Basic Line Modules in booksize format
6SL313...
|
|
|
Line connection voltage
(up to 2000 m (6562 ft) above sea level)
|
380 ... 480 V 3 AC ±10 % (in operation -15 % < 1 min)
|
|
Line frequency
|
47 … 63 Hz
|
|
SCCR (short-circuit current rating)
|
65 kA in conjunction with the recommended fuses class J or circuit breakers in accordance with UL489 / CSA 22.2 No. 5-02
see recommended line-side components
|
|
Line power factor
at rated power
|
|
- Fundamental Power factor (cos ?1)
|
> 0.96
|
|
|
0.75 … 0.93
|
|
Overvoltage category
to EN 60664?1
|
Class III
|
|
DC link voltage, approx.
|
1.35 x line voltage1)
|
|
Electronics power supply
|
24 V DC, -15 %/+20 %
|
|
Radio interference suppression
|
|
|
|
|
- 20 kW and 40 kW Basic Line Modules
|
No radio interference suppression
|
|
|
Category C3 to EN 61800?3 Total cable length up to 350 m (1148 ft) (shielded)
|
|
|
Category C2 to EN 61800?3 Total cable length up to 350 m (1148 ft) (shielded)
|
|
Type of cooling
|
- Internal air cooling,
power units with forced air cooling using a built-in fan
- Cold plate cooling
|
|
Permissible ambient and coolant temperature (air)
during operation for line-side components, Line Modules and Motor Modules
|
0 … 40 °C (32 … 104 °F) without derating, > 40 … 55 °C (104 … 131 °F) see derating characteristics
|
|
Installation altitude
|
Up to 1000 m (3281 ft) above sea level without derating, > 1000 ... 4000 m (3281 ... 13124 ft) above sea level, see derating characteristics
|
|
Conformity
|
CE (Low Voltage and EMC Directives)
|
|
Approvals, according to
|
cULus
|
1) The DC link voltage is unregulated and load-dependent. For further information see chapter System description – Dimensioning.
|
Line voltage 380 ... 480 V 3 AC
|
Basic Line Modules in booksize format
|
|
|
|
6SL3130-1TE22-0AA0
|
6SL3130-1TE24-0AA0
|
6SL3130-1TE31-0AA0
|
|
|
|
6SL3136-1TE22-0AA0
|
6SL3136-1TE24-0AA0
|
6SL3136-1TE31-0AA0
|
|
Power
|
|
|
|
|
|
|
|
|
|
|
|
|
kW
|
20
|
40
|
100
|
|
|
(HP)
|
(25)
|
(50)
|
(125)
|
|
|
kW
|
26
|
52
|
130
|
|
|
kW
|
60
|
120
|
175
|
|
Braking power
with external braking resistor
|
|
|
|
|
|
|
kW
|
40
|
80
|
–
|
- Continuous braking power Pd (= 0.25 ? Pn)
|
kW
|
5
|
10
|
–
|
|
DC link current
|
|
|
|
|
|
|
A
|
34
|
67
|
167
|
|
|
A
|
43
|
87
|
217
|
|
|
A
|
100
|
200
|
292
|
|
Input current
|
|
|
|
|
- Rated current
at 380 V 3 AC
|
A
|
35
|
69
|
172
|
|
|
A
|
113
|
208
|
301
|
|
Activation threshold
Braking chopper
|
V
|
774
|
774
|
–
|
|
Resistance value
of the external braking resistor
|
?
|
? 14.8
|
? 7.4
|
–
|
|
Cable length, max.
to braking resistor
|
m (ft)
|
15 (50)
|
15 (50)
|
–
|
|
Connection for braking resistor (X2)
|
|
Screw-type terminals
|
Screw-type terminals
|
–
|
- Conductor cross-section, max.
|
mm2
|
0.5 … 4
|
0.5 … 10
|
|
|
Current requirement, max
24 V DC electronics power supply
|
A
|
1
|
1.4
|
2
|
|
Current carrying capacity
|
|
|
|
|
|
|
A
|
20
|
20
|
20
|
|
|
A
|
100
|
200
|
200
|
|
DC link capacitance
|
|
|
|
|
|
|
?F
|
940
|
1880
|
4100
|
|
|
?F
|
20000
|
20000
|
50000
|
|
Internal air cooling
|
|
|
|
|
|
|
kW
|
0.144
|
0.284
|
0.628
|
|
|
m3/s (ft3/s)
|
0.016 (0.565)
|
0.031 (1.095)
|
0.05 (1.77)
|
- Sound pressure level LpA (1 m)
|
dB
|
< 60
|
< 65
|
< 65
|
|
Cold plate cooling
|
|
|
|
|
|
|
kW
|
0.047/0.095
|
0.071/0.205
|
0.168/0.45
|
|
|
K/W
|
0.075
|
0.05
|
0.045
|
|
Line connection
U1, V1, W1
|
|
Screw-type terminals
|
Screw-type terminals
|
M8 screw stud
|
- Conductor cross-section, max.
|
mm2
|
0.5 … 16
|
10 … 50
|
1 ? 35 … 120 or 2 ? 50
|
|
Shield connection
|
|
Integrated into the power plug
|
See Accessories
|
See Accessories
|
|
PE connection
|
|
M5 screw
|
M6 screw
|
M6 screw
|
|
Cable length, max.
(total of all motor power cables and DC link)
|
|
|
|
|
|
|
m (ft)
|
1000/1500 (3281/4921) (above 630/850 m (2067/2789 ft) with Voltage Clamping Module)
|
1000/1500 (3281/4921) (above 630/850 m (2067/2789 ft) with Voltage Clamping Module)
|
1000/1500 (3281/4921) (above 630/850 m (2067/2789 ft) with Voltage Clamping Module)
|
|
Degree of protection
|
|
IP20
|
IP20
|
IP20
|
|
Dimensions
|
|
|
|
|
|
|
mm (in)
|
100 (3.94)
|
150 (5.91)
|
200 (7.87)
|
|
|
mm (in)
|
380 (15.0)
|
380 (15.0)
|
380 (15.0)
|
|
|
|
|
|
|
- With internal air cooling
|
mm (in)
|
270 (10.6)
|
270 (10.6)
|
270 (10.6)
|
|
|
mm (in)
|
226 (8.90)
|
226 (8.90)
|
226 (8.90)
|
|
Weight, approx.
|
|
|
|
|
- With internal air cooling
|
kg (lb)
|
6.8 (15)
|
11.3 (25)
|
15.8 (35)
|
|
|
kg (lb)
|
6.4 (14)
|
10.9 (24)
|
16.4 (36)
|
1) Power loss of Basic Line Module at rated output including losses of 24 V DC electronics power supply.
2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be dimensioned accordingly.
|
|