KL5230-1GB01
|
3NA3832
|
125 A
|
41 ? 146
|
AJT125
|
|
110
|
55 (75)
|
1SE31-1...
|
3NP4070-0CH01
|
3KL5330-1GB01
|
3NA3836
|
150 A
|
41 ? 146
|
AJT150
|
|
145
|
75 (100)
|
1SE31-5...
|
3NP4270-0CA01
|
3KL5530-1GB01
|
3NA3140
|
200 A
|
41 ? 146
|
AJT200
|
|
178
|
90 (125)
|
1SE31-8...
|
3NP4270-0CA01
|
3KL5530-1GB01
|
3NA3144
|
250 A
|
54 ? 181
|
AJT250
|
1) Not suitable for 3NP and 3KL switch disconnectors.
|
|