HART
|
PROFIBUS PA or Foundation Fieldbus
|
Input
|
|
Measured variable
|
Level
|
Spans (infinitely adjustable) or nominal measuring range and max. permissible operating pressure
|
Span
|
Maximum operating pressure
|
Nominal measuring range
|
Maximum operating pressure
|
|
25 ... 250 mbar g (0.36 ... 3.63 psi g)
|
See "Mounting flange"
|
250 mbar g (3.63 psi g)
|
See "Mounting flange"
|
|
25 ... 600 mbar g (0.36 ... 8.7 psi g)
|
See "Mounting flange"
|
600 mbar g (8.7 psi g)
|
See "Mounting flange"
|
|
53 ... 1600 mbar g (0.77 ... 23.2 psi g)
|
See "Mounting flange"
|
1600 mbar g (23.2 psi g)
|
See "Mounting flange"
|
|
160 ... 5000 mbar g (2.32 ... 72.5 psi g)
|
See "Mounting flange"
|
5000 mbar g (72.5 psi g)
|
See "Mounting flange"
|
Lower measuring limit
|
|
|
- Measuring cell with silicone oil filling
|
-100 % of max. span or 30 mbar (0.435 psi a), depending on mounting flange
|
Upper measuring limit
|
100 % of max. span
|
100 % of the max. nominal measuring range
|
Output
|
|
Output signal
|
4 ... 20 mA
|
Digital PROFIBUS PA or Foundation Fieldbus signal
|
- Lower limit (infinitely adjustable)
|
3.55 mA, factory preset to 3.84 mA
|
-
|
- Upper limit (infinitely adjustable)
|
23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA
|
-
|
Load
|
|
- Without HART communication
|
R
B ≤ (UH - 10.5 V)/0.023 A in Ω, UH : Power supply in V
|
-
|
|
R
B = 230 ... 500 Ω (SIMATIC PDM) or RB = 230 ... 1100 Ω (HART Communicator)
|
-
|
Physical bus
|
-
|
IEC 61158-2
|
Protection against polarity reversal
|
Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage.
|
Measuring accuracy
|
Acc. to EN 60770-1
|
Reference conditions (All error data refer always refer to the set span)
|
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F)) r: Span ratio (r = max. span / set span)
|
Error in measurement and fixed-point setting (including hysteresis and repeatability)
|
|
|
|
≤ 0,15 %
|
|
≤ 0,15 %
|
|
|
≤ 0,3 %
|
|
|
≤ (0.0075 · r + 0.075)%
|
|
Long-term drift (temperature change ±30 °C (±54 °F))
|
≤ (0.25 · r)% every 5 years static pressure max. 70 bar g (1015 psi g)
|
≤ (0,25 % every 5 years static pressure max. 70 bar g (1015 psi g)
|
Influence of ambient temperature
|
|
|
- at -10 ... +60 °C (14 ... 140 °F)
|
|
|
- 250-mbar (3.63 psi) measuring cell
|
≤ (0.5 · r + 0.2)% (0.4 instead of 0.2 with 10 < r ≤ 30)
|
≤ 0,7 %
|
- 600-mbar (8.7 psi) measuring cell
|
≤ (0.3 · r + 0.2)% (0.4 instead of 0.2 with 10 < r ≤ 30)
|
≤ 0,5 %
|
- 1600 and 5000 mbar (23.2 and 72.5 psi) measuring cells
|
≤ (0.25 · r + 0.2) % (0.4 instead of 0.2 with 10 < r ≤ 30)
|
≤ 0,45 %
|
- at -40 ... -10 °C and +60 ... +85 °C
(-40 ... +14 °F and 140 ... 185 °F)
|
|
|
- 250-mbar (3.63 psi) measuring cell
|
≤ (0.25 · r +0.15) %/10 K double values with 10 < r ≤ 30
|
≤ 0.4 %/10 K
|
- 600-mbar (8.7 psi) measuring cell
|
≤ (0.15 · r + 0,15)%/10 K double values with 10 < r ≤ 30
|
≤ 0.3 %/10 K
|
- 1600 and 5000 mbar (23.2 and 72.5 psi) measuring cells
|
≤ (0.12 · r +0.15) %/10 K double values with 10 < r ≤ 30
|
≤ 0.27 %/10 K
|
Influence of static pressure
|
|
|
|
|
- 250-mbar (3.63 psi) measuring cell
|
≤ (0.3 · r)% per nominal pressure
|
≤ 0.3 % per nominal pressure
|
- 600-mbar (8.7 psi) measuring cell
|
≤ (0.15 · r)% per nominal pressure
|
≤ 0,15 % per nominal pressure
|
- 1600 and 5000 mbar (23.2 and 72.5 psi) measuring cells
|
≤ (0.1 · r)% per nominal pressure
|
≤ 0.1 % per nominal pressure
|
|
≤ (0.1 · r)% per nominal pressure
|
≤ 0.1 % per nominal pressure
|
Measured Value Resolution
|
-
|
3 · 10-5 of nominal measuring range
|
Rated conditions
|
|
Degree of protection (to EN 60529)
|
IP65
|
Temperature of medium
|
Note: Always take into account assignment of max. permissible operating temperature to max. permissible operating pressure of the respective flange connection!
