Environmental aspects
We use plastics that are halogen-free and recyclable. The paints are solvent-, cadmium- and lead-free.
Internal subdivision (separation)
Partitions increase operator safety and offer protection against the crossing of solid bodies between adjoining units.
Overvoltage category |
V |
1000/III |
---|---|---|
Rated impulse withstand voltage Uimp |
kV |
8 |
Clearance and creepage distances |
DIN VDE 0110 |
|
Rated insulation voltage Ui |
V |
1000 |
Rated operating voltage Ue |
V |
690 |
Rated current |
A |
1600, main busbars |
Short-circuit strength
|
|
|
Protective measures |
Safety class 1 (protective conductor connection) |
|
Number of conductors within the busbar run |
3, AC |
|
Degree of protection acc. to EN 60529 |
IP55, with cover for shock-hazard protection and sealed door |
|
Degree of pollution |
3 |
|
Ambient temperature |
°C |
35 (24-h mean value) |
Relative air humidity |
% |
50 at 40 °C |
Altitude |
m |
Max. 2000 (above sea level) |
Enclosures |
Rack and doors made of 2-mm sheet steel |
|
Mounting dimensions |
DIN 43870 |
|
Surface of metal components |
Electrogalvanized and powder-coated |
|
Color |
RAL 7035 light gray (further RAL colors are available upon request) |
|
Locking system |
2/4-point locking with integral espagnolette lock and double-bit key |