Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/new/cat.php on line 184
|
6ES7 153-2BA02-0XB0 |
|
|
General information |
|
|
Vendor identification (VendorID) |
801Eh |
|
Supply voltage |
|
|
24 V DC |
Yes |
|
permissible range, lower limit (DC) |
20.4 V |
|
permissible range, upper limit (DC) |
28.8 V |
|
permissible range (ripple included), lower limit (DC) |
20.4 V |
|
permissible range (ripple included), upper limit (DC) |
28.8 V |
|
External protection for supply cables (recommendation) |
2.5 A |
|
Mains buffering |
|
|
5 ms |
|
Input current |
|
|
Current consumption, max. |
600 mA |
|
Rated value at 24 V DC |
650 mA |
|
Inrush current, typ. |
3 A |
|
I t |
0.1 A ·s |
|
Output voltage |
|
|
Rated value, 5 V DC |
Yes |
|
Output current |
|
|
for backplane bus (5 V DC), max. |
1.5 A |
|
Power losses |
|
|
Power loss, typ. |
5.5 W |
|
Address area |
|
|
Addressing volume |
|
|
244 byte |
|
244 byte |
|
Hardware configuration |
|
|
Number of modules per DP slave interface, max. |
12 |
|
Time stamping |
|
|
Accuracy |
1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules |
|
Number of message buffers |
15 |
|
Messages per message buffer |
20 |
|
Number of stampable digital inputs, max. |
128; Max. 128 signals/station; max. 32 signals/slot |
|
Time format |
RFC 1119 |
|
Time resolution |
0.466 ns |
|
Time interval for transmitting the message buffer if a message is present |
1 000 ms |
|
Time stamp on signal change |
rising / falling edge as signal entering or exiting |
|
Interfaces |
|
|
Interface physics, RS 485 |
Yes |
|
Interface physics, FOC |
No |
|
PROFIBUS DP |
|
|
1 to 125 permitted |
|
Yes |
|
70 mA |
|
RS 485 |
|
12 Mbit/s |
|
Yes |
|
Yes |
|
Yes; Sender |
|
9-pin sub D |
|
1st interface |
|
|
DP slave |
|
|
SI04801.GSG |
|
Yes |
|
Communication functions |
|
|
Bus protocol/transmission protocol |
PROFIBUS DP to EN 50170 |
|
Isolation |
|
|
Isolation checked with |
Isolation voltage 500 V |
|
Ambient conditions |
|
|
Operating temperature |
|
|
0 °C |
|
60 °C |
|
Air pressure |
|
|
3 000 m |
|
Degree and class of protection |
|
|
IP20 |
Yes |
|
Configuration |
|
|
Configuration software |
|
|
Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
|
Dimensions |
|
|
Width |
40 mm |
|
Height |
125 mm |
|
Depth |
117 mm |
|
Weight |
|
|
Weight, approx. |
360 g |
|
6ES7 197-1LB00-0XA0 |
|
|
General system features |
|
|
Requirements for DP master system |
|
|
244 byte |
|
Supply voltage |
|
|
Description |
via bus module |
|
permissible range, lower limit (DC) |
20.4 V |
|
permissible range, upper limit (DC) |
28.8 V |
|
Interfaces |
|
|
PROFIBUS DP |
|
|
|
|
12 Mbit/s; 45.45 kbit/s to 12 Mbit/s |
|
Active terminating resistor (Bus Terminator) |
|
Yes |
|
9 |
|
31; 64 when using RS 485 repeaters or OLM/OBT |
|
Protocols |
|
|
Further protocols |
|
|
Yes |
|
Interrupts/diagnostics/status information |
|
|
Status indicator |
No |
|
Alarms |
|
|
No |
|
Diagnoses |
|
|
Yes |
|
Galvanic isolation |
|
|
to lower-level DP master system |
Yes |
|
Dimensions |
|
|
Width |
40 mm |
|
Height |
125 mm |
|
Depth |
130 mm |
|
Weight |
|
|
Weight, approx. |
200 g |