|
- Measuring cell with silicone oil filling
|
-40 ... +100 °C (-40 ... +212 °F)
|
|
pabs ≥ 1bar: -40 ... +175 °C (-40 ... +347 °F)
pabs < 1 bar: -40 ... +80 °C (-40 ... +176 °F)
|
|
-40 ... +100 °C (-40 ... +212 °F)
-20 ... +60 °C (-4 ... +140 °F) in conjunction with dust explosion protection
|
Ambient conditions
|
|
|
|
|
-30 ... +85 °C (-22 ... +185 °F)
|
|
-50 ... +85 °C (-58 ... +185 °F)
|
|
|
|
Permissible
|
- Electromagnetic Compatibility
|
|
|
Acc. to EN 50081-1
|
|
Acc. to EN 61326 and NAMUR NE 21
|
Design
|
|
Weight (without options)
|
|
To EN (pressure transmitter with mounting flange, without tube)
|
≈ 11 ... 13 kg (≈ 24.2 ... 28.7 lb)
|
To ASME (pressure transmitter with mounting flange, without tube)
|
≈ 11 ... 18 kg (≈ 24.2 ... 39.7 lb)
|
Enclosure material
|
Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. No. 1.4408
|
Wetted parts materials
|
|
High-pressure side
|
|
- Seal diaphragm of mounting flange
|
Stainless steel, mat. No. 1.4404/316L, Monel, mat. No. 2.4360, Hastelloy B2, mat. No. 2.4617, Hastelloy C276, mat. No. 2.4819, Hastelloy C4, mat. No. 2.4610, tantalum, PTFE, ECTFE
|
Measuring cell filling
|
Silicone oil
|
Process connection
|
|
High-pressure side
|
Flange to EN and ASME
|
Low-pressure side
|
Female thread ¼-18 NPT and flange connection with mounting thread M10 to DIN 19213 or 7/16-20 UNF to EN 61518
|
Power supply
U
H
|
|
Supplied through bus
|
Terminal voltage on transmitter
|
10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode
|
-
|
Separate 24 V power supply necessary
|
-
|
No
|
Bus voltage
|
|
|
-
|
9 ...32 V
|
- With intrinsically-safe operation
|
-
|
9 ...24 V
|
Current consumption
|
|
|
-
|
12.5 mA
|
- Startup current ≤ basic current
|
-
|
Yes
|
- Max. current in event of fault
|
-
|
15.5 mA
|
Fault disconnection electronics (FDE) available
|
-
|
Yes
|
Certificates and approvals
|
|
|
Classification according to PED 97/23/EC
|
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice)
|
Explosion protection
|
|
|
PTB 99 ATEX 2122
|
|
Ex II 1/2 G EEx ia/ib IIB/IIC T6
|
- Permissible ambient temperature
|
-40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +70 °C (-40 ... +158 °F) temperature class T5; -40 ... +60 °C (-40 ... +140 °F) temperature class T6
|
|
To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 Ω
|
FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W
|
- Effective internal inductance/capacitance
|
L
i = 0.4 mH, Ci = 6 nF
|
L
i = 7 μH, Ci = 1.1 nF
|
|
PTB 99 ATEX 1160
|
|
Ex II 1/2 G EEx d IIC T4/T6
|
- Permissible ambient temperature
|
-40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6
|
|
To circuits with values: UH = 10.5 ... 45 V DC
|
To circuits with values: UH = 9 ... 32 V DC
|
- Dust explosion protection for zone 20
|
PTB 01 ATEX 2055
|
|
Ex II 1 D IP65 T 120 °C Ex II 1/2 D IP65 T 120 °C
|
- Permissible ambient temperature
|
-40 ... +85 °C (-40 ... +185 °F)
|
|
120 °C (248 °F)
|
|
To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Ω
|
FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W
|
- Effective internal inductance/capacitance
|
L
i = 0.4 mH, Ci = 6 nF
|
L
i = 7 μH, Ci = 1.1 nF
|
- Dust explosion protection for zone 21/22
|
PTB 01 ATEX 2055
|
|
Ex II 2 D IP65 T 120 °C
|
|
To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W
|
To circuits with values: UH = 9 ... 32 V DC; Pmax = 1.2 W
|
- Type of protection "n" (zone 2)
|
TÜV 01 ATEX 1696 X
|
TÜV 01 ATEX 1696 X
|
|
Ex II 3 G EEx nA L IIC T4/T5/T6
|
Ex II 3 G EEx nA L IIC T4/T5/T6
|
- Explosion protection acc. to FM
|
Certificate of Compliance 3008490
|
- Identification (XP/DIP) or (IS); (NI)
|
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
|
- Explosion protection to CSA
|
Certificate of Compliance 1153651
|
- Identification (XP/DIP) or (IS)
|
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
|