Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/new/cat.php on line 184
Order No. |
6EP1 332-1SH12 |
Product |
SITOP power |
Power supply, type |
24 V/2.5 A |
Input |
|
Input |
1-phase AC or DC |
Voltage range |
93 … 264 V |
Supply voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note |
|
Input voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
110 … 350 V |
Wide-range input |
Yes |
Overvoltage resistance |
2.3 Vin rated, 1.3 ms |
Mains buffering at Iout rated, min. |
20 ms |
Mains buffering |
at Vin = 120 V, > 80 ms (typ. 100 ms) at Vin = 187 V |
Rated line frequency |
|
|
50 Hz |
|
60 Hz |
Rated line range |
47 … 63 Hz |
Input current |
|
|
1.3 A |
|
0.7 A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Switch-on current limiting (+25 °C), max. |
33 A |
Duration of current limiting at 25 °C |
|
|
|
|
3 ms |
Inrush current A s |
3.5 A ·s |
Built-in incoming fuse |
T 3.15 A (not accessible) |
Protection in the mains power input (IEC 898) |
Recommended: 2-pole miniature circuit breaker from 10 A, characteristic B, or from 6 A, characteristic D |
Output |
|
Output |
controlled, isolated DC voltage |
Rated voltage |
24 V |
Total tolerance, static ± |
1 % |
Static mains compensation, approx. |
0.1 % |
Static load balancing, approx. |
0.2 % |
Residual ripple peak-peak, max. |
50 mV |
Residual ripple peak-peak, typ. |
40 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) |
100 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) |
40 mV |
Adjustment range min. |
|
Adjustment range max. |
|
Product feature output voltage adjustable |
No |
Output voltage setting |
- |
Note |
|
Status display |
Green LED for 24 V OK |
Signaling |
|
On/off behavior |
No overshoot of Vout (soft start) |
Startup delay, max. |
600 ms |
Voltage rise, typ. |
20 ms |
Voltage increase time of the output voltage maximum |
|
Rated current value Iout rated |
2.5 A |
Current range |
0 A |
Current range up to +55 °C |
2.5 A |
Note |
|
delivered active power typ. |
60 W |
short-term overload current at short-circuit during run-up typical |
|
Duration of overloading ability for excess current on short-circuiting during the start-up |
|
constant overload current at short-circuit during run-up typical |
2.8 A |
short-term overload current at short-circuit during operation typical |
|
Duration of overloading ability for excess current on short-circuiting during the operational phase |
|
constant overload current at short-circuit during operation typical |
2.8 A |
Parallel switching for enhanced performance |
Yes |
Note |
|
Numbers of parallel switchable units for enhanced performance |
10 |
Efficiency |
|
Efficiency at Vout rated, Iout rated, approx. |
85 % |
Power loss at Vout rated, Iout rated, approx. |
11 W |
Closed-loop control |
|
Dynamic mains compensation (Vin rated ±15 %), max. |
0.3 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. |
0.5 % |
Load step setting time 50 to 100%, typ. |
1 ms |
Load step setting time 100 to 50%, typ. |
1 ms |
Setting time maximum |
2 ms |
Protection and monitoring |
|
Output overvoltage protection |
Yes, according to EN 60950-1 |
Current limitation minimum |
|
Current limitation maximum |
|
Current limitation, typ. |
2.8 A |
Characteristic feature of the output short-circuit protected |
Yes |
Short-circuit protection |
Constant current characteristic |
Enduring short circuit current Effective level |
|
|
3 A |
|
|
Note |
|
Overload/short-circuit indicator |
- |
Safety |
|
Primary/secondary isolation |
Yes |
Potential separation |
Safety extra low output voltage Vout according to EN 60950-1 |
Protection class |
Class I |
stray current |
|
|
3.5 mA |
|
|
CE mark |
Yes |
UL/CSA approval |
Yes |
UL/cUL (CSA) approval |
cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
Explosion protection |
- |
FM approval |
No |
FM approval |
- |
CB approval |
No |
Marine approval |
- |
Degree of protection (EN 60529) |
IP20 |
EMC |
|
Emitted interference |
EN 55022 Class B |
Supply harmonics limitation |
not applicable |
Noise immunity |
EN 61000-6-2 |
Operating data |
|
Ambient temparature |
|
|
0 … 60 °C |
Note |
with natural convection |
Ambient temparature |
|
|
-25 … +85 °C |
Ambient temparature |
|
|
-25 … +85 °C |
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
Mechanics |
|
Connection technology |
screw-type terminals |
Connections |
|
|
L, N, PE: 1 screw terminal each for 2 x 0.5 ... 1.5 mm finely stranded, 2 x 0.5 ... 2.5 mm single-core |
|
L+, M: 1 screw terminal each for 2 x 0.5 ... 2.5 mm |
|
|
Width of the housing |
80 mm |
Height of the housing |
135 mm |
Depth of the housing |
120 mm |
Installation width |
80 mm |
Installation height |
335 mm |
Weight, approx. |
0.5 kg |
Product feature of the housing housing for side-by-side mounting |
Yes |
Type of fixing |
|
|
Yes |
|
Yes |
Type of attachment S7-300 rail mounting |
No |
Installation |
Snaps onto DIN rail EN 60715 35x15, wall mounting |
Electrical accessories |
|
Mechanical accessories |