The pressure transmitters of the SITRANS P DS III series, can be used in industrial areas with extreme chemical and mechanical loads. Electromagnetic compatibility in the range 10 kHz to 1 GHz makes the DS III pressure transmitters suitable for locations with high electromagnetic emissions.
Pressure transmitters with type of protection "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The pressure transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX).
Pressure transmitters with the type of protection "Intrinsic safety" for use in zone 0 may be operated with power supply units of category "ia" and "ib".
The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances.
The pressure transmitter can be operated locally over 3 control keys or programmed externally over HART or over PROFIBUS PA or FOUNDATION Fieldbus interface (only DS III).
SITRANS P, DS III series
Measured variable: Gauge pressure of aggressive and non-aggressive gases, vapors and liquids.
Span (infinitely adjustable)
for DS III with HART: 0.03 ... 16 bar g (0.433 ... 232 psi g)
Nominal measuring range
for DS III with PROFIBUS PA and FOUNDATION Fieldbus: 1 ... 16 bar g (14.5 ... 232 psi g)
SITRANS P300
Span (infinitely adjustable)
for DS III with HART: 0,03 ... 16 bar g (0.433 ... 232 psi g)
Nominal measuring range
for DS III with PROFIBUS PA and FOUNDATION Fieldbus: 1 ... 16 bar g (14.5 ... 232 psi g)