SITRANS P500 for fill level |
||
---|---|---|
Input |
||
Measured variable |
Level |
|
Span (infinitely adjustable) |
Span (min. ... max.) |
Maximum operating pressure |
1.25 ... 250 mbar |
See "Mounting flange" |
|
6.25 ... 1250 mbar |
||
Lower measuring limit |
||
|
-100 % of max. span or 30 mbar a (0.44 psia) vacuum resistance (available as an option) |
|
Upper measuring limit |
100% of max. span |
|
Start of scale |
Between measuring limits (infinitely adjustable) |
|
Output |
||
Output signal |
4 ... 20 mA |
|
|
3.55 mA, factory preset to 3.8 mA |
|
|
23 mA, factory preset to 20.5 mA |
|
|
Ipp 0.4 % of max. output current |
|
|
0... 100 s in steps of 0.1 s, factory-set to 2 s |
|
|
3.55 ... 23 mA |
|
|
adjustable within limits:
|
|
Load |
||
|
R
B (UH - 10.5 V)/0.023 A in , |
|
|
||
|
R B = 230 ... 1100 |
|
|
R B = 230 ... 500 |
|
Characteristic curve |
Linearly rising or linearly falling and user-specific |
|
Measuring accuracy |
||
Reference conditions |
|
|
Error in measurement at limit setting incl. hysteresis and reproducibility r: Span ratio |
||
|
||
|
0,03 % |
|
|
(0,003. r) % |
|
Long-term stability |
0.05 % per 5 years |
|
0.08 % per 10 years |
||
Influence of ambient temperature per 28 °C1)2) |
(0,01. r + 0.035) % /28°C2) |
|
Influence of static pressure |
||
|
(0,007. r ) % per 70 bar |
|
|
0.03 % per 70 bar |
|
Influence of power supply |
0.005 ... 1 V |
|
Rated conditions |
||
Mounting position |
Defined by flange |
|
Ambient conditions |
||
|
||
|
-40 ... +85 °C (-40 ... +185 °F) |
|
|
-20 ... +85 °C (-4 ... +185 °F) |
|
|
-50 ... +90 °C (-58 ... +194 °F) |
|
Climatic class |
||
|
Relative humidity 0 … 100 % (condensation permissible) |
|
Degree of protection to IEC 60529 |
IP66/IP68 and NEMA 4X (with corresponding cable gland) |
|
Electromagnetic Compatibility |
||
|
Acc. to EN 61326 and NAMUR NE 21 |
|
Permissible pressures |
According to 97/23/EC pressure equipment directive |
|
Measuring temperature (for low-pressure side) |
||
|
-40 ... +125 °C (-40 ... +257 °F) |
|
Design |
||
Weight |
||
|
approx. 9.8 … 11.8 kg (21.6 … 26.0 lb) |
|
|
approx. 9.8 … 16.8 kg (21.6 … 37.0 lb) |
|
Material of parts in contact with the medium |
||
|
||
|
Stainless steel , mat. no. 1.4404/316L, Monel 400, W-Nr. 2.4360, Hastelloy B2, mat. no. 2.4617, Hastelloy C276, mat. no. 2.4819, Hastelloy C4,mat. no. 2.4610, Tantal, PTFE, ECTFE |
|
|
Smooth to EN 1092-1, Form b1 and/or ASME B16.5 RF 125 … 250 AA for stainless steel 316L, EN1092-1 Form B2 and/or ASME B16.5 RFSF in the case of other materials |
|
|
||
|
PTFE |
|
|
copper |
|
|
||
|
Stainless steel, mat. no. 1.4404/316L |
|
|
Stainless steel, mat. no. 1.4404/316L |
|
|
|
|
Material of parts not in contact with media |
||
Electronics housing |
|
|
Process connection screws |
Stainless steel, mat. no. 1.4404/316L |
|
Measuring cell filling |
Silicone oil |
|
|
Silicone oil or other material |
|
Process connection |
||
|
Flange to EN and ASME |
|
|
-18 NPT female thread and flange connection with M10 to DIN 19213 or 7/16-20 UNF mounting thread to 61518 |
|
Electrical connection |
|
|
Displays and controls |
||
Keys |
3; for operation directly on the device |
|
Display |
|
|
Auxiliary power supply |
||
Terminal voltage on transmitter |
|
|
Certificates and approvals |
||
Classification according to PED 97/23/EC |
||
|
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) |
|
Explosion protection |
||
Explosion protection for Europe (to ATEX) |
||
|
PTB 09 ATEX 2004 X |
|
|
Ex II 1/2 G Ex ia/ib IIC T4 |
|
|
-40 ... +85 °C (-40 ... +185 °F) |
|
|
To certified intrinsically-safe circuits with peak values: |
|
|
Li = 400 µH |
|
|
Ci = 6 nF |
|
|
BVS 09 ATEX E 027 |
|
|
Ex II 1/2 G Ex d IIC T4/T6 |
|
|
-40 ... +85 °C (-40 ... +185 °F) temperature class T4; |
|
|
To circuits with values:Um = DC 10.5 ... 45 V |
|
|
PTB 09 ATEX 2004 X |
|
|
Ex II 1 D Ex iaD 20 T 120 °C |
|
|
-40 ... +85 °C (-40 ... +185 °F) |
|
|
120 °C (248 °F) |
|
|
To certified intrinsically-safe circuits with peak values: |
|
|
Li = 400 µH |
|
|
Ci = 6 nF |
|
|
BVS 09 ATEX E 027 |
|
|
Ex II 2 D Ex tD A21 IP68 T120 °C Ex ia D21 |
|
|
To circuits with values:UH = 10.5 ... 45 V DC;Pmax = 1.2 W |
|
|
PTB 09 ATEX 2004 X |
|
|
Ex II 3 G Ex nA II T4/T6 |
|
|
Um = 45 V DC |
|
|
Ui = 45 V |
|
|
Li = 400 µH |
|
|
Ci = 6 nF |
|
Explosion protection for USA (acc. to FM) |
||
Certificate of Compliance |
No. 3033013 |
|
|
XP CL I, DIV 1, GP ABCDEFG T4 / T6 CL I, Zone 0, AEx ia IIC T4 |
|
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) |
|
|
According to “control drawing”: A5E02189134N |
|
|
NI CL I, DIV 2, GP ABCD T4/T6 |
|
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) |
|
|
According to “control drawing”: A5E02189134N |
|
Explosion protection for Canada (according toCCSAUS) |
||
Certificate of Compliance |
No. 2280963 |
|
|
CL I, DIV 1, GP ABCD T4 /T6; |
|
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) |
|
|
According to "control drawing": |
|
|
CL I, Ex ia/Ex ib IIC, T4 |
|
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) |
|
|
Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 , Li = 400 µH, Ci = 6 nF |
|
|
CL I, DIV 2, GP ABCD T4/T6 |
|
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) |
|
|
According to “control drawing”: A5E02189134N |
|
|
According to “control drawing”: A5E02189134N |
|
Explosion protection for China (acc. to NEPSI) |
||
1) The information only applies to the basic device. The temperature error of the remote seal is to be considered separately as shown in the table.
2) If the Type "D" measuring cell is used, the error should be increased by a factor of 5. This error can be reduced to 0 by a means of a zero adjustment.
HART communication |
|
---|---|
Load with connection of |
|
|
R B = 230 ... 1100 |
|
R B = 230 ... 500 |
Cable |
2 wire shielded: 3.0 km (1.86 miles), |
Protocol |
HART Version 6.0 |
PC/laptop requirements |
IBM compatible, RAM > 32 MB, |
Software for computer |