Line supply voltage +10 %, -15 %
|
3 ~ AC 230 ... 500 V (for TN/TT line supplies) 3 ~ AC 230 ... 415 V (for TN/TT line supplies) 3 ~ AC 230 ... 500 V (for IT line supplies) 3 ~ AC 400 ... 690 V (for TN/TT/IT line supplies)
|
|
Line supply cos ? (1)
|
approx. 0.99
|
|
Line supply frequency
|
47 ... 63 Hz
|
|
Maximum output frequency
|
120 ... 250 Hz (Setting range depends on the unit power rating)
|
|
Output voltage (basic fundamental)
|
3 ? 0 ... line supply voltage
|
|
Clock frequency
|
1.5 ... 10 kHz, can be parameterized (Setting range depends on the unit power rating)
|
|
Motor cable length (shielded or non-shielded)
|
200 ... 300 m (690 V: 100 to 300 m)
|
|
Degree of protection: Compact drive units Cabinet units/systems
|
IP20 IP21, degrees of protection are optionally available
|