Order No. |
6EP1 331-2BA10 |
Product |
SITOP power |
Power supply, type |
24 V/0.5 A |
Input |
|
Input |
1-phase AC |
Voltage range |
93 … 264 V |
Supply voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note |
|
Input voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Wide-range input |
Yes |
Overvoltage resistance |
2.3 Vin rated, 1.3 ms |
Mains buffering at Iout rated, min. |
0.01 s |
Mains buffering |
at Vin = 230 V |
Rated line frequency |
|
|
50 Hz |
|
60 Hz |
Rated line range |
47 … 63 Hz |
Input current |
|
|
0.22 A |
|
0.13 A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Switch-on current limiting (+25 °C), max. |
23 A |
Duration of current limiting at 25 °C |
|
|
0.001 s |
|
|
Inrush current A s |
0.3 A ·s |
Built-in incoming fuse |
T 2 A/250 V (not accessible) |
Protection in the mains power input (IEC 898) |
Recommended miniature circuit breaker: from 3 A, characteristic C |
Output |
|
Output |
controlled, isolated DC voltage |
Rated voltage |
24 V |
Total tolerance, static ± |
3 % |
Static mains compensation, approx. |
0.2 % |
Static load balancing, approx. |
0.7 % |
Residual ripple peak-peak, max. |
0.15 V |
Residual ripple peak-peak, typ. |
0.05 V |
Spikes peak-peak, max. (bandwidth: 20 MHz) |
0.24 V |
Spikes peak-peak, typ. (bandwidth: 20 MHz) |
0.15 V |
Adjustment range min. |
|
Adjustment range max. |
|
Product feature output voltage adjustable |
No |
Output voltage setting |
- |
Note |
|
Status display |
Green LED for 24 V OK |
Signaling |
|
On/off behavior |
No overshoot of Vout (soft start) |
Startup delay, max. |
1.5 s |
Voltage rise, typ. |
0.02 s |
Voltage increase time of the output voltage maximum |
|
Rated current value Iout rated |
0.5 A |
Current range |
0 A |
Current range up to +55 °C |
0.5 A |
Note |
|
delivered active power typ. |
12 W |
short-term overload current at short-circuit during run-up typical |
|
Duration of overloading ability for excess current on short-circuiting during the start-up |
|
constant overload current at short-circuit during run-up typical |
0.6 A |
short-term overload current at short-circuit during operation typical |
|
Duration of overloading ability for excess current on short-circuiting during the operational phase |
|
constant overload current at short-circuit during operation typical |
0.6 A |
Parallel switching for enhanced performance |
No |
Note |
|
Numbers of parallel switchable units for enhanced performance |
|
Efficiency |
|
Efficiency at Vout rated, Iout rated, approx. |
74 % |
Power loss at Vout rated, Iout rated, approx. |
4.2 W |
Closed-loop control |
|
Dynamic mains compensation (Vin rated ±15 %), max. |
0.3 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. |
0.7 % |
Load step setting time 50 to 100%, typ. |
0.0015 s |
Load step setting time 100 to 50%, typ. |
0.0015 s |
Setting time maximum |
|
Protection and monitoring |
|
Output overvoltage protection |
Yes, according to EN 60950-1 |
Current limitation |
0.55 … 0.65 A |
Current limitation, typ. |
|
Characteristic feature of the output short-circuit protected |
Yes |
Short-circuit protection |
Constant current characteristic up to 0 V |
Enduring short circuit current Effective level |
|
|
0.65 A |
|
|
Note |
|
Overload/short-circuit indicator |
- |
Safety |
|
Primary/secondary isolation |
Yes |
Potential separation |
Safety extra low output voltage Vout according to EN 60950-1 and EN 50178 |
Protection class |
Class I |
stray current |
|
|
0.0035 A |
|
|
CE mark |
Yes |
UL/CSA approval |
Yes |
UL/cUL (CSA) approval |
cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289, cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 |
Explosion protection |
- |
FM approval |
No |
FM approval |
- |
CB approval |
No |
Marine approval |
- |
Degree of protection (EN 60529) |
IP20 |
EMC |
|
Emitted interference |
EN 55022 Class B |
Supply harmonics limitation |
not applicable |
Noise immunity |
EN 61000-6-2 |
Operating data |
|
Ambient temparature |
|
|
-25 … +70 °C |
Note |
with natural convection |
Ambient temparature |
|
|
-40 … +70 °C |
Ambient temparature |
|
|
-40 … +70 °C |
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
Mechanics |
|
Connection technology |
screw-type terminals |
Connections |
|
|
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm single-core/finely stranded |
|
+: 1 screw terminal for 0.5 ... 2.5 mm ; -: 2 screw terminals for 0.5 ... 2.5 mm |
|
|
Width of the housing |
0.0225 m |
Height of the housing |
0.08 m |
Depth of the housing |
0.091 m |
Installation width |
0.0225 m |
Installation height |
0.18 m |
Weight, approx. |
0.11 kg |
Product feature of the housing housing for side-by-side mounting |
Yes |
Type of fixing |
|
|
No |
|
Yes |
Type of attachment S7-300 rail mounting |
No |
Installation |
Snaps onto DIN rail EN 60715 35x7.5/15 |
Electrical accessories |
|
Mechanical accessories |