Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/new/cat.php on line 184
TM54F Terminal Module

TM54F Terminal Module

6SL3055-0AA00-3BA0

Current requirement

(X524 at 24 V DC) without DRIVE-CLiQ supply

0.2 A

  • Conductor cross-section, max.

2.5 mm2

  • Fuse protection, max.

20 A

Current requirement ext. 24 V, max.

For supplying the digital outputs and 24 V sensor supply (X514 at 24 V DC)

4 A

  • Conductor cross-section, max.

2.5 mm2

  • Fuse protection, max.

20 A

I/O

  • Number of fail-safe digital inputs

10

  • Number of fail-safe digital outputs

4

  • 24 V sensor supply

3, of which 2 can be temporarily shut down using an internal test routine for dynamizing fail-safe digital inputs, current carrying capacity 0.5 A each

  • Connection system

Plug-in screw-type terminals

  • Conductor cross-section, max.

1.5 mm2

Digital inputs

According to IEC 61131 2 Type 1, with isolation

  • Voltage

-3 … +30 V

  • Low level (an open digital input is interpreted as low)

-3 … +5 V

  • High level

15 … 30 V

  • Current consumption at 24 V DC, typ.

> 2 mA

  • Delay time of digital inputs, approx.1)

  • L > H, typ.

30  s

  • H > L, typ.

60  s

  • Safe state

Low level (for inputs that can be inverted: without inversion)

Digital outputs

Sustained short-circuit strength

  • Voltage

24 V DC

  • Load current per fail-safe digital output, max.2)

0.5 A

  • Delay times (ohmic load)1)

  • L > H, typ.

300 µs

  • H > L, typ.

350 µs

  • Safe state

Output switched off

Scanning cycletSI

For fail-safe digital inputs or fail-safe digital outputs

4 ... 25 ms (adjustable)

PE connection

M4 screw

Dimensions

  • Width

50 mm (1.97 in)

  • Height

150 mm (5.91 in)

  • Depth

111 mm (4.37 in)

Weight, approx.

0.9 kg (2 lb)

Approvals, according to

cULus

Safety Integrated

Safety Integrity Level 2 (SIL2) according to IEC 61508, control category 3 according to EN 954-1


1) The specified delay times refer to the hardware. The actual reaction time depends on the time slot in which the digital input/output is processed.

2) The total current of all fail-safe digital outputs must not exceed 5.33 A.
























































  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366
Яндекс.Метрика