Product name
|
Active Line Modules in chassis format
|
| |
6SL3330-7TE3...
|
|
Line supply voltage
Up to 2000 m (6562 ft) above sea level
|
380 ... 480 V 3 AC ±10% (-15% < 1 min)
|
|
Line frequency
|
47 … 63 Hz
|
|
Line power factor
|
|
- Fundamental component (cos ?1)
|
1.0 (factory setting) can be altered by input of a reactive current setpoint
|
|
|
1.0 (factory setting)
|
|
Overvoltage category
According to EN 60664?1
|
Class III
|
|
DC link voltage Vd
|
The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.
Factory setting for DC link voltage: 1.5 ? line voltage
|
|
Electronic power supply
|
24 V DC, -15 %/+20 %
|
|
Radio interference suppression
|
|
- Standard
With Active Interface Module
|
Category C3 according to EN 61800?3
|
|
Cooling method
|
Increased air cooling by means of built-in fan
|
|
Permissible ambient or coolant temperature (air)
In operation for line-side components, Line Modules and Motor Modules
|
0 … 40 °C (32 … 104 °F) without derating, > 40 … 55 °C (104 … 131 °F), see derating characteristics
|
|
Installation altitude
|
Up to 2000 m (6562 ft) above sea level without derating, > 2000 ... 4000 m (6562 ... 13124 ft) above sea level, see derating characteristics
|
|
Declarations of conformity
|
CE (Low Voltage and EMC Directives)
|
|
Approvals, according to
|
cULus
|
|
Line supply voltage 380 … 480 V 3 AC
|
Active Line Module in chassis format
|
| |
6SL3330?...
|
7TE32-1AA3
|
7TE32-6AA3
|
7TE33-8AA3
|
7TE35-0AA3
|
|
Infeed/regenerative feedback power
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
kW
|
132
|
160
|
235
|
300
|
|
|
(HP)
|
(200)
|
(225)
|
(350)
|
(450)
|
|
|
kW
|
198
|
240
|
352,5
|
450
|
|
DC link current
|
|
|
|
|
|
|
|
A
|
235
|
291
|
425
|
549
|
|
|
A
|
209
|
259
|
378
|
489
|
|
|
A
|
352
|
436
|
637
|
823
|
|
Input current
|
|
|
|
|
|
- Rated current at 400 V 3 AC
|
A
|
210
|
260
|
380
|
490
|
|
|
A
|
315
|
390
|
570
|
735
|
|
Current requirement
|
|
|
|
|
|
- 24 V DC electronic power supply, max.
|
A
|
1.1
|
1.1
|
1.35
|
1.35
|
- Fan supply at 400 V 2 AC, 50/60 Hz, max.
|
A
|
0.63/0.95
|
1.13/1.7
|
1.8/2.7
|
1.8/2.7
|
|
DC link capacitance
|
µF
|
4200
|
5200
|
7800
|
9600
|
|
Power loss, max.
|
kW
|
2.3
|
2.9
|
4.2
|
5.1
|
|
Cooling air requirement
|
m3/s (ft3/s)
|
0.17 (6.0)
|
0.23 (8.1)
|
0.36 (12.7)
|
0.36 (12.7)
|
|
Sound pressure level
L
pA (1 m) 1) at 50/60 Hz
|
dB
|
74/76
|
75/77
|
76/78
|
76/78
|
|
Line connection
U1, V1, W1
|
|
Flat connector for M10 screw
|
Flat connector for M10 screw
|
Flat connector for M10 screw
|
Flat connector for M10 screw
|
- Conductor cross-section, max.
|
mm2
|
2 ? 185
|
2 ? 185
|
2 ? 185
|
2 ? 185
|
|
DC link connection
DCP, DCN
|
|
Flat connector for M10 screw
|
Flat connector for M10 screw
|
Flat connector for M10 screw
|
Flat connector for M10 screw
|
- Conductor cross-section, max.
|
mm2
|
2 ? 185
|
2 ? 185
|
2 ? 185
|
2 ? 185
|
|
PE connection
|
|
M10 screw
|
M10 screw
|
M10 screw
|
M10 screw
|
- Conductor cross-section, max.
|
|
|
|
|
|
|
|
mm2
|
1 ? 185
|
1 ? 185
|
1 ? 185
|
1 ? 185
|
|
|
mm2
|
2 ? 185
|
2 ? 185
|
2 ? 185
|
2 ? 185
|
|
Cable length, max.
Total of all motor cables and DC link
|
|
|
|
|
|
|
|
m (ft)
|
2700 (8859)
|
2700 (8859)
|
2700 (8859)
|
2700 (8859)
|
|
|
m (ft)
|
4050 (13288)
|
4050 (13288)
|
4050 (13288)
|
4050 (13288)
|
|
Degree of protection
|
|
IP20
|
IP20
|
IP20
|
IP20
|
|
Dimensions
|
|
|
|
|
|
|
|
mm (in)
|
326 (12.83)
|
326 (12.83)
|
326 (12.83)
|
326 (12.83)
|
|
|
mm (in)
|
1400 (55.12)
|
1400 (55.12)
|
1533 (60.35)
|
1533 (60.35)
|
|
|
mm (in)
|
356 (14.02)
|
356 (14.02)
|
543 (21.38)
|
543 (21.38)
|
|
Frame size
|
|
FX
|
FX
|
GX
|
GX
|
|
Weight, approx.
|
kg (lb)
|
88 (194)
|
88 (194)
|
152 (335)
|
152 (335)
|
1) Total sound pressure level of Active Interface Module and Active Line Module.
2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be dimensioned accordingly.
|
|